Massachusetts Low Voltage Practice: Communications Circuits and Community Antenna/Broadband Systems (NEC Articles 800 and 820)

Massachusetts Low Voltage Practice · Work through your exam, one topic at a time.

All guide sections

Communications Circuits and Community Antenna/Broadband Systems (NEC Articles 800 and 820)

What this domain tests

Article 800 covers communications circuits such as telephone and data; Article 820 covers community antenna and broadband/CATV systems. The exam tests cable substitution, separation from power, primary protection, and grounding and bonding of incoming metallic communications and coaxial cables.

Core rules

  • Communications cable markings: CM general, CMR riser, CMP plenum. CATV cable uses similar CATV, CATVR, and CATVP designations.
  • Do not substitute a lower-rated cable for the environment. Plenum spaces require CMP or CATVP; risers require CMR or CATVR.
  • Communications circuits must be separated from power conductors per Article 800 and 820 unless a barrier or listed method permits.
  • Incoming communications and CATV cables with metallic members generally require primary protection and bonding to the building grounding electrode system. The shield of coaxial cable is bonded, not left floating.
  • Grounding blocks and protectors must be listed and accessible.

Worked example

A Cat 6 cable is routed through a return-air plenum above a ceiling. CM cable is not acceptable; use CMP. A coaxial CATV drop enters the building and connects to a splitter. The coaxial shield must be bonded to the grounding electrode system through a listed grounding block, and the cable must maintain separation from power.

Traps

  • Using CM cable in a plenum because it is just data.
  • Sharing a raceway with power without a barrier.
  • Leaving the CATV shield unbonded.
  • Confusing Article 800 data cable with Article 725 Class 2 cable.