InterNACHI Certified Radon Tester · Put your knowledge to work in context.

All case studies

A 1.1-Inch U-Tube and a 4.9 Upstairs

A homeowner hires a contractor to fix a 7.2 pCi/L basement reading in a 1970s split-level with a block-wall foundation, a sump pit with a perforated liner, and a forced-air furnace whose return duct runs through the basement. The contractor drills one suction point in the slab near the sump, pipes it to a 3-inch PVC stack with an inline centrifugal fan, and seals the sump lid with silicone. The u-tube reads 1.1 inches of water column. A 48-hour post-mitigation test returns 1.5 pCi/L in the basement and 4.9 pCi/L in an upstairs bedroom. The homeowner reports the system is noisy and has been switching the fan off at night. The contractor offers a written "lifetime guarantee of 2 pCi/L" and says the upstairs number "doesn't count because the system is a basement system." The house also has a second slab section under a 1990s addition with no suction point.

1. Why is the upstairs bedroom reading higher than the basement after mitigation? Work through the likely causes.

Read the worked answer

Several causes, and the fan being switched off is the first.

Fan off at night. Sub-slab depressurization works only while the fan runs. A homeowner turning it off overnight means the house is unmitigated during the hours when stack effect is strongest - exactly when the 4.9 would be expected to appear.

Pressure-field extension. One suction point near a sump in a block-wall foundation, plus a 1990s addition slab with no suction point at all, is a design that may never have reached the addition or the far side of the block walls. A 1.1-inch u-tube reading proves the fan is moving air; it does not prove the vacuum reaches the whole slab. Hollow block walls often need dedicated wall depressurization. One suction point is a starting point, not a guaranteed field.

The basement return duct. A forced-air return in the basement can depressurize that space relative to the soil and can pick up soil gas and distribute it upstairs. That produces exactly this pattern: a low basement and an elevated bedroom. Duct sealing and return placement matter.

The perforated sump liner. Sealing the lid helps only if the pit itself is under suction; an open, perforated liner can short-circuit the field.

Conclusion: this is not a completed mitigation, and the diagnosis comes before adding equipment.

2. Evaluate the contractor's "lifetime guarantee of 2 pCi/L" and the claim that the upstairs result "doesn't count."

Read the worked answer

Both statements are wrong.

"Upstairs doesn't count" is false. Post-mitigation testing is performed in the lowest livable level of the home, but an occupied bedroom is a living space. A system that leaves 4.9 pCi/L where someone sleeps has not done its job. Occupants do not live in the sump.

A "lifetime guarantee of 2 pCi/L" is a marketing claim, not a standard. ANSI/AARST SGM-SF expects guarantees to be in writing, to state specific performance criteria and the conditions under which they are verified - fan operating, closed-house conditions, which locations, what timeframe - and to be tied to a valid post-installation test. An unconditional lifetime number with no testing conditions attached is not something a certified professional should sign, because radon levels in a house change with weather, occupancy, and building modifications.

Worth checking independently: whether the contractor holds current certification through NRPP or NRSB, whether state licensure applies, whether the fan is listed for radon service, and whether a permit or inspection was required.

The tester's role is to report measurements, not to referee a contract - but these claims belong in the written report as observations, because the homeowner will rely on them.

3. What should the post-mitigation report and recommendations contain?

Read the worked answer

The report should contain:

  • Method and device, location by location, with dates and duration.
  • System status during the test - and here, the fact that the homeowner reported switching the fan off at night, which means the system was not operating continuously during the measurement.
  • Both results, labeled by location, with the basement identified as the lowest livable level and the bedroom identified as an occupied space.
  • Diagnostic observations: no documented pressure-field verification, one suction point serving two slab sections, a basement return duct, a perforated sump liner.
  • A clear conclusion that the home does not meet the 4 pCi/L action level on the basis of the upstairs result, and that the system needs corrective work.
  • Recommendations: run the fan continuously; have a qualified mitigation professional perform pressure-field diagnostics and add suction and/or block-wall depressurization and duct sealing as needed; re-test at least 24 hours after corrective work with the system running; then test periodically - annually, and at minimum every two years per EPA guidance.

I would not issue a clearance. The 1.5 in the basement is real, but it is not the number that matters to the people sleeping upstairs, and a clearance report based on it would mislead the homeowner about the house they are living in.