AEE Business Energy Professional flashcards
AEE Business Energy Professional · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- ASHRAE 90.1 scope
- ASHRAE 90.1 sets minimum energy-efficiency requirements for most commercial and high-rise residential buildings, excluding low-rise residential buildings, and provides prescriptive, trade-off, and energy cost budget compliance paths.
- ASHRAE 62.1 purpose
- ASHRAE 62.1 specifies minimum ventilation rates and indoor air quality requirements for commercial buildings to protect occupant health and comfort.
- ISO 50001
- ISO 50001 defines requirements for an energy management system, including energy policy, planning, implementation, performance evaluation, and continual improvement.
- LEED credit categories
- LEED credits are grouped into integrative process, location and transportation, sustainable sites, water efficiency, energy and atmosphere, materials and resources, indoor environmental quality, innovation, and regional priority.
- Net-zero energy building
- A net-zero energy building produces on-site renewable energy equal to or greater than its annual site energy consumption within a defined measurement boundary.
- kWh to Btu
- One kilowatt-hour equals 3,412 British thermal units, so a 10 kWh electricity use equals 34,120 Btu of site energy.
- Power factor formula
- Power factor equals real power in kilowatts divided by apparent power in kilovolt-amperes; for sinusoidal loads, kW equals kVA multiplied by power factor.
- Affinity laws
- For fans and pumps at constant efficiency, flow varies with speed, head varies with speed squared, and shaft power varies with speed cubed.
- Demand charge
- A demand charge bills the customer for the highest average power, usually in kilowatts, measured during a billing period or a defined demand interval.
- Demand ratchet
- A demand ratchet sets the billed demand from a percentage of a prior peak, such as 80 percent of the highest monthly peak in the previous year, when current demand is lower.
- Spark spread
- Spark spread equals the electricity price minus the natural gas price multiplied by the generator heat rate, usually expressed in the same energy units.
- Firm gas transportation
- Firm natural gas transportation reserves pipeline capacity for the shipper and guarantees delivery priority, while interruptible transportation can be curtailed when pipeline capacity is scarce.
- Energy balance
- An energy balance accounts for purchased energy as useful output plus conversion losses, distribution losses, and unaccounted energy within a defined boundary.
- Weather-normalized EUI
- Weather-normalized energy use intensity adjusts annual energy use per floor area for heating and cooling degree days so different periods or buildings can be compared more fairly.
- Scope 1 emissions
- Scope 1 emissions are direct greenhouse gas emissions from sources owned or controlled by the reporting organization, such as combustion boilers, furnaces, and fleet vehicles.
- Scope 2 market-based
- The market-based Scope 2 method uses contractual instruments, such as renewable energy certificates or supplier-specific factors, to calculate emissions from purchased electricity, steam, heat, or cooling.
- CO2 equivalent
- CO2 equivalent expresses the warming effect of different greenhouse gases in metric tons of carbon dioxide using global warming potential multipliers over a stated time horizon.
- Interval data
- Interval data records energy or demand over fixed periods, commonly 15 minutes, enabling load profiling, demand analysis, and baseline development.
- Meter multiplier
- A meter multiplier scales raw meter readings to actual energy or demand and equals the current transformer ratio multiplied by the potential transformer ratio.
- ASHRAE audit levels
- ASHRAE defines Level 1 as a preliminary walk-through, Level 2 as an energy survey and analysis, and Level 3 as an investment-grade analysis.
- Blower door test
- A blower door test pressurizes a building to measure envelope airtightness, reported as air changes per hour at a specified pressure difference.
- Simple payback
- Simple payback equals the initial capital cost divided by annual energy cost savings; it does not account for time value of money or savings after payback.
- Levelized cost of energy
- Levelized cost of energy equals the present value of life-cycle costs divided by the present value of energy output over the analysis period.
- IPMVP Option C
- IPMVP Option C measures savings for a whole facility using utility meters and a baseline adjusted for weather, occupancy, or production changes.
- Commissioning OPR
- The owner's project requirements document states the owner's functional needs, performance criteria, and expectations that commissioning verifies against the design.
- M&V savings equation
- Measurement and verification savings equal adjusted baseline energy minus reporting-period energy, with adjustments for weather, occupancy, production, and other independent variables.
- Chiller kW per ton
- Chiller efficiency in kW per ton equals input power in kilowatts divided by cooling output in tons; lower values indicate better efficiency.
- Economizer operation
- An air-side economizer uses cool outdoor air instead of mechanical cooling when outdoor air temperature or enthalpy is below the return air condition.
- Compressed air specific power
- Compressed air specific power is input kilowatts divided by delivered flow in hundreds of cubic feet per minute; leaks and pressure drop increase it.
- Steam trap failure
- A failed-open steam trap wastes live steam, while a failed-closed trap traps condensate, reduces heat transfer, and can cause water hammer.
- CHP total efficiency
- Combined heat and power total efficiency equals useful electric output plus useful thermal output divided by total fuel energy input.
- Topping-cycle CHP
- A topping-cycle CHP system generates electricity first and then recovers exhaust or jacket heat for thermal loads such as steam, hot water, or absorption cooling.