Movement Accommodation in a Large Open Area

ACT Large Format Tile · Put your knowledge to work in context.

All case studies

Movement Accommodation in a Large Open Area

A contractor is installing 24" x 24" porcelain tile in a 40' x 60' commercial lobby over a concrete slab. The slab has control joints at 20' intervals in both directions. The contractor plans to install tile directly over the control joints with a standard modified thinset and no movement joints. The building will experience temperature fluctuations from 65°F to 85°F. The tile is installed with 1/8" grout joints. The contractor argues that the control joints in the slab will prevent cracking and that the tile will be fine because it's porcelain.

1. Evaluate the contractor's plan regarding movement accommodation. What are the risks and what does industry standard require?

Read the worked answer

The contractor's plan is inadequate. Industry standards (TCNA EJ171, ANSI A108.01) require movement accommodation joints (expansion joints) in tile installations to accommodate substrate movement, thermal expansion, and moisture changes. Tile must not be installed directly over control joints; instead, these joints must be honored through the tile layer with a movement joint. Additionally, the large area (40'x60') requires perimeter movement joints and intermediate movement joints at intervals (typically 20-25' for interior, depending on conditions). Without movement joints, the tile will likely crack or debond due to stress from slab movement and thermal expansion. Porcelain is not immune; it has a low coefficient of expansion but still requires accommodation. The contractor should install movement joints over all control joints, at the perimeter, and at intermediate intervals (e.g., every 20-25'). The joints should be filled with a flexible sealant (e.g., ASTM C920) and not grout.

2. Describe how you would design the movement joint layout for this lobby.

Read the worked answer

The movement joint layout should include: (1) joints directly over all existing control joints in the slab (at 20' intervals), extending full width and depth through the tile and setting bed; (2) perimeter joints at all walls and columns (typically 1/4" to 3/8" wide); (3) intermediate joints to divide the large field into smaller sections, typically at 20-25' intervals for interior installations. Given the 40'x60' area, the control joints already divide the slab into 20'x20' panels, so honoring those joints provides a grid of movement joints. However, the field between control joints is 20'x20', which is within the 20-25' recommendation, so additional intermediate joints may not be necessary if the control joints are honored. The joints should be at least 1/4" wide (or as specified by the sealant manufacturer) and filled with a flexible sealant meeting ASTM C920. The tile layout should be planned so that movement joints align with the control joints and are not obscured by tile. The contractor must also ensure that the setting bed and tile are isolated from the slab at the joints (e.g., using a bond breaker tape).