DCEP: Cooling Systems and Airflow Management

DCEP · Work through your exam, one topic at a time.

All guide sections

Cooling Systems and Airflow Management

What this domain tests

Cooling is where most efficiency opportunity lives. Questions test your grasp of airflow physics, containment, setpoints, and the trade-offs between air- and liquid-based approaches.

Core concepts to know:

  • Airflow management: hot-aisle/cold-aisle layout, blanking panels, brush seals, and containment (hot or cold aisle). Bypass airflow and recirculation are the two failure modes; containment addresses both.
  • Temperature setpoints and ASHRAE guidance: the allowable and recommended envelopes for inlet temperature and humidity. Raising the supply setpoint within the recommended range reduces compressor lift and economizer hours.
  • Economizers: air-side and water-side free cooling; effectiveness depends on climate and hours available.
  • Part-load performance: chillers, CRAH fans, and pumps follow affinity laws - fan power scales roughly with the cube of speed, so variable-speed control yields large savings.
  • Liquid cooling: direct-to-chip and immersion for high-density racks where air cannot economically remove heat.
  • Airflow metrics: rack inlet temperature uniformity, return air temperature, and CFM per kW.

Traps to watch:

  • Recommending setpoint increases without checking that all rack inlets stay within the recommended envelope - the coldest inlet is not the constraint, the hottest is.
  • Forgetting that containment must be paired with blanking and grommets to be effective.
  • Assuming economizer hours from outdoor temperature alone, ignoring humidity limits.
  • Treating fan affinity as linear rather than cubic.

Worked example

A CRAH fan runs at 100% and draws 10 kW. Reducing speed to 80% via VFD control gives power ≈ 10 × (0.8)³ = 5.1 kW, roughly half. That is the affinity-law rule of thumb: an 80% speed cut saves about 50% of fan power.