Craftsman Smart Factory: Industrial Networks, Connectivity, and Data Acquisition

Craftsman Smart Factory · Work through your exam, one topic at a time.

All guide sections

Industrial Networks, Connectivity, and Data Acquisition

This domain tests network segmentation, industrial protocol selection, deterministic behavior, and reliable data acquisition from controllers to historians and cloud services.

Core rules

  • Segment by Purdue level and by function. A DMZ between IT and OT prevents direct enterprise-to-controller traffic.
  • Modbus TCP is simple request/response and has no built-in authentication or encryption; protect it with conduits and compensating controls.
  • PROFINET and EtherNet/IP are fieldbus/control protocols; OPC UA provides structured, secure client/server and publish/subscribe data exchange; MQTT is lightweight publish/subscribe, and Sparkplug B adds state awareness and payload structure.
  • Real-time closed-loop control stays on deterministic wired networks. Wi-Fi, public cloud, and best-effort routing are for supervisory or analytical traffic, not motion or interlock control.
  • Acquisition design must define polling rate, deadband, timestamp source, buffering, and time synchronization (NTP or PTP).

Worked example

An ERP system needs work orders from MES, while a cloud dashboard needs machine temperature. Do not connect ERP directly to a PLC. Place MES and the historian at Level 3, an MQTT broker or OPC UA gateway in the Level 3.5 DMZ, and allow only required flows: OPC UA from Level 3 to the DMZ, MQTT over TLS from the DMZ to cloud, and no inbound sessions from Level 4 to Level 2. The reasoning is blast-radius reduction: each conduit carries only the protocol, direction, and data needed for the use case.

Traps

Assuming Modbus has security; polling every tag at maximum rate and overloading controllers; using a cloud broker for control loops; omitting buffering during network outages; and confusing OPC UA with a fieldbus.

Key points

  • Use Purdue-level segmentation and a DMZ.
  • Match protocol to purpose: control, supervisory, or cloud.
  • Protect legacy protocols with conduits and compensating controls.
  • Define polling, deadband, timestamps, and buffering explicitly.