Water Distribution Operator Class III flashcards
Water Distribution Operator Class III · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Pressure head conversion
- One foot of water column equals 0.433 psi, and one psi equals 2.31 feet of head. Use these to convert between elevation and pressure in distribution systems.
- Hazen-Williams equation
- Predicts head loss in a pipe from flow, diameter, length, and a roughness coefficient C. Higher C means smoother pipe and lower friction loss.
- Fire flow residual pressure
- Fire flow testing measures available flow while maintaining a minimum residual pressure, commonly 20 psi, to protect the system from contamination and collapse.
- Thrust block purpose
- Rigid concrete blocks or restrained joints absorb the unbalanced force at bends, tees, reducers, and dead ends so pipe joints do not separate under pressure.
- Pump affinity laws
- For a given pump, flow varies with speed, head with speed squared, and power with speed cubed. Impeller diameter changes follow the same relationships.
- Brake horsepower formula
- Brake horsepower equals flow in gpm times head in feet divided by 3960, then divided by pump efficiency. It represents power delivered to the pump shaft.
- NPSH available
- The absolute pressure head at the pump suction minus vapor pressure head. It must exceed the pump's required NPSH to avoid cavitation.
- Cavitation symptoms
- Gravel-like noise, vibration, fluctuating discharge pressure, and impeller pitting indicate vapor bubbles collapsing. Reduce suction lift, friction, or water temperature to correct it.
- Pumps in series vs parallel
- Series pumps add head at the same flow; parallel pumps add flow at the same head. Choose based on whether the system needs more pressure or more volume.
- Tank static pressure
- Pressure at a service point equals the elevation difference between the tank water surface and the point, multiplied by 0.433 psi per foot.
- Minimum and maximum pressure
- Systems typically target 40 to 80 psi normal working pressure, maintain at least 20 psi under peak or fire demand, and use pressure-reducing valves above about 100 psi.
- Tank turnover and water age
- Storage should turn over often enough to keep water age low, generally under three to five days, to preserve disinfectant residual and limit nitrification.
- Altitude valve function
- An altitude valve throttles or closes tank fill based on water level, preventing overflow and controlling which tank or zone fills first.
- CT disinfection concept
- Disinfection credit equals residual concentration in mg/L multiplied by contact time in minutes. Required CT depends on pH, temperature, and target pathogen log inactivation.
- Breakpoint chlorination
- Adding chlorine past the point where ammonia demand is satisfied causes free chlorine to rise sharply. Before that point, combined chloramines dominate and cause taste and odor.
- Air gap backflow protection
- A physical unobstructed separation between a potable supply and a receiving vessel. It is the highest level of cross-connection protection and needs no testing.
- RPZ assembly
- A reduced-pressure-zone device uses two check valves and a relief valve to protect against backsiphonage and backpressure. It must be tested annually by a certified tester.
- Turbidity limits
- Conventional filtration systems must keep turbidity at or below 0.3 NTU in 95 percent of monthly samples, with an absolute maximum of 1 NTU.
- New main disinfection
- New mains are chlorinated to roughly 25 to 50 mg/L for 24 hours, flushed, then sampled for coliform bacteria before being placed in service.
- Hydrostatic test
- New pipe is pressure tested, often at 1.5 times working pressure for a set duration, and leakage must not exceed the allowable rate before acceptance.
- Valve exercising program
- Operating each distribution valve on a scheduled cycle and recording turns confirms it is operable. Stuck valves greatly slow emergency isolation of main breaks.
- Utility separation distances
- Water mains are typically kept at least 10 feet horizontally from sanitary sewers, with greater separation or casing where crossing, to reduce contamination risk.
- Confined space atmosphere limits
- Entry requires oxygen between 19.5 and 23.5 percent, flammable gas below 10 percent of the lower explosive limit, and toxic gases below exposure limits.
- Total coliform repeat sampling
- A positive routine total coliform sample requires repeat samples, typically at the same site and adjacent sites, to confirm or rule out contamination.
- TTHM and HAA5 MCLs
- Disinfection byproduct limits are 0.080 mg/L for total trihalomethanes and 0.060 mg/L for five haloacetic acids, evaluated as locational running annual averages.
- Consumer Confidence Report
- An annual report delivered to customers by July 1 that lists detected contaminants, their levels, applicable limits, and potential health effects.
- Public notification tiers
- Tier 1 covers acute violations and requires notice within 24 hours. Tier 2 allows 30 days, and Tier 3 is annual, based on violation severity.
- Chlorine gas emergency
- Chlorine gas is heavier than air and settles in low areas. Evacuate upwind, use SCBA, and never enter the area without respiratory protection.
- Trench protective systems
- Trenches five feet or deeper require shoring, sloping, or a trench box. Spoil and equipment must be kept back from the edge to prevent collapse.
- Lockout tagout
- Energy-isolating devices are locked and tagged before servicing pumps, motors, or valves. Zero energy must be verified before work begins.
- Sodium hypochlorite storage
- Store hypochlorite cool and out of sunlight to slow strength loss. Never mix it with acid, which releases dangerous chlorine gas.
- Water loss accounting
- Compare master-meter production to billed consumption. The gap includes apparent loss from meter error and real loss from leaks, guiding repair priorities.
- Monthly operating report
- A monthly summary of flows, chemical doses, residuals, and compliance samples submitted to the primacy agency to document ongoing regulatory compliance.