Quick reference

Water Sources, Hydrology, and Source Water Protection

  • The hydrologic cycle: evaporation, transpiration, condensation, precipitation, runoff, infiltration, and groundwater recharge; about 97% of Earth's water is saline, and about 2% is frozen.

  • Surface water sources include rivers, lakes, and reservoirs; groundwater sources include wells and springs, typically with higher mineral content and lower turbidity than surface water.

  • A watershed (drainage basin) is the land area that drains to a common water body; source water protection focuses on preventing contamination within the watershed.

  • Safe yield of a water source is the maximum rate of withdrawal that can be sustained without depleting the source or causing undesirable effects.

  • Wellhead protection areas are delineated by time-of-travel (e.g., 1-year, 5-year, 10-year) or by fixed radius, and land uses within them are managed to prevent contamination.

  • Groundwater flows from higher hydraulic head to lower head; Darcy's law: Q = K·i·A, where Q = flow, K = hydraulic conductivity, i = hydraulic gradient, A = cross-sectional area.

  • Total maximum daily load (TMDL) is the maximum amount of a pollutant a water body can receive and still meet water quality standards; it includes point and nonpoint sources with a margin of safety.

  • Source water assessment includes delineation of the area, inventory of potential contaminant sources, susceptibility analysis, and public availability of results.

Quick reference

Water Treatment Processes

  • Coagulation destabilizes colloidal particles by neutralizing negative surface charges; common coagulants include alum, ferric chloride, ferric sulfate, and polyaluminum chloride.

  • Flocculation is gentle mixing (typically 30–60 minutes at 10–50 rpm) that promotes collisions and growth of floc particles after coagulation.

  • Sedimentation (clarification) removes settleable solids; typical overflow rates are 0.5–1.0 gpm/ft² for conventional clarifiers, and detention time is usually 2–4 hours.

  • Filtration removes residual particles and pathogens; rapid sand filters typically operate at 2–6 gpm/ft², with media such as anthracite over sand and gravel support.

  • Filter backwash is triggered by head loss (typically 6–10 ft) or turbidity breakthrough, and uses a flow rate of 15–20 gpm/ft² for 10–15 minutes.

  • Disinfection inactivates pathogens; CT (disinfectant concentration × contact time) is used to determine inactivation credit, with CT requirements increasing at higher pH and lower temperature for chlorine.

  • Chlorine residual must be maintained throughout the distribution system; free chlorine residual is typically 0.2–4.0 mg/L, and the maximum contaminant level (MCL) for total chlorine is 4.0 mg/L.

  • Turbidity is a key treatment performance indicator; conventional filtration must produce filtered water turbidity ≤0.3 NTU in at least 95% of monthly samples, and never exceed 1 NTU.

Quick reference

Chemical Feed, Storage, and Handling

  • Chemical feed rate formula: feed rate (lb/day) = dose (mg/L) × flow (MGD) × 8.34 lb/gal.

  • For liquid chemicals, feed rate (gal/day) = (dose × flow × 8.34) / (solution strength × specific gravity × 8.34) simplifies to (dose × flow) / (solution strength × specific gravity).

  • Chlorine gas is stored in pressurized cylinders; 1 lb of chlorine gas produces about 1 lb of chlorine in water, and the gas is 2.5 times heavier than air.

  • Sodium hypochlorite (liquid bleach) degrades over time and with heat and sunlight; store in a cool, dark, ventilated area and use within recommended shelf life.

  • Chemical storage areas must have secondary containment (e.g., curbs, dikes) sized to hold at least 110% of the largest container's volume.

  • Acids and bases must be stored separately to prevent violent reactions; oxidizing agents (e.g., chlorine, permanganate) must be segregated from reducing agents and organics.

  • Chemical metering pumps (positive displacement) require calibration; stroke length and speed adjustments control feed rate, and calibration is verified by drawdown or weight checks.

  • Personal protective equipment (PPE) for chemical handling includes chemical-resistant gloves, goggles or face shield, apron, and respiratory protection as specified in the safety data sheet (SDS).

Quick reference

Pumps, Motors, Valves, and Mechanical Equipment

  • Centrifugal pumps are the most common in water systems; flow varies with head, and the pump operates at the intersection of the pump curve and system curve.

  • Cavitation occurs when the net positive suction head available (NPSHA) is less than the net positive suction head required (NPSHR); symptoms include noise, vibration, and reduced flow.

  • Pump affinity laws: flow varies directly with speed, head varies with the square of speed, and power varies with the cube of speed.

  • Motor power formula: brake horsepower (bhp) = (flow in gpm × head in ft × specific gravity) / (3960 × pump efficiency).

  • Valves: gate valves are for isolation (on/off), globe valves for throttling, butterfly valves for large-diameter isolation and some throttling, and check valves prevent backflow.

  • A pressure relief valve protects pumps and piping from overpressure; it should be set at or below the system's maximum allowable working pressure.

  • Preventive maintenance includes lubrication, vibration analysis, alignment checks, packing or mechanical seal inspection, and monitoring of bearing temperatures.

  • Electric motor current unbalance should be within 1–2%; higher unbalance causes overheating and reduced motor life.

Quick reference

Distribution Systems, Storage, and Cross-Connection Control

  • Distribution system minimum pressure is typically 20 psi under normal conditions and 20 psi during fire flow; maximum pressure is usually 100–125 psi to prevent damage.

  • Water storage tanks provide equalization, emergency reserve, and fire flow; they must maintain a chlorine residual and be inspected and cleaned periodically.

  • Cross-connections are physical links between potable and nonpotable water; they are controlled by air gaps (the only absolute protection) or by backflow prevention assemblies (RPZ, DCVA, PVB).

  • An air gap must be at least twice the diameter of the supply pipe and never less than 1 inch above the flood-level rim of the receiving vessel.

  • Backflow can occur by backpressure (downstream pressure exceeds supply pressure) or by backsiphonage (negative pressure in the supply line).

  • Reduced pressure zone (RPZ) assemblies must be tested annually by a certified tester; test results must be reported to the water utility.

  • Water mains are typically flushed to remove sediment and biofilm; flushing velocities should be at least 2.5–3.0 ft/s to achieve scouring.

  • Disinfection of new water mains typically uses a chlorine concentration of 25–50 mg/L for 24 hours, followed by flushing and bacteriological sampling.

Quick reference

Water Quality Monitoring, Sampling, and Laboratory Analysis

  • Sample collection must use clean, appropriate containers (e.g., sterile for bacteriological, amber glass for organics) and follow chain-of-custody procedures.

  • Bacteriological samples are collected in sterile bottles containing sodium thiosulfate to neutralize chlorine; sample volume is typically 100 mL.

  • Total coliform MCL: no more than 5% of monthly samples may be positive for systems collecting at least 40 samples per month; any positive sample requires repeat sampling and investigation.

  • E. coli is a fecal indicator; its presence in a distribution system requires public notification and corrective action.

  • Turbidity is measured in nephelometric turbidity units (NTU) using a nephelometer; it is a key indicator of filtration effectiveness.

  • pH is measured electrometrically with a pH meter calibrated with standard buffers (e.g., pH 4, 7, 10); it affects coagulation, disinfection, and corrosion control.

  • Chlorine residual is measured by DPD colorimetric or amperometric methods; the DPD method is common for field testing.

  • Quality control in the laboratory includes duplicates, blanks, spikes, and calibration verification to ensure accuracy and precision.

Quick reference

Regulations, Reporting, and Public Health Compliance

  • The Safe Drinking Water Act (SDWA) authorizes the EPA to set national drinking water standards; states may adopt primacy and enforce regulations.

  • National Primary Drinking Water Regulations (NPDWRs) are enforceable maximum contaminant levels (MCLs) and treatment techniques for health-related contaminants.

  • National Secondary Drinking Water Regulations (NSDWRs) are non-enforceable guidelines for aesthetic contaminants (e.g., chloride, color, odor, pH, TDS).

  • Consumer Confidence Report (CCR) must be delivered to customers annually by July 1 and include source water information, detected contaminants, and compliance status.

  • Public notification is required for violations; Tier 1 (immediate) for acute health risks within 24 hours, Tier 2 within 30 days, and Tier 3 within 90 days.

  • Lead and Copper Rule: action level for lead is 0.015 mg/L and for copper is 1.3 mg/L; compliance is based on 90th percentile of tap samples.

  • Disinfection byproducts (DBPs) regulated include total trihalomethanes (TTHM) and five haloacetic acids (HAA5), with MCLs of 0.080 mg/L and 0.060 mg/L, respectively.

  • Operator certification requirements vary by state; operators must meet education, experience, and examination requirements and complete continuing education for renewal.

Quick reference

Safety, Emergency Response, and Security

  • Confined space entry requires a permit, atmospheric testing (oxygen 19.5–23.5%, LEL <10%, H2S <10 ppm, CO <35 ppm), ventilation, attendant, and rescue plan.

  • Lockout/tagout (LOTO) procedures isolate hazardous energy sources during maintenance; only authorized employees may apply locks and tags.

  • Hazard communication (HazCom) requires safety data sheets (SDS) for each hazardous chemical and labeling of containers.

  • Chlorine gas leak response: evacuate upwind, use self-contained breathing apparatus (SCBA), and never enter a chlorine atmosphere without proper PPE.

  • Emergency response plans should address power outages, main breaks, contamination events, and natural disasters, with mutual aid agreements and emergency contact lists.

  • Security measures include fencing, locked gates, intruder detection, cybersecurity for SCADA systems, and background checks for personnel.

  • Fire safety: use appropriate fire extinguishers (Class A for ordinary combustibles, Class B for flammable liquids, Class C for electrical, Class D for metals).

  • Bloodborne pathogens and personal hygiene: wash hands, use PPE, and properly dispose of sharps and contaminated materials.