ASSE 5110 key terms
ASSE 5110 · Get comfortable with the vocabulary.
- Cross-connection
- Related: Backflow, Backsiphonage, Air gap
Any actual or potential physical connection between a potable water supply and a source of contamination or pollution that could allow non-potable fluid to enter the drinking water.
- Backflow
- Related: Backsiphonage, Backpressure, Cross-connection
The unwanted reverse flow of water or other fluid from a non-potable source into the potable water distribution system, occurring by either backsiphonage or backpressure.
- Backsiphonage
- Related: Backpressure, Barometric loop
Backflow caused by negative or sub-atmospheric pressure in the supply piping, which draws non-potable fluid through a cross-connection into the potable system.
- Backpressure
- Related: Backsiphonage, Backflow
Backflow caused when downstream pressure exceeds supply pressure, pushing non-potable fluid backward into the potable system, often from pumps, boilers, or elevated piping.
- Contaminant
- Related: Health hazard, Degree of hazard
Any substance that, if introduced into drinking water, could cause illness, injury, or death, as opposed to a pollutant, which only affects taste, odor, or appearance.
- Air gap
- Related: Flood-level rim, Reduced pressure principle assembly
An unobstructed vertical physical separation between the lowest point of a potable water outlet and the flood-level rim of the receiving vessel; it provides the highest degree of cross-connection protection.
- Flood-level rim
- Related: Air gap
The edge of a receiving vessel, fixture, or tank over which water would overflow, used as the reference point for measuring air gap separation.
- Reduced pressure principle assembly
- Related: Differential relief valve, Test cock, Double check valve assembly
A testable assembly containing two independently acting spring-loaded check valves with a hydraulically operated differential relief valve between them, used for high-hazard protection.
- Reduced pressure detector assembly
- Related: Reduced pressure principle assembly, Double check detector assembly
A reduced pressure principle assembly combined with a meter and bypass that detects low flows, used on fire lines where high-hazard protection and flow measurement are both needed.
- Double check valve assembly
- Related: Check valve, Reduced pressure principle assembly
A testable assembly of two spring-loaded check valves in series used for low-hazard protection; it has no relief valve and cannot discharge to atmosphere.
- Double check detector assembly
- Related: Double check valve assembly
A double check valve assembly combined with a bypass and detector meter, commonly installed on fire protection systems to reveal leaks or unauthorized water use.
- Pressure vacuum breaker
- Related: Air inlet opening point, Spill-resistant vacuum breaker, Atmospheric vacuum breaker
A testable vacuum breaker with a spring-loaded check and an air inlet that opens at low supply pressure; it must be installed above downstream piping and cannot be under continuous pressure.
- Spill-resistant vacuum breaker
- Related: Pressure vacuum breaker
A spill-resistant vacuum breaker similar in function to a pressure vacuum breaker but designed not to spill water during normal operation, so it may be used where discharge is objectionable.
- Atmospheric vacuum breaker
- Related: Air inlet opening point, Pressure vacuum breaker
A non-testable vacuum breaker with a float-operated air inlet and no spring; it must be downstream of the last control valve and cannot be under continuous pressure.
- Hose-connection vacuum breaker
- Related: Atmospheric vacuum breaker
A small non-testable, non-removable device threaded onto a hose bibb to stop backflow through the hose by admitting air during backsiphonage.
- Dual check valve
- Related: Double check valve assembly
A non-testable, non-removable assembly of two check valves used on low-hazard residential or appliance connections where routine field testing is not required.
- Barometric loop
- Related: Backsiphonage
A fixed inverted U of piping rising at least 35 feet above the highest downstream outlet, which prevents backsiphonage by keeping an air column but gives no backpressure protection.
- Check valve
- Related: Double check valve assembly, Seat disc fouling
A one-way valve that permits flow in one direction only and closes to stop reverse flow; it is the basic working component of every mechanical backflow preventer.
- Differential relief valve
- Related: Reduced pressure principle assembly, Relief valve opening point
The hydraulically operated valve in a reduced pressure principle assembly that opens to atmosphere when the pressure differential between the two check valves falls below a set minimum.
- Test cock
- Related: Differential pressure gauge, Sight tube
A small numbered quarter-turn valve installed on a backflow assembly, used to connect test equipment and to apply or read pressure at specific points during field testing.
- Sight tube
- Related: Test cock
A clear plastic or glass tube on test equipment that lets the tester see water discharge or air movement, confirming a valve has opened during a test.
- Differential pressure gauge
- Related: Gauge calibration, Test cock
An instrument that measures the difference between two pressures, used to verify the pressure drop across check valves and the opening point of a relief valve.
- Hold-tight test
- Related: Check valve, Seat disc fouling
A field test in which pressure is applied to one side of a check valve and watched for a set period to confirm the valve seals and holds.
- Relief valve opening point
- Related: Differential relief valve
The pressure differential at which the differential relief valve of a reduced pressure assembly opens and begins discharging water to atmosphere.
- Air inlet opening point
- Related: Pressure vacuum breaker, Atmospheric vacuum breaker
The vacuum or pressure condition at which the air inlet of a vacuum breaker opens, admitting air to break the vacuum and stop backsiphonage.
- Cross-connection control program
- Related: Containment, Isolation, Authority having jurisdiction
An organized local effort combining surveys, regulations, device installation, periodic testing, and recordkeeping to keep contaminants out of the potable water system.
- Containment
- Related: Isolation, Cross-connection control program
Protecting the public water distribution system at the service connection or property line so contamination originating on a premises cannot reach the water main.
- Isolation
- Related: Containment
Protecting potable water inside a building by installing backflow protection at each point of use or at the branch serving a hazardous fixture or process.
- Degree of hazard
- Related: Health hazard, Contaminant
A classification of the risk a cross-connection poses, separating health hazards involving toxic or illness-causing substances from non-health hazards that affect only aesthetics.
- Health hazard
- Related: Degree of hazard, Reduced pressure principle assembly
A cross-connection that could introduce contaminants able to cause illness, injury, or death, requiring the highest protection such as an air gap or reduced pressure assembly.
- Authority having jurisdiction
- Related: Cross-connection control program, Test report form
The agency or official that enforces cross-connection control rules, approves devices and installations, and reviews test reports submitted for a water system.
- Annual testing
- Related: Test report form, Certified tester
The periodic field verification, typically every twelve months or as the local program requires, that a testable assembly's check valves and relief valve function correctly.
- Thermal expansion
- Related: Water hammer
The pressure rise created when water is heated in a closed system that has no provision for expansion, capable of damaging assemblies, check valves, and plumbing.
- Water hammer
- Related: Thermal expansion, Check valve
A pressure surge produced by a sudden change in water velocity, capable of damaging check valves, seat discs, and gauges unless controlled by arrestors or slow-closing valves.
- Seat disc fouling
- Related: Check valve, Rebuild kit, Hold-tight test
The buildup of debris, scale, or mineral deposits on a check valve seat or disc, a frequent cause of leakage and failed tightness tests.
- Rebuild kit
- Related: Seat disc fouling
A manufacturer-supplied set of replacement parts such as seats, discs, springs, and O-rings, used to restore a backflow assembly to reliable working condition.
- Gauge calibration
- Related: Differential pressure gauge
The documented verification, usually performed annually, that field test gauges read within the allowed tolerance when compared with a certified reference standard.
- Certified tester
- Related: Test report form, Annual testing
A person who has passed an approved competency examination and holds current credentials permitting them to field test backflow prevention assemblies in a given jurisdiction.
- Test report form
- Related: Certified tester, Authority having jurisdiction
A standardized record documenting assembly type, size, location, serial number, test results, and tester certification details, submitted to the water supplier or authority.