ACT Mud Floors flashcards
ACT Mud Floors · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Standard Proctor Test
- ASTM D698 test determines maximum dry density and optimum moisture content of soil; used to set field compaction requirements for subgrade.
- Proof Rolling
- A loaded truck or roller passes over subgrade to identify soft or yielding areas; deflection indicates need for additional compaction or replacement.
- USCS Soil Classification
- ASTM D2487 groups soils by particle size and plasticity; helps determine suitability for subgrade, with organic and expansive clays requiring treatment.
- Subgrade Compaction Requirement
- Subgrade must be compacted to at least 95% of maximum dry density per Standard Proctor (ASTM D698) unless project specifications require higher.
- Field Density Test
- Nuclear gauge (ASTM D6938) or sand cone (ASTM D1556) measures in-place density and moisture; results compared to Proctor to verify compaction.
- Expansive Soil Treatment
- Highly plastic clays (CH) require lime or cement stabilization or a minimum 4-inch gravel base to prevent volume change and floor cracking.
- Frost-Susceptible Subgrade
- Frozen subgrade must be thawed and compacted before mud floor placement; frost heave can cause uneven settlement and cracking.
- Subgrade Elevation Tolerance
- Subgrade must be graded to ±0.05 ft (±15 mm) of design elevation to ensure uniform mud floor thickness and proper drainage.
- Mud Floor Mix Proportion
- Typical mix: 1 part Portland cement to 3 parts sand by weight, with water-cement ratio 0.45–0.55 for workability and strength.
- Sand Gradation for Mud Floor
- Sand must conform to ASTM C33, be clean and well-graded, with fines passing #200 sieve not exceeding 5% to avoid strength loss.
- Water Quality for Concrete
- Potable water free of oils, acids, and organic matter is suitable; ASTM C1602 provides acceptance criteria for mixing water.
- Hydrated Lime in Mud Mix
- Up to 10% hydrated lime by cement weight can improve workability and reduce cracking; do not add extra water for flow.
- Fiber Reinforcement
- Polypropylene or glass fibers at 0.1–0.3% by volume reduce plastic shrinkage cracking in mud floors.
- Mud Floor Compressive Strength
- Target 28-day compressive strength is 2,500–3,500 psi (17–24 MPa) for typical mud floor applications, tested per ASTM C39.
- Slump for Mud Floor
- Slump should be 4–6 inches (100–150 mm) for placement by chute or buggy; excessive slump reduces strength and causes segregation.
- Calcium Chloride Accelerator
- Do not use in mud floors; it can cause corrosion of reinforcement and efflorescence, and may affect finish appearance.
- Bond Coat Application
- Apply cement slurry or latex bonding agent over prepared subgrade immediately before placing mud mix to ensure proper adhesion.
- Placement Bay Width
- Place mud in strips or bays not exceeding 10 ft (3 m) wide, alternating placement to minimize cold joints and improve workability.
- Consolidation of Mud Mix
- Use mechanical vibrator or jitterbug to consolidate; avoid over-vibration which causes segregation and weak surface.
- Screeding Mud Floor
- Strike off to required elevation using a screed guided by edge forms or laser screed; ensures uniform thickness and level surface.
- Bull Floating
- Immediately after screeding, use a bull float to embed aggregate and remove high spots; do not trowel while bleed water is present.
- Construction Joints
- Plan joints at predetermined locations; use keyed joints or dowels for load transfer; avoid cold joints by continuous placement.
- Installation Temperature Range
- Ambient and subgrade temperature must be between 40°F (4°C) and 90°F (32°C) during placement and curing for proper set.
- Curing Duration
- Keep concrete moist for at least 7 days (or 3 days for accelerated mixes) per ACI 308; use wet burlap, curing compound, or plastic sheeting.
- Moisture Vapor Emission Rate
- MVER should be ≤3 lb/1000 ft²/24h (ASTM F1869) before applying floor coverings; excess requires mitigation.
- Relative Humidity Testing
- In-situ RH inside slab should be ≤75% (ASTM F2170) before installing moisture-sensitive flooring; test at proper depth.
- Drying Time per Inch
- Allow approximately 30 days per inch of slab thickness for normal-weight concrete to dry to acceptable moisture levels before covering.
- Vapor Retarder Requirement
- A vapor retarder (ASTM E1745) beneath slab is required to prevent moisture migration from subgrade and reduce MVER.
- Floor Flatness (FF) Number
- FF per ASTM E1155 quantifies surface flatness; typical mud floor minimum FF 25, higher for critical areas.
- Floor Levelness (FL) Number
- FL per ASTM E1155 quantifies levelness; typical minimum FL 20 for mud floors, higher for very flat floors.
- Straightedge Tolerance
- Maximum deviation of 1/8 inch in 10 feet (3 mm in 3 m) from a straightedge for standard floors; check per ASTM E1155.
- Surface Finish Types
- Common finishes: troweled (smooth), broom (non-slip), or exposed aggregate; specify per project requirements and use.
- Compressive Strength Testing
- Cast cylinders per ASTM C31 and test per ASTM C39 at 7 and 28 days; acceptance requires strength ≥ specified.