Load Calculation for a Workshop Circuit
A trade workshop has a 230 V single-phase supply protected by a 16 A miniature circuit breaker. The following equipment is connected to one radial circuit: a 1.5 kW bench grinder, a 750 W drill press, a 500 W work lamp, and a 2.2 kW welding set used intermittently. The trainee wants to run the grinder, drill press and lamp together, then start the welder without switching anything off. The cable is rated for 20 A continuous. The workshop also has a second circuit on a separate 16 A breaker that is currently unused.
1. Calculate the total current drawn by the continuously running equipment and decide whether the welder can be added to the same circuit.
Read the worked answer
Continuous load = 1500 + 750 + 500 = 2750 W.
Current = P / V = 2750 / 230 โ 11.96 A, so about 12.0 A.
Adding the welder: 2750 + 2200 = 4950 W, giving 4950 / 230 โ 21.5 A. This exceeds both the 16 A breaker rating and the 20 A cable rating. Even though the welder is intermittent, its starting surge would be higher still, so the breaker would trip.
Conclusion: the welder cannot be run on the same circuit with all three items. The trainee should move the welder to the unused second circuit, which has its own 16 A breaker, or switch off the grinder while welding. Running 21.5 A through a 20 A cable risks overheating and insulation damage.
2. Explain why the cable rating of 20 A matters even though the breaker trips at 16 A, and state one consequence of ignoring it.
Read the worked answer
The cable rating is the maximum current the conductor can carry continuously without its insulation exceeding its temperature limit. The breaker protects the circuit, but a breaker rated above the cable's capacity would allow damaging current to flow without tripping; here the 16 A breaker is below the 20 A cable rating, which is the correct arrangement.
The risk arises if someone replaces the 16 A breaker with a larger one to stop nuisance tripping. The cable would then carry more than 20 A, heat up, and its insulation could degrade and eventually fail, causing a short circuit or fire. The correct response to tripping is to reduce the load, not to uprate the breaker.