WBCHSE HS Vocational Power · Work through your exam, one topic at a time.

All guide sections

Power Generation, Transmission and Distribution

Power Generation, Transmission and Distribution

This domain tests how electricity is generated, why it is transmitted at high voltage, and how it reaches low-tension consumers through substations and feeders.

Core rules

  • Generation: thermal (coal, steam turbine), hydro (potential energy), nuclear (fission heat), solar PV and wind, each with different capital cost, running cost and load-following behaviour.
  • Transmission voltages in India include 132, 220, 400 and 765 kV AC, with HVDC for very long bulk corridors. ACSR conductors are standard; bundled conductors reduce corona and reactance.
  • For the same power, raising voltage lowers current (P = √3 V I cos φ), reducing I²R loss and conductor size.
  • Distribution: 33/11 kV substations step down to 11 kV feeders; distribution transformers give 400 V three-phase and 230 V single-phase.
  • Radial, ring-main and interconnected systems differ in reliability and cost.
  • Load factor = average load / maximum demand; diversity factor = sum of individual maxima / maximum demand on the system.

Worked example

A balanced three-phase load of 100 kW operates at 400 V and 0.8 power factor lagging. Find the line current. I = P/(√3 × V × cos φ) = 100 000/(1.732 × 400 × 0.8) = 100 000/554.2 = 180.4 A. If power factor were corrected to 0.95, current would fall to about 152 A, cutting cable and transformer loading without changing the useful kW.

Traps that cost marks

  • Using 400 V as a phase voltage; in a 400 V star system the phase voltage is 231 V.
  • Omitting cos φ from the three-phase current formula.
  • Confusing kW (real), kVA (apparent) and kvar (reactive).
  • Claiming high-voltage transmission reduces loss by reducing resistance; it reduces current, and loss falls as I²R.
  • Mixing up transmission and distribution voltage levels in India.