A client wants you to reuse unknown existing cable

ACMA Restricted Cabling Registration Exam · Put your knowledge to work in context.

All case studies

A client wants you to reuse unknown existing cable

You are asked to add six new outlets to a small legal office. The building was fitted out about twelve years ago and there is an existing comms cabinet with a patch panel. The client says the existing cable is "all Cat 5e" and wants you to reuse spare pairs and spare cables where possible to save money. On inspection, the cable jacket markings are worn and unreadable on several runs. Two existing cables are stapled to timber studs and pass within 20 mm of a mains cable for about 3 m. One existing outlet has a crack in the faceplate. The client wants the new outlets to match the existing ones and wants the job done in one day.

1. How do you handle the unmarked existing cable?

Read the worked answer

You cannot assume the existing cable is Cat 5e, or any category, from the client's recollection. Unreadable jacket markings mean the cable's performance is unknown, and reusing it for new outlets would mean certifying cable you cannot verify.

Options: trace the runs and see if any section of jacket is legible; if not, treat the cable as unknown. You can either replace the runs you intend to use for the new outlets, or test the existing links and, if they pass the required category tests, document that the performance was verified by test rather than by marking. Testing gives evidence, but you should still record that the cable is unidentified and that the result is based on test only.

Do not connect new outlets to unidentified cable and present the result as a known-category installation.

2. What do you do about the stapled cable near the mains and the cracked faceplate?

Read the worked answer

The stapled cable is a problem for two reasons. Staples compress the cable and distort the pair geometry, which degrades performance, and the proximity to the mains cable for 3 m creates a separation issue. If the cable is to be reused, it should be re-routed off the staples and given proper separation from the mains, or replaced.

The cracked faceplate should be replaced. A cracked faceplate is a physical hazard and can let dust and moisture in, and it looks like a defect the client will blame on you later. Replace it with a matching outlet.

These are existing defects, not caused by your work. Document them, tell the client, and either remediate them as part of the job or record that the client declined remediation. Do not silently leave them and then certify the whole installation.

3. The client insists the job be done in one day. How do you respond?

Read the worked answer

The schedule is the client's to set, but the scope and testing are yours to define. If the day does not allow for proper routing, termination, and testing of six outlets plus remediation of the existing defects, you should say so and propose a realistic plan.

One approach: complete the new outlets and their testing first, and schedule remediation of the existing runs separately. Another: reduce scope, for example by installing the new outlets on new cable rather than reusing unknown cable, which removes the tracing and testing uncertainty.

What you should not do is skip testing or certify untested work to meet the deadline. Explain the risk in plain terms: untested links fail later, and the cost of a return visit exceeds the cost of the extra time now.