Sensible heat formula
Q_s = 1.08 × CFM × ΔT, where Q_s is sensible BTU/h, CFM is airflow, and ΔT is dry-bulb temperature difference. Used at sea level for air.
Latent heat formula
Q_l = 0.68 × CFM × ΔW, where ΔW is humidity ratio difference in grains per pound. Represents moisture removal or addition in BTU/h.
Total heat formula
Q_t = 4.5 × CFM × Δh, where Δh is enthalpy difference in BTU/lb. Combines sensible and latent loads for coil capacity.
Superheat definition
Suction line temperature minus evaporator saturation temperature at the bulb. Target 8–12°F for fixed orifice, 5–10°F for TXV systems.
Subcooling definition
Condenser saturation temperature minus liquid line temperature. Target 8–12°F for TXV, 5–10°F for fixed orifice; indicates charge and condenser performance.
Heat pump reversing valve
A four-way valve that swaps evaporator and condenser roles. In heating, outdoor coil becomes evaporator and indoor coil becomes condenser.
Defrost cycle initiation
Triggered when outdoor coil temperature falls below about 30°F or a pressure/temperature sensor detects frost. Terminates on time or temperature.
Manual J load calculation
ACCA method that calculates room-by-room heating and cooling loads using orientation, insulation, windows, infiltration, and internal gains.
Sensible heat ratio (SHR)
Sensible load divided by total load. Equipment SHR should closely match structure SHR to avoid humidity control problems.
Manual S equipment selection
ACCA procedure for selecting equipment using manufacturer expanded performance data at design conditions rather than nominal capacity ratings.
Manual D duct sizing
Sizes ductwork using friction rate = available static pressure ÷ total effective length. Typical supply friction is 0.08–0.10 in. w.c. per 100 ft.
Balance point
Outdoor temperature at which heat pump capacity equals building heat loss. Below this point, auxiliary heat supplements the heat pump.
ASHRAE 62.2 ventilation
Requires mechanical ventilation when natural infiltration is below 0.35 ACH. CFM = 0.03 × floor area + 7.5 × (bedrooms + 1).
Nitrogen purge brazing
Flow 1–2 psig nitrogen through tubing while brazing to prevent internal oxidation. Use silver-phos or 15% silver alloy depending on joint type.
Evacuation to 500 microns
Evacuate system to 500 microns or below and hold for 10 minutes with pump isolated. Rising microns indicate leak or moisture.
Weigh-in charging
Charge refrigerant by weight when line set length differs from factory charge. Adjust per manufacturer table, typically 0.6 oz per foot of 3/8-inch liquid line.
Temperature split check
Return air dry-bulb minus supply air dry-bulb. Normal cooling split is 18–22°F; low split suggests low airflow or charge issue.
Condensate trap requirement
Trap depth must be at least total static pressure; drain slope 1/8 inch per foot. Secondary pan with float switch is required.
External static pressure
Measured pressure resistance of duct system and components. Compare to fan performance table; target 350–450 CFM/ton cooling, 400–450 CFM/ton heating.
High superheat diagnosis
High superheat with low suction pressure indicates undercharge or restriction. Low superheat with high suction pressure indicates overcharge or overfeed.
High subcooling diagnosis
High subcooling with high head pressure indicates overcharge or condenser airflow restriction. Low subcooling with bubbles indicates undercharge.
Compressor amp draw check
Measure compressor amps and compare to nameplate RLA. Amps above RLA with high head pressure suggest mechanical or electrical fault.
Capacitor microfarad test
Use a multimeter with capacitance function to measure microfarads. Replace capacitor if reading is outside ±10% of rated value.
Leak detection methods
Electronic leak detector, UV dye, or nitrogen pressure test at 150–300 psig. Never use oxygen or acetylene for pressure testing.
Balometer airflow verification
Measure CFM at each register with a balometer. Total measured airflow should match design within ±10%.
Thermostat voltage check
Verify 24 VAC ±10% at R–Y, R–G, and R–W terminals during call. Check anticipator or cycle rate settings for proper operation.
Lockout/tagout procedure
Disconnect power at breaker, verify with meter, and apply lock before servicing. Never rely on thermostat off position.
R-410A pressure safety
R-410A operates at about 1.6 times R-22 pressure. Use gloves and eye protection; never heat a sealed system or mix refrigerants.
EPA Section 608 certification
Technicians must be certified to purchase or handle refrigerant. Recovery is required before opening system; venting is prohibited.
Electrical safety verification
Test 24 VAC control voltage and line voltage separately. Treat all conductors as live until tested with a meter.
Startup documentation
Record model/serial, refrigerant type and charge, filter sizes, startup readings, and deficiencies on invoice for warranty and reference.
Fall protection threshold
Use fall protection on roofs above 6 feet. Wear safety glasses, gloves, and steel-toe boots as personal protective equipment.