Water Distribution Operator Class IV flashcards
Water Distribution Operator Class IV · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Hazen-Williams equation
- An empirical formula relating head loss to pipe length, flow, diameter, and roughness coefficient C; higher C values indicate smoother pipe and lower friction loss.
- Static pressure conversion
- Each foot of elevation head produces 0.433 psi, and 2.31 feet of head equals 1 psi; used to convert between elevation and pressure in distribution systems.
- Minimum residual fire flow pressure
- Twenty psi is the minimum residual pressure maintained at the point of fire flow during a fire; falling below risks backflow and contamination intrusion into mains.
- Water hammer
- A pressure surge caused by rapid changes in flow velocity, such as fast valve closure; mitigated with slow-closing valves, surge arrestors, and air valves.
- CT concept
- CT equals disinfectant residual concentration in mg/L multiplied by contact time in minutes; the calculated value is compared to a required CT based on pH, temperature, and log inactivation.
- Filtered water turbidity limits
- Combined filter effluent must be 0.3 NTU or less in at least 95 percent of monthly samples and must never exceed 1 NTU for surface water filtration compliance.
- Breakpoint chlorination
- The point at which added chlorine fully oxidizes free ammonia to nitrogen gas, after which additional chlorine produces a persistent free chlorine residual.
- Chlorine demand
- The difference between the chlorine dose applied and the residual remaining after a specified contact time; it reflects chlorine consumed by reducing agents and organics.
- Langelier Saturation Index
- A calculated index of water's calcium carbonate saturation; a negative value indicates corrosive tendency and a positive value indicates scaling tendency.
- Unidirectional flushing
- A flushing method that closes valves to create one-way flow at 2.5 to 3 feet per second, sequencing from clean to dirty sections to scour sediment from mains.
- Non-revenue water
- System input volume minus billed authorized consumption; real losses are leaks and breaks, while apparent losses are meter error and unauthorized use.
- Boil water advisory trigger
- Issued when system pressure drops below 20 psi or contamination is suspected; requires flushing and coliform and chlorine sampling before service is restored.
- Tank turnover
- The practice of maintaining adequate daily flow through storage tanks, sometimes with mixing or drawdown, to prevent stratification, nitrification, and chlorine loss.
- Brake horsepower formula
- BHP equals flow in gpm times head in feet times specific gravity, divided by 3960 times pump efficiency; used to size motors and estimate power cost.
- Affinity laws
- For a centrifugal pump, flow varies directly with speed, head with the square of speed, and power with the cube of speed; impeller trim follows similar relationships.
- NPSH available
- NPSHa equals atmospheric pressure head plus static suction head minus vapor pressure head minus suction friction losses; it must exceed the pump's NPSH required.
- Specific speed
- Ns equals speed times the square root of flow divided by head to the 0.75 power; low values indicate radial high-head impellers and high values indicate axial high-flow impellers.
- Motor voltage unbalance
- Voltage unbalance should stay below 1 percent and current unbalance below 10 percent; higher values cause overheating and shortened motor life.
- Backflow causes
- Backflow requires a cross-connection plus either backsiphonage from negative supply pressure or backpressure where downstream pressure exceeds supply pressure.
- Air gap
- A physical separation between a supply outlet and the flood level rim, typically twice the pipe diameter and at least 1 inch; it is the highest protection and needs no testing.
- Reduced pressure zone assembly
- An RPZ protects against both backpressure and backsiphonage and is required for high health hazards; it is tested annually with a differential pressure gauge.
- Pressure vacuum breaker
- A PVB protects against backsiphonage only, cannot be under continuous pressure, and is used for low to moderate hazards such as irrigation systems.
- Containment versus isolation
- Containment protects the public main at the meter, while isolation protects hazards inside a facility such as boilers, chemical feed, and irrigation connections.
- Confined space atmospheric limits
- Acceptable entry conditions are oxygen between 19.5 and 23.5 percent, combustible gas below 10 percent of LEL, hydrogen sulfide below 10 ppm, and carbon monoxide below 35 ppm.
- Chlorine gas leak response
- Evacuate upwind, wear SCBA, and never apply water to the leak; only trained responders with PPE attempt containment and repair.
- Trench protective systems
- Trenches 5 feet deep or deeper require protective systems; spoil piles stay at least 2 feet from the edge and ladders within 25 feet of workers.
- Public notice tiers
- Tier 1 notice is issued within 24 hours for acute violations such as E. coli or nitrate, Tier 2 within 30 days, and Tier 3 annually for less urgent issues.
- Consumer Confidence Report
- An annual report delivered by July 1 that summarizes source water, detected contaminants, and compliance status for customers of a public water system.
- Sanitary survey
- A primacy agency review of source, treatment, distribution, and records every 3 to 5 years; significant deficiencies require corrective action and may trigger violations.
- Span of control
- The number of direct reports a supervisor effectively manages, commonly 5 to 8; wider spans require greater delegation and standardized procedures.
- Progressive discipline
- A documented sequence of corrective steps from verbal warning to termination, applied consistently to protect against claims of unfair treatment.
- Feed rate formula
- Feed rate in pounds per day equals dose in mg/L times flow in MGD times 8.34; rearranged, it solves for dose or flow given the other two values.