Remote Air-Cooled Ice Machine Low Production

NATE CR Service · Put your knowledge to work in context.

All case studies

Remote Air-Cooled Ice Machine Low Production

A remote air-cooled 500 lb/day ice machine (R-404A) produces about 200 lb/day. The machine is rated at 500 lb/day at 70°F air and 50°F water; current conditions are 85°F air and 70°F water. The harvest cycle lasts 4 minutes instead of the normal 1.5 minutes. The ice slab is thin and cloudy. The water trough has scale, and the water pump is noisy. Condenser ambient is 85°F, and the condenser coil is clean. Suction pressure during freeze is 28 psig, head pressure 230 psig. The machine uses a hot-gas harvest solenoid. The water inlet filter was last changed 14 months ago. The technician notices the purge valve discharges a large volume of water at the end of each cycle. The bin level is normal.

1. Identify the likely causes of the long harvest and low production, separating water-side from refrigeration-side factors.

Read the worked answer

The long harvest and low production point to a refrigeration-side and water-side combination. Thin, cloudy ice indicates poor freezing and mineral scale on the evaporator or water distributor. Scale insulates the evaporator, slows freeze, and makes the slab release poorly. The noisy water pump and scaled trough suggest reduced water flow, which also lengthens freeze and harvest. The 4-minute harvest is too long; hot-gas harvest may be restricted by a failing solenoid or a partially blocked hot-gas valve, or the slab is too thick because the freeze cycle is not terminating on thickness. The purge valve discharging a large volume wastes water and can lower the water level, affecting the next cycle. The 230 psig head pressure at 85°F ambient is high and reduces capacity even with a clean condenser.

2. How would you prioritize repairs and verify the machine after service?

Read the worked answer

Prioritize water-side cleaning first: clean the evaporator, water distributor, and trough with an approved ice-machine cleaner, then verify water flow and pump operation. Replace the water filter. Next, check the hot-gas harvest solenoid and valve for restriction; measure the temperature of the hot-gas line at the evaporator during harvest. Confirm the purge setting is not excessive and that the water level is correct. Verify refrigerant charge and condenser condition; head pressure should drop after cleaning the condenser if it is dirty. Run a complete cycle and compare freeze and harvest times to the manufacturer's chart. If harvest remains long after cleaning, replace the hot-gas valve or solenoid.