Water Treatment Operator Class IV flashcards
Water Treatment Operator Class IV · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Detention time formula
- Detention time in hours equals basin volume in gallons divided by flow in gallons per minute, then divided by 60. Verify against design criteria for each unit process.
- Surface overflow rate
- Flow in gallons per minute divided by clarifier surface area in square feet. Rising rates shorten detention time and increase the risk of solids carryover.
- Filter loading rate
- Flow in gallons per minute divided by filter bed area in square feet. Backwash is triggered by terminal headloss or turbidity breakthrough, whichever occurs first.
- CT concept
- CT equals disinfectant residual in mg/L multiplied by contact time in minutes. Required CT increases with higher pH, lower temperature, and greater target log inactivation.
- Lime-soda softening
- Precipitation process removing calcium and magnesium hardness as carbonate and hydroxide solids. Excess lime raises pH and requires recarbonation or acid for stabilization.
- Weir overflow rate
- Flow in gallons per minute divided by total weir length in feet. Excessive rates cause short-circuiting and density currents in the clarifier.
- Filtered water turbidity limit
- At least 95 percent of monthly filtered-water samples must be at or below 0.3 NTU, and no individual sample may exceed 1 NTU.
- Combined chlorine calculation
- Combined chlorine equals total chlorine minus free chlorine. A rising combined fraction signals chloramine formation or distribution-system nitrification.
- Langelier Saturation Index
- LSI equals measured pH minus saturation pH. Negative values indicate corrosive water, positive values indicate scale-forming tendency, near zero is balanced.
- Coliform MCL violation
- Detection of E. coli in a distribution sample is an acute maximum contaminant level violation requiring public notice and corrective action.
- Fluoride regulatory values
- Optimal fluoride dose is near 0.7 mg/L. The primary MCL is 4.0 mg/L and the secondary standard is 2.0 mg/L.
- Bacteriological sample bottle
- Sterile bottle containing sodium thiosulfate to neutralize residual chlorine. Collect from designated sites and record chlorine residual and temperature at collection.
- Sample preservation acids
- Nitric acid to pH below 2 for metals; sulfuric acid to pH below 2 for ammonia and nitrate. Most organic samples are chilled to 4 degrees Celsius.
- Holding time examples
- Bacteriological samples analyzed within 8 hours, extended to 30 hours when transport-limited. Nitrate within 48 hours; metals within 6 months.
- Grab versus composite sample
- Grab samples suit pH, chlorine, temperature, and dissolved gases. Composite samples average loads across time for flow-weighted or time-weighted characterization.
- Chain of custody
- Form recording collector, date, time, analyses requested, and every transfer of possession. Required to demonstrate sample integrity for regulatory reporting.
- Feed pump calibration
- Drawdown test measuring volume delivered over a timed interval. Recalibrate whenever dose or feed rate changes or after pump maintenance.
- Pump condition monitoring
- Track vibration, bearing temperature, seal leakage, and discharge pressure. Rising vibration indicates wear, misalignment, or cavitation before failure.
- Analyzer maintenance
- Turbidimeters, chlorine analyzers, and pH meters need scheduled cleaning, standard verification, and reagent replacement to prevent measurement drift.
- Filter media inspection
- Check bed depth, media loss, mudball formation, and gravel support disturbance. Media problems cause short runs and turbidity breakthrough.
- Lockout tagout
- Electrical and instrumentation service requires energy isolation, lock and tag application, and verification of zero energy before work begins.
- Short filter run causes
- Alternating short and long runs suggest media upset, channeling, or uneven backwash distribution rather than a simple coagulant dose problem.
- Chlorine gas leak response
- Evacuate upwind and use supplied-air respiratory protection. Chlorine gas is heavier than air and accumulates in low-lying areas.
- Confined space entry
- Requires permit, atmospheric testing for oxygen, flammables, hydrogen sulfide, and carbon monoxide, plus ventilation, attendant, and retrieval system.
- Chemical dilution rule
- Never add water to concentrated acid or caustic. Add the chemical slowly to water with agitation to control heat release and splattering.
- Pump cavitation symptoms
- Noise, vibration, and reduced flow indicate cavitation. Check suction lift, available net positive suction head, and clogged strainers.
- Total coliform rule
- No more than 5 percent of monthly samples may be positive for systems collecting 40 or more samples; any E. coli is an acute violation.
- Disinfection byproduct LRAA
- Locational running annual averages limit total trihalomethanes to 80 micrograms per liter and five haloacetic acids to 60 micrograms per liter.
- Lead and copper action levels
- 90th percentile action levels are 0.015 mg/L for lead and 1.3 mg/L for copper. Exceedance triggers corrosion control and public education requirements.
- Surface water treatment log credits
- Requires 99.9 percent (3-log) Giardia and 99.99 percent (4-log) virus inactivation, plus combined filter effluent turbidity limits.
- Public notification tiers
- Tier 1 within 24 hours for acute health risk, Tier 2 within 30 days, Tier 3 within one year. Consumer Confidence Report delivered annually by July 1.
- Record retention periods
- Bacteriological and chemical monitoring records retained at least 5 years; certain rule-specific records require 10 years or longer.