40 hp Motor Branch Circuit, Overload, and Short-Circuit Protection

ME Electrician · Put your knowledge to work in context.

All case studies

40 hp Motor Branch Circuit, Overload, and Short-Circuit Protection

A 40 hp, 480 V, 3-phase, 1,750 rpm TEFC motor drives a conveyor in a paper mill. The nameplate reads 50 A, 1.15 service factor, 40°C ambient, 75°C rise, code letter G. The branch circuit is 150 ft of 6 AWG THHN copper in EMT from a 480 V MCC. Terminals are rated 75°C. The starter has a Class 20 overload relay with a 45-65 A range, currently set at 55 A. The engineer specifies a 150 A inverse-time circuit breaker for short-circuit and ground-fault protection. The motor is not hermetic, not a fire pump, and not multi-speed. Available fault current at the MCC is 22 kA. The electrician asks whether the conductor, overload setting, and breaker are acceptable, and whether voltage drop is a concern.

1. Is the 6 AWG THHN conductor acceptable for the motor branch circuit? Show the sizing and any ambient correction.

Read the worked answer

Use the motor FLC from Table 430.250, not the nameplate, for branch-circuit conductors: 40 hp at 480 V is 52 A. 430.22 requires 125% of FLC: 52 × 1.25 = 65 A. 6 AWG Cu THHN has a 90°C ampacity of 75 A and a 75°C ampacity of 65 A. With 75°C terminals, the termination limit is 65 A, so 6 AWG is exactly at the minimum before ambient correction. If the actual ambient at the conductors is 40°C, apply the correction factor: the 75°C ampacity becomes about 57 A, or even using the 90°C column the corrected ampacity is about 68 A but still limited by the 75°C termination; the installation is marginal and likely noncompliant. Use 4 AWG Cu (75°C ampacity 85 A; corrected about 75 A) or reduce the ambient. Verify the equipment grounding conductor and the MCC terminals.

2. Is the Class 20 overload relay set at 55 A acceptable? How should it be set?

Read the worked answer

Overload protection is based on the motor nameplate, not the table FLC. With a 1.15 service factor, 430.32(A)(1) permits the overload device to be selected at no more than 125% of nameplate current: 50 × 1.25 = 62.5 A. The Class 20 relay range 45–65 A can be set up to 62.5 A. A setting of 55 A is not a code violation because it is below the maximum, but it is likely to cause nuisance tripping on a conveyor with a high-inertia start. Set it to 60 A or 62.5 A if starting current requires, but do not exceed 62.5 A without the applicable 430.32 exception. Confirm the relay is listed for the motor and that the actual nameplate current is 50 A.

3. Is the 150 A inverse-time breaker acceptable, and is voltage drop a concern?

Read the worked answer

Short-circuit and ground-fault protection for a standard inverse-time breaker is 250% of FLC under 430.52: 52 × 2.50 = 130 A. 130 A is not a standard rating; 430.52(C)(1) Exception No. 1 permits the next higher standard rating, 150 A, if the 250% value does not correspond to a standard size, and 150 A is 288% of FLC, within the 400% ceiling. The breaker must also have an interrupting rating at least equal to the 22 kA available fault current. Voltage drop: for 150 ft of 6 AWG Cu at 50 A, 480 V three-phase, VD ≈ 1.732 × 50 × 0.491 × 150 / 1000 ≈ 6.4 V, about 1.3%; that is acceptable for most industrial motors, although the NEC does not mandate a specific voltage-drop limit. The 150 A breaker is acceptable only if the conductor and starter are protected as required and the breaker is listed for the available fault current.