Quick reference

Protective Coatings

  • Barrier, inhibitive, and sacrificial are the three primary protection mechanisms; zinc-rich primers protect by galvanic action, while epoxies typically protect by barrier effect.

  • Dry film thickness (DFT) is measured on the cured film; wet film thickness (WFT) relates to DFT by WFT = DFT / volume solids fraction.

  • Volume solids is the fraction of a coating that remains after solvent evaporates; it drives coverage, VOC, and required WFT to reach a target DFT.

  • Coverage in square feet per gallon at 1 mil DFT = 1604 x (volume solids fraction); divide by target DFT in mils for actual coverage.

  • Critical pigment volume concentration (CPVC) is the pigment level above which binder no longer fully encapsulates particles; exceeding CPVC causes porosity, blistering, and loss of barrier protection.

  • Surface preparation standard for a given coating is set by the coating manufacturer; abrasive blast profiles typically fall in the 1.5 to 4 mil range depending on coating type.

  • Ambient cure conditions: substrate temperature must be at least 5 degrees F (3 degrees C) above dew point, and relative humidity and temperature must fall within the product data sheet range.

  • Epoxy coatings chalk and lose gloss under UV exposure; aliphatic polyurethanes or polysiloxanes are specified for exterior color and gloss retention.

  • Pot life is the usable time after mixing a multi-component coating; exceeding pot life degrades adhesion and cure and requires discarding the mixed material.

Quick reference

Coatings Inspection

  • Inspection holds are points where work cannot proceed without inspector sign-off: typically pre-surface-prep, post-surface-prep, primer application, and final DFT/continuity.

  • SSPC-SP 10 / NACE No. 2 (near-white blast) permits staining on no more than 5 percent of each unit area; SSPC-SP 5 / NACE No. 1 (white metal) permits no visible residue.

  • Blast profile is measured by replica tape (press-o-film) or by comparator; surface cleanliness by solvent rub, soluble salt test (Bresle or sleeve), or visual comparator.

  • Soluble salt contamination is measured in conductivity units; common acceptance limits are on the order of 3 to 5 microsiemens/cm depending on the specification.

  • DFT on steel is measured with magnetic pull-off or magnetic induction gauges; on non-ferrous substrates an eddy-current gauge is used.

  • A Type 1 or Type 2 DFT gauge requires calibration verification against foils or a known standard before and after each inspection series.

  • Holiday/continuity testing: low-voltage wet-sponge for thin films, high-voltage spark tester for thick films; voltage must be set per the specification and film thickness.

  • Adhesion is verified by pull-off (ASTM D4541) or cross-cut/knife tests; cohesive failure within the coating differs from adhesive failure at the substrate interface.

  • Environmental readings (ambient and substrate temperature, dew point, RH) are recorded before, during, and after application to document compliance with the product data sheet.