Cooling-Water Pump Cavitation After 18 Months

PRC Mechanical Engineer · Put your knowledge to work in context.

All case studies

Cooling-Water Pump Cavitation After 18 Months

A cooling-water pump draws 120 m³/h from an open sump through 8 m of DN150 (150 mm ID) suction pipe with friction factor 0.02 and fittings equivalent to K = 6.5 velocity heads. The pump centreline sits 0.8 m above the sump water level. Water is at 30 °C (ρ = 996 kg/m³, vapour pressure 4.25 kPa); site barometric pressure is 101.3 kPa. A clean basket strainer adds 0.5 m of head loss. The pump curve gives NPSHr = 4.5 m at 120 m³/h, rising with the square of flow. After 18 months in service the operators report a rattling noise at the pump, a fluctuating discharge pressure and slight vibration, always worst in the afternoon when demand is highest.

1. Compute the NPSH available at the design flow with a clean strainer and state whether the installation has an adequate margin.

Read the worked answer

Q = 120/3600 = 0.03333 m³/s; A = π(0.150)²/4 = 0.01767 m²; v = 1.886 m/s; v²/2g = 0.181 m

Friction: hf = f(L/D)(v²/2g) = 0.02 × (8/0.15) × 0.181 = 0.193 m Fittings: 6.5 × 0.181 = 1.179 m Strainer (clean): 0.500 m Total suction loss = 1.87 m

Pressure head available: (p_b − p_v)/(ρg) = (101.3 − 4.25) × 10³/(996 × 9.81) = 9.93 m Static: −0.80 m (pump centreline above sump level)

NPSHA = 9.93 − 0.80 − 1.87 = 7.26 m Margin over NPSHr = 7.26 − 4.50 = 2.76 m (about 60% of NPSHr, well above the usual 1.0–1.5 m or 10% rule).

So the as-designed installation is sound. The problem is therefore not the layout - it is something that changed in service, which is the useful conclusion to carry into troubleshooting.

2. A differential pressure gauge across the strainer now reads 35 kPa. Test the cavitation hypothesis quantitatively, including the afternoon peak.

Read the worked answer

Strainer loss now: 35 000/(996 × 9.81) = 3.58 m, i.e. 3.08 m more than assumed.

At 120 m³/h: NPSHA = 9.93 − 0.80 − 1.87 − 3.08 = 4.18 m < NPSHr 4.5 m → cavitation.

At the afternoon peak, take flow 15% above design (v² rises by 1.15² = 1.32): Suction piping loss = 1.37 × 1.32 = 1.81 m; strainer = 3.58 × 1.32 = 4.73 m NPSHA = 9.93 − 0.80 − 1.81 − 4.73 = 2.59 m NPSHr = 4.50 × 1.32 = 5.95 m Margin = −3.36 m

The hypothesis fits every symptom: rattling (bubble collapse), fluctuating discharge pressure, vibration, and a peak-demand bias because NPSHr climbs faster with flow than NPSHA can follow. Diagnose a fouled suction strainer compounded by a high-flow operating point, not a worn impeller or a bearing fault.

3. Recommend remedial actions, ranked, and give the NPSHA that results from the most durable one.

Read the worked answer
  1. Clean or replace the strainer element and fit a dP transmitter with an alarm at 20 kPa. This restores the 7.26 m margin at essentially zero capital cost and prevents recurrence - the real failure here is the absence of condition monitoring, not the strainer.

  2. Raise the sump level or lower the pump. Every metre of static head is a metre of NPSHA; often the cheapest permanent fix if civil work is easy.

  3. Increase the suction line to DN200. At DN200, A = 0.03142 m², v = 1.06 m/s, v²/2g = 0.0574 m; friction plus fittings = (0.02 × 8/0.20 + 6.5) × 0.0574 = 0.42 m. With the strainer still fouled at 3.58 m: NPSHA = 9.93 − 0.80 − 0.42 − 3.58 = 5.13 m, which survives fouling and peak flow better than anything else on the list.

  4. Cap maximum flow (trim impeller or throttle to a set maximum). Since NPSHr rises as Q² and NPSHA falls as Q², limiting flow protects the margin - but do not open the discharge valve further hoping to 'flush' the problem; that moves the duty point the wrong way.

Sequence: clean now to restore production, then instrument the strainer and schedule the suction-line upgrade at the next outage.