Escalator Inspection Findings at a Transit Station

TSSA EDM-A Exam · Put your knowledge to work in context.

All case studies

Escalator Inspection Findings at a Transit Station

You are performing the periodic inspection on a 20-year-old escalator in a busy transit station. It runs at 0.5 m/s, 32-degree incline, and carries about 12,000 people per day. Measurements: skirt-panel-to-step clearance is 6 mm on the left side near the lower comb; two comb teeth are missing at the lower landing; handrail speed measures 0.52 m/s; brake stopping distance with rated load is 1.4 m, while last year’s test record shows 0.95 m; several step demarcations are worn; the step chain shows visible elongation marks and the tension carriage is near its adjustment limit. The station manager says the escalator cannot be shut down during rush hour and asks you to “note it and come back Monday.” It is Friday 07:00.

1. Which findings require immediate removal from service, and why?

Read the worked answer

I would remove the escalator from service now. Missing comb teeth and a 6 mm skirt-panel clearance are direct entrapment hazards at the lower landing, where passengers step on and off. The brake stopping distance has increased from 0.95 m to 1.4 m with rated load, a roughly 47% increase; that is not normal wear and must be treated as a brake deficiency until proven otherwise. The step chain is showing elongation and the tension carriage is near its limit, which raises derailment risk. The handrail speed is about 4% above step speed, outside the normal code tolerance, and must be corrected, though it is not the first priority. Worn step demarcations are a lesser defect. The combination of entrapment, braking, and derailment indicators means the escalator cannot be left running for rush hour. I would stop it, place barriers at both landings, tag the control, and notify the station manager and my supervisor in writing.

2. What measurements and tests would you require after repair?

Read the worked answer

After repair, measure rather than visually accept. Check comb teeth and comb alignment, skirt-panel clearance on both sides through the step travel, and step-to-skirt clearance. Measure step chain elongation and confirm the tension carriage is within its adjustment range. Perform the brake test with rated load and compare the stopping distance with the code limit and the historical baseline. Measure handrail speed against step speed and correct the drive or tension as needed. Check for missing or damaged steps, worn demarcations, lighting, and the lower and upper landing plates. Operate the escalator through several complete cycles and observe for tracking, vibration, and unusual noise. Record every measurement and the test conditions. The escalator should not be returned to public service until the brake, chain, comb, and skirt results are within tolerance and the records are complete.

3. How do you handle the manager’s pressure and document the decision?

Read the worked answer

I would explain that the defects are not cosmetic and that keeping the unit running would expose passengers to entrapment and brake failure. The manager’s staffing problem does not change the code obligation. I would shut down the escalator, erect barriers, apply a tag, and record the time, findings, and measurements. I would notify my supervisor and the owner in writing the same day, listing each deficiency and the reason for removal. I would not agree to “come back Monday” while the unit remains in service. If the manager attempts to restart it, I would escalate to TSSA. A formal incident report is not automatically required for a defect found during inspection, but the maintenance and inspection records must show what was found and when the unit was removed. Return to service requires a signed record of corrected measurements and passed tests.