- Minimum approach distance
- The closest distance a qualified worker may approach an energized conductor, set by voltage class and maximum switching surge per OSHA 1910.269 tables.
- Arc flash boundary
- The distance from energized equipment at which incident energy equals 1.2 cal/cm2, used to select arc-rated PPE per NFPA 70E.
- Step potential
- Voltage difference between two points on the earth's surface one step apart, caused by fault current flowing through the ground.
- Qualified electrical worker
- A worker trained in and familiar with the construction and operation of equipment and the hazards involved, per OSHA 1910.269(a)(2).
- NESC Rule 232
- The National Electrical Safety Code rule that sets vertical clearance of wires above ground, roads, rails, and water by voltage class.
- NESC Grade B construction
- A construction grade requiring higher safety factors, typically 4 for pole strength, applied where higher reliability and public safety are needed.
- 29 CFR 1910.269
- OSHA standard covering electric power generation, transmission, and distribution, including approach distances, grounding, and protective equipment testing.
- Temporary protective grounds
- Grounding cables sized to carry available fault current and installed with a shotgun stick from a safe position to protect workers from induced or backfeed voltage.
- Three-phase power formula
- P = √3 x VLL x I x power factor, used to compute real power from line-to-line voltage, line current, and power factor.
- Per-unit impedance
- A normalized impedance value; to convert to ohms, multiply by Z(base) = kV^2/MVA for a three-phase base.
- Transformer fault current
- Isc ≈ kVA x 1000 / (√3 x VLL x Z%); a 5% impedance transformer produces about 20 times rated current on a bolted fault.
- Symmetrical components
- A method that resolves unbalanced three-phase quantities into positive, negative, and zero sequence components for fault analysis.
- Pole class
- ANSI O5.1 classification (Class 1 through 5) specifying the circumference at 6 ft from the butt and rated load at 2 ft from the top.
- Ruling span
- The equivalent span used to set stringing sag-tension for a line section; individual span sags are adjusted from the ruling span value.
- Guy lead angle
- The angle between the guy and the pole; a 45-degree guy carries about 1.41 times the horizontal load it resists.
- Armor rods
- Preformed rods wrapped around a conductor at a support to protect against chafing, bending fatigue, and vibration damage.
- Cable pulling tension
- The longitudinal force applied during cable installation; limited by conductor strength and by sidewall pressure at bends.
- Concentric neutral cable
- Underground cable with a neutral conductor wrapped around the insulation; the neutral carries unbalanced and fault current and must be grounded at both ends.
- Time-domain reflectometry
- A cable test that sends a pulse and measures the reflection time; distance = (velocity of propagation x time)/2 to locate opens and low-resistance faults.
- Cable bending radius
- The minimum radius to which a cable may be bent without damaging insulation or semicon; typically 8x to 12x the cable diameter for solid dielectric cable.
- Open-delta capacity
- A bank of two transformers in open delta delivers about 58% of the three-transformer capacity, or √3 times the kVA of one unit.
- Subtractive polarity
- A transformer polarity where H1 and X1 are adjacent; most distribution transformers are subtractive and must be connected accordingly.
- Wye-grounded primary to delta secondary
- A connection not permitted on four-wire multi-grounded primary systems because it provides a zero-sequence path and can cause ferroresonance.
- Transformer tap changer
- A device that changes the number of primary turns to compensate for primary voltage variation, typically in ±5% steps.
- Sectionalizer
- A device that counts fault-current interruptions and opens on the last count; it has no fault-interrupting rating and must be backed by a recloser.
- Recloser fast and delayed curves
- A recloser typically uses two fast and two delayed operations; the fast curve saves fuses and the delayed curve lets downstream fuses clear.
- Time-current coordination
- Selection of protective device settings so that the device nearest the fault operates first and curves do not cross in the fault current range.
- Polarization index
- The ratio of 10-minute to 1-minute insulation resistance; a value above 2.0 indicates good insulation condition.
- Transformer turns ratio test
- A test comparing measured winding ratio to nameplate; a deviation greater than 0.5% indicates a winding problem.
- Dissolved gas analysis
- A transformer oil test that identifies arcing, overheating, and corona by measuring dissolved gases; a rising trend is more significant than a single reading.
- Single line-to-ground fault
- The most common distribution fault type, accounting for roughly 70% to 80% of faults, often caused by trees, animals, or insulation failure.
- Surge generator thumper
- A fault-locating tool that applies high-voltage pulses to break down a cable fault, located by acoustic and electromagnetic detection.