Common Venting and Combustion Air for a Condensing Boiler and Draft-Hood Water Heater

IAPMO UMC MPE · Put your knowledge to work in context.

All case studies

Common Venting and Combustion Air for a Condensing Boiler and Draft-Hood Water Heater

A 100,000 Btu/h condensing boiler, Category IV, and a 50,000 Btu/h natural-draft water heater are installed in a 10 ft by 12 ft mechanical room with a 7 ft ceiling. The room has two louvered openings to a corridor: one 12 in by 12 in opening 6 in above the floor and one 12 in by 12 in opening 6 in below the ceiling. Each louver has 75 percent free area. The boiler is vented with 2-in PVC through a sidewall. The contractor proposes to connect the water heater draft hood to the same PVC vent with a wye fitting. The water heater's existing vent is a 6 in by 8 in masonry chimney with a 10-ft exterior offset. The building official has asked for a combustion-air and venting evaluation before issuing the permit.

1. Determine whether the two openings provide adequate combustion air. Show volume and opening calculations and state the assumption about the corridor.

Read the worked answer

Room volume = 10 x 12 x 7 = 840 ft^3. For 150,000 Btu/h total input, the unconfined-space threshold is 50 ft^3 per 1,000 Btu/h = 7,500 ft^3, so the room is a confined space. Two permanent openings: each opening = 1 in^2 per 4,000 Btu/h = 37.5 in^2. Each 12 x 12 louver has 144 in^2 gross and 75% free area = 108 in^2, so the opening area appears adequate. However, the openings connect to a corridor, not directly outdoors. If the corridor does not freely communicate with outdoors, the indoor-air method applies: 1 in^2 per 1,000 Btu/h = 150 in^2 free area per opening, and 108 in^2 is insufficient. The AHJ must determine whether the corridor qualifies as outdoor air; otherwise, enlarge the openings or provide direct outdoor air.

2. Can the water heater be common-vented with the condensing boiler? Explain.

Read the worked answer

No. A Category IV condensing boiler is positive-pressure and produces acidic condensate; a natural-draft water heater with a draft hood is negative-pressure and relies on dilution air. Common venting is limited to appliances of the same category and listed for common venting; the boiler manufacturer's instructions will almost certainly prohibit it. Connecting the draft hood to the PVC vent would create spillage at the draft hood, possible condensate damage, and unsafe flue-gas release. The water heater needs a separate vent sized per its listing and the UMC vent tables. The boiler's sidewall PVC termination also needs to meet clearance and condensate-management requirements.

3. The contractor proposes a 4-in PVC liner in the masonry chimney for the water heater. Evaluate.

Read the worked answer

PVC is not acceptable as a liner for a natural-draft water heater. PVC is limited to low flue-gas temperatures (roughly 140 F or per listing), while natural-draft flue gases can be much hotter. A masonry chimney that is not gastight needs a listed liner; use a properly sized stainless-steel or other listed metal liner, installed with the required clearance, support, and termination. The 4-inch size may or may not be correct; verify against the vent tables for the appliance input, height, and connector rise. The boiler's sidewall PVC vent is a separate Category IV system and should not be connected. The chimney's exterior offset may also affect draft and needs to be included in the vent sizing.