NCCER Welding · Put your knowledge to work in context.

All case studies

Entry and Hot Work on a Diesel Tank

A maintenance crew must weld a 6-inch square patch over a crack on the inside shell of a 1,500-gallon horizontal steel tank that last contained No. 2 diesel. The tank was drained 24 hours ago and the drain valve left open; about 2 inches of sludge remain at the bottom. The only access is an 18-inch manhole. A gas meter at the manhole reads O2 19.3%, LEL 0%, CO 4 ppm, H2S 0 ppm. The foreman wants a welder inside with a 25-ft stinger, a small 120-V fan at the opening, and an acetylene cylinder on a cart 10 feet from the manhole for a torch used to tack a patch. The welder is told to "make it quick" before the permit is written. Ambient temperature is 94°F and the tank is in direct sun.

1. Which readings and conditions make entry unacceptable now, and why is a 0% LEL reading not proof that the tank is safe for hot work?

Read the worked answer

The entry should not proceed. The oxygen reading of 19.3% is below the usual acceptable range of 19.5–23.5%, so the space is oxygen-deficient and must be ventilated and retested before entry. A 0% LEL at the manhole is not proof of a gas-free tank: the 2 inches of diesel sludge can release flammable vapor when disturbed, heated by welding, or when the meter is sampled only at the opening. Test at top, middle, and bottom, and monitor continuously. The acetylene cylinder near the manhole, the 120-V fan, the long stinger, and the missing permit are all unacceptable. The fan may be non-explosion-proof and may just recirculate fumes; the cylinder must stay outside, upright, and secured; the welder needs supplied ventilation, retrieval equipment, an attendant, and a rescue plan. The 94°F direct-sun condition also creates heat-stress risk.

2. Lay out the order of operations and controls you would require before anyone enters with a torch.

Read the worked answer
  1. Isolate and clean: lockout/tagout, blank or disconnect lines, drain, and remove sludge; the tank cannot be declared gas-free while sludge remains. 2. Ventilate: use explosion-proof forced-air ventilation and retest at multiple levels. Entry only after O2 is 19.5–23.5%, LEL is below the permit limit (commonly <10% and often 0% for hot work), and CO/H2S are acceptable. 3. Permits: confined-space entry permit, hot-work permit, rescue plan, attendant, harness/tripod, communications, intrinsically safe lighting, GFCI protection. 4. Equipment: welding machine and cylinders outside; leads protected from damage; flashback arrestors; no acetylene inside. 5. PPE/fire: FR clothing, respirator if ventilation cannot keep fume below limits, fire watch, extinguisher. 6. Continuous monitoring and evacuation for any change; retest after breaks.

3. The foreman proposes skipping entry by welding a doubler plate over the crack from the outside. What must be verified before accepting or rejecting that change?

Read the worked answer

An outside doubler is not automatically safer or acceptable. It changes the repair design, so an engineer must approve it and confirm it restores strength and does not trap a crack. Welding on the outside still heats the shell and can ignite vapors from the sludge, so the tank must be cleaned and monitored, with a fire watch. If the crack is internal or requires full penetration, an outside patch may not work. Accept only with engineering approval, a written procedure, gas testing, and inspection; otherwise clean and ventilate for internal entry. Do not let schedule pressure override the permit.