MTTC Electrical Trade Test · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Qualified Person
- A person who has demonstrated skills and knowledge related to electrical equipment construction and operation and has received safety training on the hazards involved, per NFPA 70E.
- Limited Approach Boundary
- A distance from an exposed energized conductor that unqualified persons may not cross unless escorted and protected; for 600 V class equipment it is typically 10 ft.
- Lockout/Tagout Verification
- The step after isolating and locking energy sources where a voltage tester, proved functional before and after, confirms the circuit is de-energized.
- Ohm's Law
- The relationship E = I x R, where voltage in volts equals current in amperes multiplied by resistance in ohms. Combined with power, P = E x I.
- Three-Phase Power Formula
- Real power equals the square root of three times line voltage times line current times power factor; apparent power omits the power factor term.
- Synchronous Speed
- The rotating speed of a motor's magnetic field, calculated as 120 times frequency divided by the number of poles; a 4-pole motor on 60 Hz runs at 1800 rpm.
- Impedance
- The total opposition to alternating current, combining resistance and net reactance as the square root of R squared plus the square of inductive minus capacitive reactance.
- RMS Value
- The effective value of a sine wave, equal to 0.707 times the peak value; it produces the same heating effect as an equal DC value.
- Box Fill Calculation
- A method summing conductor equivalents, clamps, devices, and grounding conductors, then multiplying by the volume allowance per conductor from Table 314.16(B).
- NM-B Cable Limits
- Nonmetallic sheathed cable is prohibited in wet locations, masonry cavities, and outdoors in raceways, and needs protection where within 1-1/4 in of framing surfaces.
- Ampacity Adjustment
- When more than three current-carrying conductors share a raceway, Table 310.15(C)(1) reduces ampacity: 4-6 conductors to 80%, 7-9 to 70%, 10-20 to 50%.
- EMT Support Rules
- Electrical metallic tubing must be supported within 3 ft of each box and at intervals not exceeding 10 ft along the run, using listed straps or clamps.
- Conduit Fill Percentages
- Chapter 9 permits one conductor at 53%, two at 31%, and more than two at 40% of the raceway internal cross-sectional area.
- Voltage Drop Formula
- Single-phase drop equals 2 times K times current times length divided by circular mils; three-phase uses the square root of three in place of the 2.
- Parallel Conductors
- Conductors run in parallel must share the same length, material, insulation, and termination, with a minimum size of 1/0 AWG in most installations.
- THHN Insulation Rating
- Thermoplastic high-heat nylon insulation rated 90 degrees C dry and 75 degrees C wet; ampacity is limited by the termination rating, commonly 75 degrees C.
- Continuous Load Rule
- A load operating at maximum current for three hours or more must be calculated at 125% of its rating when sizing branch circuits, feeders, and overcurrent devices.
- Small-Appliance Circuit
- A 20 A branch circuit serving dwelling kitchen receptacle outlets; at least two are required, and they may not serve lighting outlets.
- Feeder Tap Rule
- A tap up to 10 ft long may use conductors at least one-tenth the overcurrent device rating if protected from damage and terminated in a single device.
- Dwelling Lighting Load
- General lighting in a dwelling is calculated at 3 volt-amperes per square foot, then demand factors from Table 220.42 are applied to the total.
- Motor Conductor Sizing
- Branch-circuit conductors supplying a single motor must have ampacity at least 125% of the motor full-load current from the applicable Article 430 table.
- Motor Overload Protection
- Running overload protection is sized from the motor nameplate service factor and temperature rise, protecting the winding from sustained excess current, not short circuits.
- Motor Disconnect Rating
- The disconnecting means must be rated at least 115% of the motor full-load current and located within sight of the motor or lockable open.
- Reduced-Voltage Starting
- A starting method that lowers voltage during acceleration, reducing inrush current but also reducing starting torque in proportion to the square of the voltage reduction.
- Grounding Electrode Conductor
- The conductor connecting the grounded service conductor to the grounding electrode; sized from Table 250.66 based on the largest ungrounded service conductor.
- Equipment Grounding Conductor
- The conductive path connecting equipment enclosures to the system grounding point; sized from Table 250.122 based on the overcurrent device rating.
- Series Rating
- An arrangement where a downstream breaker with lower interrupting rating is protected by an upstream current-limiting device, only when listed and marked as a combination.
- GFPE Requirement
- Ground-fault protection of equipment is required for solidly grounded wye services over 150 V to ground and 1000 A or more, with settings not exceeding 1200 A.
- Insulation Resistance Test
- A DC overvoltage test measuring leakage in megohms; readings below 1 megohm, or below 1 megohm per 1000 test volts, indicate degraded insulation.
- Clamp Meter Residual Reading
- Placing the clamp around all circuit conductors together should read zero; any residual current indicates leakage or a ground fault on the circuit.
- Motor Winding Resistance Test
- Measuring phase-to-phase and phase-to-ground resistance detects opens (infinite), shorted turns (near zero), and grounds (low resistance to the frame).
- Performance Assessment
- An evaluation in which learners demonstrate a trade task such as conduit bending or motor wiring against a rubric covering safety, code compliance, and workmanship.
- Formative Assessment
- A low-stakes check during instruction, such as an exit ticket or code-lookup drill, used to adjust teaching before the summative evaluation.