Turbine Operation (TO) flashcards
Turbine Operation (TO) · Build recall with a focused review session.
35 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Isentropic efficiency
- Ratio of actual enthalpy drop across a turbine stage or cylinder to the ideal isentropic enthalpy drop for the same inlet and outlet pressures; typically 80-90% for large steam turbines.
- Rankine cycle
- Ideal steam power cycle with pump, boiler, turbine, and condenser; efficiency improves with higher steam temperature and pressure and with lower condenser pressure.
- Nozzle choking
- Condition where steam velocity reaches sonic at the nozzle throat; further downstream pressure reduction does not increase mass flow, which then depends only on upstream conditions.
- Degree of reaction
- Fraction of stage enthalpy drop occurring in the rotor; a 50% reaction stage has equal enthalpy drops in stator and rotor and symmetrical velocity triangles.
- Heat rate
- Thermal energy input per unit electrical output, usually kJ/kWh; lower heat rate means higher efficiency and is calculated as 3600 divided by thermal efficiency.
- Fir-tree blade root
- Serrated root profile that transmits centrifugal load to the rotor disc through multiple contact surfaces; used on long blades and inspected for fretting and cracking.
- Gland steam system
- Supplies low-pressure steam to shaft-end labyrinth seals to prevent air ingress into the condenser vacuum and steam escape into the turbine hall.
- Kingsbury thrust bearing
- Tilting-pad thrust bearing that carries residual axial thrust not balanced by the dummy piston; pad temperature and oil flow are monitored during operation.
- Surface condenser
- Shell-and-tube heat exchanger that condenses exhaust steam on the shell side using cooling water in tubes; maintains vacuum and returns condensate to the feedwater system.
- Turning gear
- Low-speed barring device that rotates the rotor after shutdown to prevent thermal bowing from uneven cooling; interlocked against engagement at high shaft speed.
- Differential expansion
- Difference in thermal growth between rotor and casing along the axis; excessive positive or negative values cause axial rubs and are a key startup and trip parameter.
- Critical speed
- Shaft rotational speed at which a natural frequency of the rotor-bearing system is excited; speeds must be passed rapidly during startup and never held.
- Cold start
- Startup where turbine metal temperatures are near ambient, requiring slow steam admission and gradual loading to limit thermal stress and differential expansion.
- Water induction
- Entry of water into the turbine from drains, attemperation, or boiler carryover; causes thermal shock, water hammer, and blade damage, requiring immediate trip.
- Speed droop
- Governor characteristic where a frequency change of a set percentage (typically 4-5%) causes output to change from zero to full load; supports load sharing among units.
- Overspeed trip
- Independent protection that closes main stop and control valves when speed reaches about 110-111% of rated; tested periodically by mechanical or electronic means.
- Fail-safe trip design
- Protection philosophy where loss of control power or hydraulic pressure causes valves to close and the unit to trip, so failures default to a safe state.
- First-out indication
- Control system function that identifies the first trip signal in a sequence, helping operators determine the initiating cause among multiple subsequent alarms.
- Proximity probes
- Eddy-current sensors mounted on bearing housings that measure shaft-relative vibration and axial position, feeding protection and diagnostic systems.
- Load rejection
- Sudden loss of electrical load while the unit is running; bypass valves and speed control act to prevent overspeed, and the unit may run back to house load.
- Reverse power protection
- Relay that trips the generator breaker when power flows into the generator from the grid, preventing turbine blade overheating from motoring and windage.
- Bearing metal temperature
- Temperature measured by embedded RTDs in bearing pads; rising values indicate oil starvation, misalignment, or overload and lead to alarm or trip.
- Condenser vacuum loss
- Rise in exhaust pressure from air in-leakage, cooling-water loss, or fouling; raises exhaust hood temperature and risks LP blade overheating, requiring load reduction or trip.
- Non-destructive examination
- Inspection methods such as dye penetrant, magnetic particle, ultrasonic, and eddy current used to detect cracks and defects without damaging turbine components.
- Overspeed test
- Periodic verification that the overspeed trip operates at its setpoint, performed by actual overspeed or by a test device that simulates trip conditions.
- Valve stroke test
- Scheduled test that moves main stop and control valves through full travel to verify freedom of movement and closing time, often done before startup.
- Oil analysis
- Laboratory testing of lube oil for water content, particle count, acidity, and varnish potential to detect contamination and degradation before bearing damage occurs.
- Lockout/tagout
- Energy isolation procedure that de-energizes and locks steam, water, oil, and electrical sources before maintenance, with verification of zero energy state.
- Confined space permit
- Authorization required before entering condensers, drums, or vessels; includes atmosphere testing, ventilation, an attendant, and rescue provisions.
- Thermal discharge limits
- Regulatory limits on cooling-water return temperature and temperature rise to protect aquatic ecosystems; compliance monitored by discharge temperature records.
- Cation conductivity
- Conductivity measured after passing a sample through cation resin; sensitive indicator of dissolved ionic impurities such as chloride and sulfate in steam and condensate.
- Hydrogen purity
- Percentage of hydrogen in generator cooling gas; maintained above a set minimum, with oxygen and moisture limited to prevent arcing and corrosion of windings.
- Synchronization conditions
- Before breaker closure, generator voltage magnitude, frequency, phase angle, and phase sequence must match the grid within specified tolerances to avoid damaging transients.
- Primary frequency response
- Automatic governor response to grid frequency deviation, changing output according to droop setting to help restore system frequency within seconds.
- Loss-of-field protection
- Relay scheme that detects loss of generator excitation and trips or alarms, preventing stator overheating and unstable operation from reduced reactive support.