Standpipe Pressure on the Third Floor

Chicago Firefighter · Put your knowledge to work in context.

All case studies

Standpipe Pressure on the Third Floor

You are the operator on Engine 42 at a four-story brick warehouse, 60 feet tall. A fire on the third floor has been located by the attack team, and the division chief has ordered a standpipe operation. The standpipe connection is at street level. The attack line is 100 feet of 1¾-inch hose with a 150-gpm fog nozzle; nozzle pressure should be 50 psi. The department's friction-loss card lists 35 psi per 100 feet for this hose at 150 gpm. The standpipe and the 2½-inch supply line have a combined loss of 20 psi at this flow. The third-floor outlet is about 30 feet above the pump. Your apparatus is a 1,500-gpm pump with a relief valve set at 150 psi. You charge the line; the pump discharge gauge reads 90 psi, and the nozzle firefighter radios that the stream is weak.

1. Calculate the pump discharge pressure needed at the engine. Show each component and the arithmetic.

Read the worked answer

Use the standard pump-operations relationship:

PDP = nozzle pressure + hose friction loss + appliance/standpipe loss + elevation loss

  • Nozzle pressure: 50 psi.
  • Attack-line friction loss: 100 feet at 35 psi per 100 feet = 35 psi.
  • Standpipe and supply loss: 20 psi given for this flow.
  • Elevation: 3 floors above street × 5 psi per floor = 15 psi. (Using 0.434 psi per foot for 30 feet gives about 13 psi; department practice uses 5 psi per floor, so 15 psi is the expected answer.)

PDP = 50 + 35 + 20 + 15 = 120 psi.

The gauge reading of 90 psi is therefore about 30 psi below what the nozzle needs. That explains the weak stream. I would not simply assume the gauge is wrong; I would verify the components. If the fire were on the fourth floor, the elevation component would become 20 psi and the required PDP would be 125 psi, assuming the same hose and appliance losses.

2. The gauge reads 90 psi and the nozzle team reports low pressure. List the likely causes in order of probability and the checks you would make from the pump panel. State what you would not do.

Read the worked answer

Likely causes, most probable first:

  1. Dry standpipe still filling or air-bound. The pre-plan says the system is dry, so water must displace air before full pressure reaches the outlet.
  2. Discharge valve not fully open. A partially open valve acts like a restrictor.
  3. Kink or partial obstruction in the attack line.
  4. Throttle not advanced enough for the required flow.
  5. Leak or open drain at the standpipe connection.
  6. Gauge error or a standpipe pressure-reducing valve limiting pressure.

Checks from the panel: advance the throttle slowly while watching the discharge gauge; confirm the discharge valve is fully open; radio the nozzle and ask for a pressure report; ask the nozzle team to check for kinks; verify the standpipe connection is tight and the drain is closed; compare the panel gauge with a second gauge if available.

What I would not do: I would not slam the throttle open to 'make the gauge read right.' That can cause water hammer, overpressure the standpipe, or injure the nozzle team when air and water surge. I would not leave the pump panel to investigate personally, because the engineer must stay with the pump and radio traffic.

3. Why does the fact that the standpipe is a dry system matter, and how should you charge it differently?

Read the worked answer

A dry standpipe is full of air. When water is introduced, it compresses and pushes air ahead of it, so pressure at the outlet may lag behind the pump gauge and the stream may sputter or run weak until the air is bled off. The line can also surge when the air pocket clears.

Charging procedure: open the discharge valve slowly rather than fully and abruptly; watch the gauge for a pressure drop followed by a rise; keep radio contact with the nozzle team and have them bleed air at the outlet if the nozzle design allows; bring the pressure up to the calculated 120 psi gradually; and be ready to adjust if the standpipe has a pressure-reducing device. Charging slowly protects the crew from water hammer and gives the operator time to see whether the system is leaking or blocked.