AK Water Operator flashcards
AK Water Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- MCL
- Maximum Contaminant Level: the highest legally allowed concentration of a contaminant in drinking water, enforceable under the Safe Drinking Water Act.
- Secondary standard (SMCL)
- A non-enforceable aesthetic guideline for contaminants affecting taste, odor, color, or appearance, such as iron, manganese, or sulfate.
- Turbidity limit
- For conventional filtration, turbidity must be 0.3 NTU or less in at least 95% of monthly samples and never exceed 1 NTU.
- 3-log Giardia removal
- Surface Water Treatment Rule requires 99.9% removal or inactivation of Giardia lamblia for systems using filtration.
- Nitrate MCL
- The enforceable limit for nitrate is 10 mg/L as nitrogen, protecting infants from methemoglobinemia (blue baby syndrome).
- Velocity gradient (G)
- A measure of mixing intensity in coagulation and flocculation, typically 10-75 per second for flocculation and 100-300 for rapid mix.
- Surface overflow rate
- Sedimentation design parameter equal to flow divided by basin surface area, typically 0.5-1.0 gpm/ft2 for conventional plants.
- CT value
- Product of disinfectant residual concentration in mg/L and contact time in minutes, used to determine pathogen inactivation credit.
- Backwash media expansion
- Filter backwash should expand the media bed 15-25% to release captured particles without washing media out of the filter.
- Minimum distribution pressure
- Distribution systems must maintain at least 20 psi under normal and emergency conditions to prevent backflow and contamination.
- Air gap
- The highest level of cross-connection protection: a physical separation between the water supply outlet and the flood-level rim of a receiving vessel.
- Unidirectional flushing
- A flushing method that isolates pipe sections and pushes water at 2.5-5 ft/s from clean to dirty areas to scour sediment.
- Main disinfection after repair
- New or repaired mains are chlorinated to 25-50 mg/L for 24 hours or per AWWA C651, then flushed and tested for coliforms.
- Pump head from pressure
- Head in feet equals pressure in psi multiplied by 2.31; conversely, psi equals feet of head divided by 2.31.
- Brake horsepower formula
- Brake horsepower equals (gpm x head in feet) divided by (3960 x pump efficiency), giving power delivered to the pump.
- Affinity laws
- For a centrifugal pump, flow varies with speed, head with speed squared, and power with speed cubed.
- Cavitation
- Vapor bubbles form and collapse when NPSH available is less than NPSH required, causing noise, vibration, and impeller damage.
- NPSH
- Net Positive Suction Head: the absolute pressure energy at the pump suction, available versus required, to prevent cavitation.
- HOCl versus OCl-
- Free chlorine exists as hypochlorous acid and hypochlorite ion; HOCl is the stronger disinfectant and dominates below pH 7.5.
- Chlorine demand
- The difference between chlorine dose applied and the free chlorine residual remaining after a specified contact time.
- TTHM MCL
- The maximum contaminant level for total trihalomethanes is 0.080 mg/L, evaluated as a locational running annual average.
- HAA5 MCL
- The maximum contaminant level for five haloacetic acids is 0.060 mg/L, evaluated as a locational running annual average.
- Chloramination ratio
- Monochloramine forms best at pH 8-9 with a chlorine-to-ammonia weight ratio near 5:1, reducing regulated disinfection byproducts.
- DPD method
- A colorimetric test for free and total chlorine; total minus free approximates combined chlorine (chloramines).
- Jar test
- A bench-scale test simulating rapid mix, flocculation, and settling at varying coagulant doses to determine optimal treatment conditions.
- Bacteriological holding time
- Coliform samples must be chilled and analyzed within holding time, typically 8 hours when chlorine residual is measured, 30 hours otherwise.
- Tier 1 public notice
- Public notice required within 24 hours for violations posing immediate health risk, such as E. coli detection or failure to maintain pressure.
- Consumer Confidence Report
- An annual report delivered to customers by July 1 describing source water, detected contaminants, and compliance for the prior year.
- Lead action level
- The 90th percentile lead concentration of 0.015 mg/L; exceedance triggers corrosion control treatment and public education.
- Confined space oxygen range
- Acceptable oxygen for entry is 19.5-23.5 percent; outside this range requires ventilation and respiratory protection before entry.
- Lockout/tagout
- A procedure isolating hazardous energy sources before maintenance, verifying zero energy state to prevent unexpected startup or release.
- Dose formula
- Pounds of chemical equals dose in mg/L multiplied by 8.34 and by million gallons treated.