Boiler Inspection

  • External inspection: covers shell, fittings, piping, insulation, supports, and accessible safety devices without opening the boiler.

  • Internal inspection: requires the boiler to be cooled, drained, opened, and cleaned so shell, tubes, sheets, and stays can be examined.

  • Hydrostatic test: boiler filled with water and pressurized to the required test pressure; used when visual inspection cannot resolve strength questions.

  • Inspection certificate records the maximum allowable working pressure (MAWP) established by the inspector, not the relief valve setting alone.

  • Ultrasonic thickness testing is used to evaluate wall loss from corrosion or erosion when surfaces are pitted or scaled.

  • Inspectors look for caustic embrittlement, grooving, cracking at staybolts, and ligament cracks between tube holes.

  • Safety valve test lever must be lifted during inspection to confirm the valve opens freely and reseats.

  • A boiler with a defective safety valve or low-water fuel cutoff is not eligible for a certificate until repaired and reinspected.

Quick reference

Licensing and Permits

  • Operating a boiler without a valid certificate of inspection where one is required is a violation enforceable by the state boiler authority.

  • Boiler operator licenses are issued by grade/class and authorize operation only of boilers within that class's size or pressure limits.

  • License renewal typically requires documented continuing education hours and payment of a renewal fee before expiration.

  • New installations require an installation permit and a plan review before construction or relocation begins.

  • Certificate of inspection is posted at or near the boiler and is available for review by the inspector on arrival.

  • Operating a boiler outside the scope of the operator's license grade can result in suspension or revocation of the license.

  • Repairs to pressure-retaining parts require approval of the inspector and use of qualified welders with documented procedures.

Quick reference

Boiler Construction

  • MAWP is calculated from shell thickness, diameter, joint efficiency, and allowable stress using the applicable ASME code formula.

  • Longitudinal seam joint efficiency depends on the type of welded or riveted joint; higher efficiency permits higher MAWP for the same thickness.

  • Staybolts support flat surfaces; their size, spacing, and pattern are governed by code rules for stayed surfaces.

  • Safety valve capacity must equal or exceed the boiler's maximum steaming capacity at MAWP.

  • Boiler shells are built from steel plate with welded longitudinal and circumferential seams; riveted construction appears in older units.

  • Handhole and manhole openings require reinforcement when they remove metal from a pressure-retaining surface.

  • Tube sheets, tubes, and firebox sheets are pressure parts; their thickness and support determine allowable pressure.

  • Nameplate data includes MAWP, design pressure, heating surface, and manufacturer; it must match the certificate records.

Quick reference

Installation and Repair

  • Boilers must be set level with adequate clearance for inspection, cleaning, and access to safety devices and fittings.

  • Steam and water connections must include required valves, check valves, and drains arranged so the boiler can be isolated.

  • Safety valve discharge piping must be independent, unobstructed, and drain freely so no back pressure builds on the valve.

  • Repairs by welding on pressure parts require qualified welders, approved procedures, and post-repair inspection or testing.

  • After major repairs, a hydrostatic test at the required pressure is performed before the boiler is returned to service.

  • Combustion air supply and venting must be sized for the burner input; inadequate air causes incomplete combustion and CO.

  • Refractory, insulation, and casing must be reinstalled so the boiler is not left with hot spots or exposed pressure parts.

  • Inspector notification is required before covering up concealed work on pressure parts so it can be examined.

Quick reference

Boiler Operation, Maintenance and Safety Devices

  • Low-water fuel cutoff must be tested by evaporating or draining water to the cutoff level and confirming burner shutdown.

  • Safety valve setting is the boiler's maximum allowable working pressure; the valve must open at or below that setting.

  • Try cocks and gauge glass are used to verify water level; the gauge glass must be blown down to confirm it is not plugged.

  • Bottom blowdown removes sludge and sediment; it is done with the boiler at low fire and the water level watched closely.

  • Water column and gauge glass connections must be kept clear; a clogged connection gives a false water level reading.

  • High-pressure and high-temperature limits, flame scanners, and combustion safeguards are tested per the manufacturer's schedule.

  • Feedwater treatment controls scale, corrosion, and carryover; blowdown frequency is set by tested water chemistry.

  • A boiler with a tripped low-water cutoff must not be restarted until the cause is found and water level is restored.

Quick reference

Arkansas Boiler Law and Rules

  • The Arkansas Boiler Safety Act is administered by the state boiler inspection authority within the labor department.

  • Boilers must be inspected at the intervals set by rule; the certificate of inspection is issued only after a satisfactory inspection.

  • The inspector may order a boiler taken out of service when it is unsafe, and operation after that order is prohibited.

  • Rules adopt recognized codes such as ASME for construction and NBIC for repairs and alterations.

  • Owner/operator must report accidents, explosions, or serious injuries involving a boiler to the authority.

  • Operating without a required certificate or license is subject to penalties under the Act.

  • Exemptions from the Act are limited and defined by rule; operators should confirm applicability rather than assume exemption.