Water Treatment Operator Class III flashcards
Water Treatment Operator Class III · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Alkalinity
- The capacity of water to neutralize acid, measured as mg/L CaCO3; it buffers pH changes and is consumed by alum coagulation.
- Turbidity
- A measure of water clarity caused by suspended particles, reported in NTU; high turbidity can shield pathogens from disinfection.
- Hardness
- The sum of dissolved calcium and magnesium in water, expressed as mg/L CaCO3; it causes scale and affects coagulant demand.
- Coliform bacteria
- Indicator organisms used to detect potential fecal contamination; their presence in finished water triggers repeat sampling and public notice.
- Total organic carbon
- The measure of organic matter in water that reacts with chlorine to form regulated disinfection byproducts such as THMs and HAAs.
- Coagulation
- The process of destabilizing suspended particles by adding chemicals like alum, allowing them to agglomerate into larger floc.
- Flocculation
- Gentle mixing that encourages destabilized particles to collide and grow into settleable floc, typically 15–45 minutes at low velocity gradient.
- Jar test
- A laboratory procedure that simulates coagulation, flocculation, and sedimentation to determine the optimal coagulant dose and pH.
- Overflow rate
- The flow divided by the clarifier surface area, expressed in gpm/ft²; it determines the settling velocity required for particle removal.
- Sludge blanket
- The layer of accumulated solids in a clarifier; its depth is controlled by sludge withdrawal to prevent carryover.
- Filter backwash
- Reversing flow through a filter to remove captured particles; it expands the bed 15–25% and typically lasts 10–15 minutes.
- Filter run
- The period between backwashes; it ends when effluent turbidity exceeds 0.3 NTU, headloss reaches its limit, or run time expires.
- Media effective size
- The sieve size that passes 10% of the filter media by weight; typical rapid sand effective size is 0.5–1.0 mm.
- Log removal value
- A measure of pathogen removal or inactivation expressed as log10; LRV 4 equals 99.99% removal.
- CT
- The product of disinfectant residual concentration (mg/L) and contact time (minutes), used to determine pathogen inactivation credit.
- Chlorine demand
- The difference between the chlorine dose applied and the residual remaining after a specified contact time, caused by reactions with impurities.
- Breakpoint chlorination
- The point at which enough chlorine has been added to oxidize all ammonia and a free chlorine residual begins to appear.
- Trihalomethanes
- Regulated disinfection byproducts formed when chlorine reacts with organic matter; total THM limit is 80 µg/L as a locational running annual average.
- HOCl
- Hypochlorous acid, the stronger form of free chlorine; its fraction decreases as pH rises above 7.5, reducing disinfection efficiency.
- Chemical feed rate
- The mass of chemical applied per day, calculated as dose (mg/L) × flow (MGD) × 8.34.
- Secondary containment
- A structure or dike around chemical storage tanks that captures spills or leaks, preventing environmental contamination.
- Sodium hypochlorite degradation
- The loss of chlorine strength over time, accelerated by heat, light, and high concentration; store in a cool, dark area and rotate stock.
- Metering pump calibration
- Verifying the actual volume delivered per unit time against the setpoint, typically by drawing down a measured volume over a timed interval.
- Pump cavitation
- The formation and collapse of vapor bubbles when local pressure drops below vapor pressure, causing noise, vibration, and impeller damage.
- Pump curve
- A graph of head versus flow for a pump; the operating point is where it intersects the system curve.
- Water hammer
- A pressure surge caused by sudden changes in flow velocity, such as rapid valve closure; mitigated by slow-closing valves or surge tanks.
- Brake horsepower
- The power required by a pump, calculated as (gpm × head in ft) ÷ (3960 × pump efficiency).
- DPD method
- A colorimetric test for chlorine residual using N,N-diethyl-p-phenylenediamine; high turbidity or manganese can interfere.
- Control chart
- A statistical tool that plots process data over time with control limits to detect trends, shifts, and out-of-control conditions.
- Stage 2 DBPR
- A regulation limiting locational running annual averages for TTHM (80 µg/L) and HAA5 (60 µg/L) in distribution systems.
- Surface Water Treatment Rule
- Requires 99.9% (3-log) removal/inactivation of Giardia and 99.99% (4-log) of viruses for surface water systems.
- Consumer Confidence Report
- An annual water quality report that must be delivered to customers by July 1, summarizing contaminant levels and compliance.