Well Pump, Storage, and Fire-Flow Adequacy

Water Distribution Operator Class I · Put your knowledge to work in context.

All case studies

Well Pump, Storage, and Fire-Flow Adequacy

A community has one well pump rated 500 gpm and a 250,000-gal elevated tank with 200,000 gal usable storage. Average-day demand is 450,000 gal. On the peak day, demand is 900 gpm for 4 consecutive hours; the rest of the day averages 300 gpm. The state requires the system to maintain 1,000 gpm fire flow for 2 hours plus normal demand, and to keep a 50,000-gal emergency reserve. The pump can run continuously but its motor is 20 years old. The operator must decide whether to add a second pump, increase tank size, or manage demand.

1. Calculate the peak-period drawdown and the storage available above the required reserve.

Read the worked answer

Usable storage = 200,000 gal. Required reserve = 50,000 gal, so storage available above reserve = 150,000 gal.

During the 4-hour peak, the pump supplies 500 gpm and demand is 900 gpm, so the tank supplies 400 gpm: 400 gpm × 240 min = 96,000 gal.

After the peak, the tank would contain 200,000 − 96,000 = 104,000 gal, which is 54,000 gal above the 50,000-gal reserve. The peak alone is therefore within usable storage.

2. Calculate whether the tank can meet the required fire flow plus normal demand at the worst time.

Read the worked answer

Fire flow plus normal demand = 1,000 + 300 = 1,300 gpm. With the pump at 500 gpm, the tank must supply 800 gpm for 2 hours: 800 gpm × 120 min = 96,000 gal.

The worst normal condition is after the 4-hour peak, when the tank is at 104,000 gal. After the fire flow: 104,000 − 96,000 = 8,000 gal, which is below the required 50,000-gal reserve. So the system fails the fire-flow requirement at the worst time. If the fire occurred with a full tank, 200,000 − 96,000 = 104,000 gal would remain and the reserve would be met, but operators cannot rely on a full tank at the worst moment.

3. What recommendation would you make, and what supporting checks are needed?

Read the worked answer

Recommend additional supply or storage. A second pump of about 400 gpm or more would reduce the fire-flow drawdown: with 900 gpm total pumping, the tank would supply only 400 gpm × 120 min = 48,000 gal, leaving 56,000 gal after the post-peak low level, just above the 50,000-gal reserve. Additional tank capacity would also work. Before choosing, verify the well's sustainable yield, the actual fire-flow requirement, normal demand patterns, tank mixing and turnover, and the condition of the 20-year-old motor. Demand management can reduce normal demand but should not be counted on to solve a fire-flow deficiency.