Blackout and Emergency Generator Failure in Heavy Weather

BD Marine Engineer Class 1 (Chief Engineer) · Put your knowledge to work in context.

All case studies

Blackout and Emergency Generator Failure in Heavy Weather

A 25,000 DWT bulk carrier is in heavy weather 200 nautical miles off the coast. At 2245 the main switchboard trips, causing a total blackout. The emergency generator starts automatically but fails to close its breaker; the emergency switchboard remains dead. The vessel is rolling heavily, and the steering gear has lost power. The bridge reports that the vessel is drifting toward a lee shore at about 1.5 knots. The chief engineer and the electrical officer are on watch. The emergency generator's fuel supply valve is open, but the starting battery voltage is 22 V on a 24 V system. The main engine is stopped, and the auxiliary boiler is offline.

1. What are your immediate priorities and actions to restore essential power and control the vessel?

Read the worked answer

Priorities:

  1. Restore emergency power to the emergency switchboard to supply navigation lights, radio, steering gear emergency supply, and emergency lighting.
  2. Regain steering control and propulsion as soon as possible.
  3. Prevent the vessel from drifting further toward the lee shore.

Actions:

  • Bridge team: inform the master, broadcast a safety message, and prepare for anchoring if depth and conditions permit. The master should consider requesting tug assistance.
  • Engine room: investigate why the emergency generator breaker did not close. Check the automatic voltage regulator, breaker control circuit, and the emergency generator's protection relays. With 22 V on a 24 V starting battery, the battery may be marginal; attempt a manual start or use the emergency battery charger.
  • If the emergency generator cannot be brought online, try to restore the main generator from the emergency switchboard if a tie is available, or use the emergency battery to supply essential circuits.
  • Manually operate the steering gear emergency pump if fitted, and post a helmsman with emergency steering communications.
  • Start the main engine only after essential power and steering are available, following the engine maker's blackout recovery procedure.

Documentation: Record all times, actions, and equipment status for the investigation and class reporting.

2. How should you diagnose the emergency generator breaker failure and the low battery voltage, and what would you do if the fault cannot be found quickly?

Read the worked answer

Diagnosis:

  • Breaker failure: check the closing coil, control circuit fuses, undervoltage release, and the generator's voltage and frequency before closing. Verify that the emergency generator is running at rated speed and voltage. Check the breaker's mechanical interlock and the automatic transfer scheme.
  • Battery voltage: 22 V on a 24 V system is low but may still start the engine; load-test the battery and check the charger output. Inspect terminals for corrosion and verify the charging alternator.

If the fault is not found quickly:

  • Use the emergency battery to supply essential lighting and radio if a manual connection is available.
  • Consider cross-connecting a healthy battery or using a portable charger, provided it is safe and approved.
  • Keep the bridge informed and recommend anchoring or heaving to if the vessel cannot be controlled safely.
  • Notify the company, class, and flag state as required, and prepare a formal report. Do not attempt unauthorized modifications to emergency circuits.