AEE Certified Energy Auditor study materials
AEE Certified Energy Auditor study resources

AEE Certified Energy Auditor cheat sheet

AEE Certified Energy Auditor · Keep the key ideas within reach.

Quick reference

Developing an Energy Audit Strategy & Plan

  • ASHRAE Level 1 (walk-through) uses 12 months of utility bills plus a brief site walk to identify no- and low-cost measures and a preliminary EUI benchmark.

  • Level 2 (energy survey and analysis) adds an end-use breakdown, a bin or hourly model, and cost and payback estimates for each recommended measure.

  • Level 3 (detailed analysis) requires a calibrated simulation, design-level scoping of capital measures, and a measurement and verification plan.

  • Define the audit boundary and baseline period (typically 12 consecutive months) before collecting data, then normalize for weather, occupancy, and floor-area changes.

  • EUI = annual site energy (kBtu or kWh) divided by conditioned floor area; benchmark it against ENERGY STAR Portfolio Manager medians for the property type.

  • Energy Cost Index (ECI) = annual utility cost divided by floor area; use it to rank buildings within a portfolio before committing audit effort.

  • Per ASHRAE Guideline 14, a monthly utility-bill regression baseline needs CV(RMSE) of 15% or less and NMBE within plus or minus 5% to be defensible.

  • Screen measures by simple payback first, then re-rank by life-cycle cost or NPV before recommending capital-intensive projects.

Quick reference

Energy Use Analysis

  • Energy balance rule: purchased energy = end-use consumption + distribution losses + conversion losses; unaccounted energy above roughly 10% of the total signals a metering or model gap.

  • Load factor = average demand divided by peak demand over the period; values below about 0.40 point to demand-charge exposure or oversized equipment.

  • Degree-day model: E = a + b x HDD for heating, E = a + b x CDD for cooling; the intercept a is the weather-independent base load.

  • A four-parameter model adds both HDD and CDD and is required when the building carries significant heating and cooling load.

  • Check demand ratchet clauses (for example, 80% of the highest monthly peak billed for 11 months) before claiming any demand savings.

  • The bin method multiplies annual hours in each temperature bin by equipment part-load performance to estimate HVAC energy without a full simulation.

  • Benchmark EUI against CBECS or ENERGY STAR medians, but adjust for operating hours, plug-load intensity, and climate zone before drawing conclusions.

  • Typical commercial end-use split is HVAC 40-60%, lighting 15-25%, and plug loads 10-20% of site energy; reconcile the split against bills rather than assuming it.

Quick reference

Data Collection & Analysis

  • Unit conversions: 1 kWh = 3,412 Btu; 1 therm = 100,000 Btu = 29.3 kWh; 1 ton of refrigeration = 12,000 Btu/h = 3.517 kW.

  • Interval data at 15-minute resolution supports load-shape, peak-demand, and schedule analysis; monthly bills cannot resolve peaks or after-hours operation.

  • Clamp-on power meters are typically accurate to plus or minus 2% of reading; verify CT ratio, phase orientation, and true-RMS capability on VFD-fed circuits.

  • For engineering measurements, a common sampling target is 90% confidence with plus or minus 10% precision.

  • Cross-check sub-metered totals against utility bills; a discrepancy over 10% indicates missing loads, CT errors, or unbilled fuel.

  • Power factor = kW divided by kVA; values below about 0.90 can trigger utility penalties and reduce usable transformer capacity.

  • Weather-normalize with TMY3 or actual station data for the baseline period, not long-run averages, when regressing consumption.

  • Document every data gap and the method used to fill it (interpolation versus engineering estimate); each number in the report must be traceable.

Quick reference

Economic Analysis

  • Simple payback (years) = total installed cost divided by annual savings; it ignores the discount rate and all savings after the payback date.

  • NPV = sum of [cash flow in year t divided by (1+i)^t] minus initial cost; accept measures with NPV greater than zero at the organization's discount rate.

  • IRR is the discount rate that drives NPV to zero; compare it against the hurdle rate, commonly 8-12% for public and higher for private capital.

  • Capital recovery factor CRF = i(1+i)^n divided by [(1+i)^n - 1]; annualized cost = initial cost x CRF.

  • Life-cycle cost analysis must include energy escalation, O&M, replacement, and salvage over the study period, typically 20-30 years.

  • Use real discount rates with real escalation rates, or nominal with nominal; mixing the two distorts NPV.

  • Levelized cost of conserved energy = (annualized capital + incremental O&M) divided by annual kWh saved; compare it with the utility's marginal rate.

  • Value demand savings at the marginal demand charge plus any ratchet effect, and value energy savings at the marginal rather than average energy rate.

Quick reference

Lighting Systems

  • Efficacy in lm/W: incandescent 10-17, halogen 15-25, T8 fluorescent 85-100, metal halide 60-100, high-pressure sodium 80-140, LED 100-160 and higher.

  • Lumen method: N = (E x A) divided by (lumens per luminaire x CU x LLF), where E is the target maintained illuminance and A is the area.

  • LLF = lamp lumen depreciation x luminaire dirt depreciation x ballast factor; typical design values fall between 0.70 and 0.85.

  • LPD = total connected lighting watts divided by floor area; compare against the ASHRAE 90.1 space-by-space allowance before proposing a retrofit.

  • Occupancy sensors save roughly 20-30% in intermittently occupied spaces such as restrooms, private offices, and conference rooms.

  • Photosensor daylight dimming in perimeter zones typically saves 20-40% of the lighting energy in those zones.

  • Replacing T12 fixtures with magnetic ballasts by T8 lamps with electronic ballasts cuts lighting energy about 35-45% at comparable light output.

  • For any LED retrofit, verify delivered lumens, CCT, CRI, L70 driver life, dimming compatibility, and that existing wiring and voltage drop support the new load.

Quick reference

Heating, Ventilation & Air Conditioning Systems

  • COP = cooling output in kW divided by electrical input in kW; EER = Btu/h divided by watts; EER = 3.412 x COP; kW/ton = 12 divided by EER.

  • Affinity laws for fans and pumps: flow varies with speed, head with speed squared, power with speed cubed; a 20% speed reduction cuts power about 49%.

  • An air-side economizer is beneficial when outdoor air enthalpy (or dry-bulb in arid climates) is below the return-air condition.

  • Chilled-water supply reset upward and condenser-water reset downward each save roughly 1-2% of chiller energy per degree Fahrenheit within design limits.

  • Boiler stack loss rises about 1% per 40 degrees Fahrenheit of excess flue-gas temperature; target roughly 15% excess air on natural-gas boilers.

  • Condensing boilers only capture latent heat when return water is below about 130 degrees Fahrenheit; without low return temperature the condensing premium is lost.

  • Demand-controlled ventilation with CO2 sensors saves fan and conditioning energy wherever occupancy varies widely.

  • Night setback saves roughly 1-3% of heating or cooling energy per degree Fahrenheit of setback held for 8 hours, depending on envelope and thermal mass.

  • Verify economizer dampers, linkages, and changeover sensors during the audit; failed economizers are common and invisible in utility bills.

Quick reference

Domestic Hot Water Systems

  • DHW energy: Q in Btu = gallons x 8.33 lb/gal x 1.0 Btu/(lb x degree F) x temperature rise; divide by system efficiency to get input energy.

  • Store hot water at 140 degrees Fahrenheit or above where Legionella risk exists, and temper down to no more than 120 degrees Fahrenheit at the fixture to prevent scalding.

  • Standby loss dominates low-use DHW systems; inspect tank insulation R-value, pipe insulation coverage, and recirculation loop controls.

  • Continuous recirculation can waste 15-25% of DHW energy; timer-based or demand-controlled recirculation reduces that loss substantially.

  • Heat-pump water heaters deliver COP of 2-3 but need roughly 700-1,000 cubic feet of tempered air and add a space-cooling load.

  • Condensing gas water heaters reach UEF above 0.90, while atmospheric units with standing pilots typically rate 0.55-0.65.

  • Low-flow fixtures (1.5 gpm showerheads, 0.5 gpm aerators) cut hot-water draw without requiring occupant behavior change.

  • Drain-water heat recovery units reclaim 40-60% of the heat in greywater and perform best on showers with high simultaneous flow.

Quick reference

Motors & Drives & Compressed Air Systems

  • Motor efficiency classes are IE1 standard, IE2 high, IE3 premium (NEMA Premium), and IE4 super-premium; size motors to run in the 75-100% load band.

  • Slip-method load estimate: load fraction = (synchronous speed - measured speed) divided by (synchronous speed - rated full-load speed).

  • Rewind versus replace: replace when rewind cost exceeds about 50-60% of a new premium-efficiency motor or when rewind efficiency loss exceeds 1-2%.

  • VFDs on variable-torque loads such as fans and pumps capture cube-law savings; on constant-torque loads, savings scale linearly with speed.

  • Compressed air specific power is typically 18-22 kW per 100 cfm at 100 psig, and one horsepower of compressor delivers roughly 4-5 cfm.

  • Lowering system pressure by 2 psi reduces compressor energy about 1%; every 2 psi of unnecessary pressure carries a measurable annual cost.

  • Leaks typically waste 20-30% of compressed air output; an ultrasonic leak survey belongs in every compressed-air audit.

  • Storage sizing: 1-3 gallons per cfm for demand events, up to 5 gallons per cfm on highly fluctuating systems, located near the largest loads.

  • Heat recovery from air- or oil-cooled compressors can supply 50-90% of compressor input energy as useful hot water or space heating.

Quick reference

Building Envelope

  • Conductive heat flow Q = U x A x delta-T; the U-factor is the reciprocal of the R-value (U = 1/R).

  • Insulation R-values add in series only; thermal bridging through steel studs, slab edges, and shelf angles substantially reduces the effective assembly R-value.

  • Blower-door CFM50 divided by roughly 20 approximates natural infiltration, and 0.1-0.3 ACH50 per 1,000 square feet of envelope is a common tightness range.

  • Window performance requires three numbers: U-factor for conduction, SHGC for solar gain, and visible transmittance for daylight.

  • In cooling-dominated climates specify SHGC of 0.25-0.35 to cut solar gain; in heating-dominated climates keep higher SHGC on south-facing glass.

  • Cool roofs are characterized by solar reflectance and thermal emittance, which combine into the Solar Reflectance Index.

  • Air sealing typically saves 5-15% of heating and cooling energy, but only when the envelope is a dominant loss and ducts sit inside the boundary.

  • Continuous rigid insulation above the roof deck avoids the thermal bridging that batt insulation between joists leaves in place.

Quick reference

BAS, PAS, and EMCS

  • BAS architecture: field sensors and actuators feed DDC controllers, which report to a supervisory workstation over BACnet, Modbus, or LonWorks.

  • EMCS is the legacy term for a building automation system with energy functions such as scheduling, duty cycling, demand limiting, and optimal start.

  • PAS (process automation system) applies the same control and trending logic to industrial process loops, where setpoint and sequencing savings often exceed HVAC savings.

  • Optimal start uses indoor and outdoor temperature and building mass to reach setpoint exactly at occupancy, eliminating unnecessary pre-conditioning hours.

  • Scheduling and night setback are the highest-value, lowest-cost BAS measures; audit the programmed schedule against actual occupancy.

  • Reset schedules for supply-air temperature, chilled-water temperature, duct static pressure, and condenser-water temperature deliver persistent savings with no hardware.

  • Trend logs at 15-minute intervals supply the data for measurement and verification and for fault detection; confirm the trends exist and cover the baseline period.

  • Demand limiting sheds non-critical loads as interval kW approaches a target, reducing demand charges and ratchet exposure.

  • Fault detection and diagnostics rules catch simultaneous heating and cooling, stuck dampers, and sensor drift that utility bills cannot reveal.

Quick reference

Alternative Generation & Storage

  • PV annual energy (kWh) is approximately system kW x peak sun hours x 365 x derate factor, where derate is typically 0.75-0.85 for wiring, inverter, soiling, and temperature losses.

  • Standard test conditions are 1,000 W/m² irradiance at 25 degrees Celsius cell temperature; module output falls roughly 0.3-0.5% per degree Celsius above 25.

  • Wind power scales with air density x rotor area x velocity cubed; the Betz limit caps extraction at 16/27, or about 59.3%, of the wind's kinetic energy.

  • CHP efficiency = (electric output + useful thermal output) divided by fuel input; well-designed systems reach 75-85% versus about 50% for separate generation.

  • Storage sizing: usable kWh = rated kWh x depth of discharge; delivered kWh = usable kWh x round-trip efficiency, which is 85-95% for lithium-ion.

  • Storage value streams include demand-charge reduction, time-of-use arbitrage, peak shaving, backup capacity, and demand-response revenue.

  • Ground-source heat pumps reach COP of 3-5 by exploiting stable ground temperature; ground-loop sizing dominates first cost.

  • Net metering and interconnection tariffs set the value of exported generation; confirm the tariff structure before sizing the array.

Quick reference

Transport

  • Fleet fuel use = miles divided by MPG; report gallons per 100 miles so vehicles of different sizes can be compared on equal footing.

  • Idling burns roughly 0.5-1.0 gallon per hour in light trucks; anti-idling policy and auxiliary power units eliminate that consumption.

  • Fuel economy drops sharply above 50 mph because aerodynamic drag rises with the square of speed; speed governance is a measurable efficiency measure.

  • Under-inflated tires raise fuel consumption about 1-3% for every 10 psi below the recommended cold pressure.

  • Electric vehicle efficiency is expressed in miles per kWh; a typical light-duty EV uses 0.25-0.35 kWh per mile.

  • Tailpipe CO2 is about 8.89 kg per gallon of gasoline and 10.18 kg per gallon of diesel; well-to-wheel accounting adds fuel production and delivery emissions.

  • Route optimization and telematics typically cut fleet fuel 5-15% through fewer miles driven and improved driver behavior.

  • Alternative-fuel decisions require total cost of ownership: vehicle price premium, fuel cost per diesel-gallon-equivalent, infrastructure, and maintenance.