Control systems and automation: sensors, actuators, open/closed loop, PLCs and robotics
This domain tests whether you can describe a control loop, choose a sensor from its specifications, explain what a PLC does in each scan and justify a robot morphology. Expect questions on sensor characteristics, PID behaviour, PLC I/O and degrees of freedom.
Sensors and actuators
- Key specifications: range, sensitivity (Δoutput/Δinput), resolution (smallest detectable change), precision, accuracy, linearity, hysteresis, response time.
- Typical sensors: PT100, thermocouple, thermistor; potentiometer, encoder, inductive and limit switches; pressure, flow and level sensors; photoelectric cells.
- Actuators: DC/AC motors, stepper, servo, solenoid valves, cylinders, heaters.
Open and closed loop
- Open loop does not measure the output; it is valid only for stable, predictable processes.
- Closed loop uses feedback: error e = setpoint − measured value. On/off control uses hysteresis; proportional (K_p) acts on the present error, integral removes steady-state error, derivative anticipates and damps oscillation.
PLCs and robotics
- Scan cycle: read inputs → execute the program → update outputs. Scan time limits the response speed.
- Digital I/O (24 V DC) and analogue I/O (0–10 V, 4–20 mA); addressing %I, %Q, %M.
- Robotics: degrees of freedom, prismatic and rotational joints, workspace, end effector, repeatability versus accuracy, and morphologies (Cartesian, SCARA, anthropomorphic).
Worked example
A 0–10 bar pressure transmitter gives 4–20 mA. Sensitivity = 16 mA/10 bar = 1.6 mA/bar. A reading of 12 mA means (12 − 4)/1.6 = 5 bar. If it were a 0–20 mA signal, 12 mA would mean 6 bar: the 4 mA live zero is what allows a broken wire (0 mA) to be detected. With a 10-bit ADC over 0–10 V, the resolution is 10/1024 ≈ 9.8 mV.
Marks lost
- Confusing resolution with sensitivity, or precision with accuracy.
- Claiming a PID loop is open loop.
- Ignoring the 4 mA offset when converting current to pressure.
- Getting the scan-cycle order wrong.
- Confusing repeatability (spread when repeating) with accuracy (closeness to the true value).
- Quoting a sensitivity without units.