Flammable Liquids and an Unpermitted Spray Booth in an Auto Body Shop

NFPA CFI-II · Put your knowledge to work in context.

All case studies

Flammable Liquids and an Unpermitted Spray Booth in an Auto Body Shop

You inspect a 2,400-square-foot auto body shop after a neighbor complaint. In the work area you find 18 gallons of Class I flammable liquid in open buckets, a 55-gallon drum of solvent with a hand pump, and about 30 gallons of paint in a wooden cabinet. The spray booth has no permit and is separated from the office by a wood-framed wall with a hollow-core door. The shop's flammable-liquids permit expired eight months ago. An extension cord powers a space heater near the solvent drum. The owner says the shop has operated for 20 years, the liquids are 'just for touch-up,' and the cabinet is 'fire-rated' because it is painted red. Two employees are working, and the rear exit is blocked by pallets of empty paint cans.

1. How do you classify the hazards and permit status?

Read the worked answer

The Class I flammable liquids in open buckets and the solvent drum are the most serious hazards. Open containers allow vapor release and ignition; Class I liquids have low flash points. The wooden cabinet is not an approved flammable-liquid storage cabinet, and 30 gallons of paint plus 18 gallons in open containers likely exceed exempt amounts and require approved storage, ventilation, grounding and bonding, and a permit. The spray booth is a hazardous operation and requires a permit, fire separation, and an approved suppression and ventilation system. The expired permit means the operation is unpermitted. The extension cord and space heater add ignition sources. I would treat this as a combination of flammable-liquid storage, spray application, and housekeeping violations under the adopted fire code and NFPA 30 and NFPA 33, not as a minor housekeeping issue.

2. What immediate abatement and enforcement actions do you take?

Read the worked answer

I would order immediate elimination of ignition sources: shut down the space heater and remove the extension cord, and stop spray operations until the booth is permitted and separated. The open containers must be closed and moved to an approved cabinet or removed from the building. The 55-gallon drum should be bonded and grounded and equipped with an approved pump or self-closing valve. I would issue a notice of violation for the expired permit, unapproved storage, and blocked rear exit, and require the pallets to be removed immediately. Depending on the adopted code, I may order the spray booth and flammable-liquid storage to cease until permits and corrections are complete. I would schedule a reinspection and involve the fire prevention bureau for permit review. If the owner refuses, escalation could include a stop-use order or legal referral.

3. What documentation and follow-up are needed?

Read the worked answer

Document the quantities, container types, cabinet construction, booth separation, ignition sources, permit status, and blocked exit with photos and measurements. The notice should separate immediate hazards from permit and plan-review items. I would record the owner's statements, employee counts, and the absence of a permit. Follow-up includes verifying the flammable-liquid cabinet is listed and approved, the booth has been permitted and inspected, ventilation and suppression are functional, and the exit is clear. I would also check whether the building has other tenants and whether the wall separation affects them. A reinspection should occur after corrections, and the file should include the permit application, plans, and inspection results. If the owner repeats open-container storage, escalate to citation or closure.