- Ohm's Law
- Voltage equals current multiplied by resistance (V = I × R). Used to compute expected current, voltage drop, or resistance in any low-voltage circuit.
- Power formula
- Electrical power equals voltage times current (P = V × I), also expressed as I²R or V²/R. Determines conductor sizing and heat generation.
- Series circuit rule
- Total resistance is the sum of individual resistances, and the same current flows through every component. Voltage divides proportionally across each element.
- Parallel circuit rule
- Reciprocal of total resistance equals the sum of reciprocals of branch resistances. Voltage is identical across all branches and current divides.
- Decibel definition
- A logarithmic ratio: 20 log10(V2/V1) for voltage or 10 log10(P2/P1) for power. A 6 dB voltage increase doubles signal level.
- TIA-568 channel length
- Copper horizontal channel maximum is 100 meters, comprising 90 meters of permanent link plus up to 10 meters of patch cords at each end.
- Category 6A distance
- Category 6A balanced twisted-pair supports 10GBASE-T to the full 100-meter channel. Category 6 supports the same rate only to 55 meters.
- T568A versus T568B
- Two pin/pair assignments for eight-position modular jacks. They differ in which pairs occupy pins 1-2 and 3-6; both ends must match.
- PoE 802.3at
- Power over Ethernet standard delivering up to 30 watts at the power sourcing equipment and 25.5 watts at the powered device over two pairs.
- Fiber APC connector
- Angled physical contact connector with an eight-degree polished ferrule. Lower return loss than UPC but not intermateable with flat-polish connectors.
- NEC Article 725
- Governs Class 1, Class 2, and Class 3 remote-control and signaling circuits. Defines power-limited thresholds and permitted cable types.
- NEC Article 760
- Covers fire alarm systems wiring, distinguishing non-power-limited (NPLFA) from power-limited (PLFA) circuits and requiring listed fire alarm cable.
- Class A circuit
- Fire alarm signaling circuit that continues to operate with a single open or ground fault. Class B circuits lose function on a single open.
- Smoke detector spacing
- Nominal 30-foot spacing on smooth ceilings with 15 feet maximum to any wall. Always confirm with the adopted code edition and local amendments.
- NAC voltage drop
- Notification appliance circuits must deliver rated voltage to the last device. Calculate using conductor resistance and total appliance current at worst case.
- Fail-safe lock
- Access-controlled lock that unlocks when power is removed. Required where life safety egress depends on the door releasing automatically.
- OSDP protocol
- Open Supervised Device Protocol: bidirectional, encrypted reader-to-controller communication that supersedes Wiegand for secure access control installations.
- Wiegand interface
- Legacy unidirectional reader-to-controller signaling using data-zero and data-one lines. Commonly 26-bit format; not encrypted and easily compromised.
- Request-to-exit device
- Sensor or pushbutton that signals the controller to release the lock for egress. Required by life safety codes where free egress is mandated.
- RS-485 termination
- A 120-ohm resistor at each end of the bus prevents signal reflections. Mid-bus termination or missing terminators cause intermittent communication faults.
- BACnet MS/TP
- Building automation protocol running over RS-485 twisted pair. Uses a token-passing master-slave scheme for device communication on a segment.
- Modbus RTU
- Serial register-based protocol over RS-485 using binary encoding. Master polls slaves by address; no built-in authentication or encryption.
- HDBaseT extension
- Technology extending HDMI, Ethernet, and control up to 100 meters over Category 6A cable. Used for displays beyond passive HDMI cable reach.
- 70V distributed audio
- Constant-voltage speaker system using step-down transformers at each speaker. Higher voltage lowers line current and reduces conductor loss over long runs.
- Lockout tagout
- OSHA 1910.147 requirement to isolate, lock, tag, and verify de-energization before servicing equipment. Each worker applies a personal lock.
- Arc flash boundary
- Distance at which incident energy equals 1.2 calories per square centimeter. Inside this boundary, arc-rated PPE is required per NFPA 70E.
- Assured grounding program
- OSHA alternative to GFCI on construction sites: tools are tested, logged, and inspected on a documented schedule with visual checks before each shift.
- GFCI on construction
- Temporary receptacles on construction sites require ground-fault protection unless an assured equipment grounding conductor program is implemented and documented.
- TDR testing
- Time-domain reflectometer sends a pulse and measures reflections to locate opens, shorts, and cable length. Common on copper cabling commissioning.
- OTDR testing
- Optical time-domain reflectometer characterizes fiber by measuring backscatter and reflections. Locates breaks, splices, and connector loss along the link.
- Insulation resistance test
- Megohmmeter applies DC voltage to measure leakage between conductors or to ground. Low readings indicate moisture, damage, or contamination in the cable.
- Ground loop symptom
- Hum in audio, rolling bars in video, or intermittent data caused by multiple ground references. Resolve with isolation or single-point grounding.