C-NNIC study materials
C-NNIC study resources

C-NNIC cheat sheet

C-NNIC · Keep the key ideas within reach.

Quick reference

Network Cabling Systems and Structured Wiring

  • Six structured cabling subsystems: entrance facility, equipment room, backbone cabling, horizontal cabling, telecommunications room, and work area.

  • Horizontal cabling maximum length is 90 m (295 ft) of permanent link plus 10 m of patch cords for a 100 m channel.

  • ANSI/TIA-568 recognizes balanced twisted-pair categories 3, 5e, 6, 6A, 8, and multimode/singlemode fiber as horizontal media.

  • Solid conductor cable is used for permanent horizontal runs; stranded conductor is used for patch cords because of flex life.

  • T568A and T568B differ only in the pin positions of pairs 2 and 3; both are valid if used consistently at both ends.

  • A cross-connect in the telecommunications room terminates horizontal cable on a patch panel to allow flexible administration.

  • Backbone cabling connects entrance facilities, equipment rooms, and telecommunications rooms; recognized media include fiber and multipair copper.

  • Consolidation point is an interconnection point within horizontal cabling, allowed only in open ceilings or zone boxes, not as a cross-connect.

Quick reference

Network Infrastructure Design and Topologies

  • Star topology dominates structured cabling: every horizontal link home-runs to a telecommunications room, giving single-point fault isolation.

  • Hierarchical design layers: access (workgroup), distribution (building/floor), and core (campus backbone).

  • The 100 m channel rule and 90 m permanent link rule set the practical 90 m service radius of a telecommunications room.

  • Each floor should have at least one telecommunications room; additional rooms are added when the 90 m horizontal distance cannot be met.

  • Backbone distance limits depend on media: multimode fiber is typically limited by application reach, singlemode by transceiver budget.

  • Redundant topology (dual core, dual homing) removes single points of failure at the cost of extra cable, pathways, and switch ports.

  • Point-to-point links are used for backbone and inter-building runs; shared-media bus topologies are legacy and not recommended for new designs.

  • Separation of voice, data, and building-automation cabling by pathway or by jacket rating reduces EMI and simplifies administration.

Quick reference

Physical Layer Standards and Media Types

  • Category 6 supports 250 MHz, Category 6A supports 500 MHz, and Category 8 supports 2000 MHz over limited 30 m channels.

  • Category 6A is specified for 10GBASE-T up to 100 m; Category 6 supports 10GBASE-T only to about 55 m in favorable alien-crosstalk conditions.

  • Balanced twisted-pair nominal impedance is 100 ohms; coaxial cable used for broadband is typically 75 ohms.

  • Multimode fiber core sizes are 50/125 and 62.5/125 micrometres; singlemode is 8-10 micrometre core with much lower attenuation.

  • OM3/OM4 laser-optimized multimode supports 10GBASE-SR to 300 m/400 m and 40/100GBASE-SR to shorter reaches.

  • Singlemode attenuation is roughly 0.3-0.5 dB/km at 1310/1550 nm; multimode is roughly 3.0-3.5 dB/km at 850 nm.

  • Shielded twisted pair (F/UTP, S/FTP) provides a foil or braid shield that improves alien crosstalk and EMI immunity versus U/UTP.

  • Plenum-rated cable (CMP) uses low-smoke, low-flame-spread materials and is required in air-handling spaces; riser (CMR) is used in vertical shafts.

Quick reference

Installation Practices, Pathways, and Cable Management

  • Minimum bend radius: four times the cable outside diameter for UTP during installation, ten times for fiber (varies by count and jacket).

  • Maximum pulling tension for 4-pair copper is typically 25 lbf (110 N); exceeding it stretches conductors and degrades return loss.

  • Cable ties should be hook-and-loop or loose; over-cinched ties deform the pair geometry and raise insertion loss and crosstalk.

  • Fill ratio for conduit is commonly 40 percent of cross-sectional area for new pulls to allow future capacity and reduce friction.

  • Support horizontal cable at intervals not exceeding 1.5 m (5 ft) and no more than 300 mm from a box or termination.

  • Separate communications cable from power raceways; maintain at least 300 mm separation from unshielded power lines where practical.

  • Pathways include conduit, cable tray, J-hooks, raceway, and under-floor ducts; each must be bonded to the telecommunications bonding backbone.

  • Leave a service loop of about 3 m at the telecommunications room end and 300 mm at the work area for retermination.

Quick reference

Testing, Certification, and Troubleshooting of Cabling

  • Field certification of copper measures insertion loss, return loss, NEXT, PS-NEXT, ACR-F, PS-ACR-F, propagation delay, delay skew, and wire map.

  • Permanent link test excludes patch cords and uses reference test plugs; channel test includes the user patch cords and is the end-to-end result.

  • Alien crosstalk (ANEXT/PSANEXT) is measured between adjacent cables and is critical for 10GBASE-T over Category 6/6A.

  • Wire map faults: open, short, crossed pair, split pair, and reversed pair; a split pair passes continuity but fails NEXT badly.

  • Fiber tier 1 testing uses an optical loss test set (OLTS) for attenuation and length; tier 2 adds an OTDR trace for event location.

  • Optical loss budget equals source power minus receiver sensitivity; total link loss is the sum of connector, splice, and fiber attenuation.

  • Common causes of failing NEXT are untwisted conductors at the termination, excessive jacket removal, and tight cable ties.

  • Troubleshooting sequence: verify link status, test the patch cord, run the permanent link test, inspect terminations, then replace the run.

Quick reference

Codes, Standards, and Safety Compliance

  • ANSI/TIA-568 defines cabling performance and pin assignments; ANSI/TIA-569 covers pathways and spaces; ANSI/TIA-606 covers administration labeling.

  • ANSI/TIA-607 covers telecommunications bonding and grounding; ANSI/TIA-942 covers data center infrastructure.

  • NFPA 70 (NEC) Article 800 governs communications circuits; Article 770 covers optical fiber; Article 300 covers wiring methods.

  • NEC 300.22 restricts cable in air-handling spaces: plenum-rated cable is required in ducts and plenums used for environmental air.

  • CMP cable is tested for low smoke and flame spread; CMR is for risers; CM/CMG are general-purpose and not for plenum spaces.

  • Bonding conductor sizing follows TIA-607 and NEC; the telecommunications bonding backbone ties the TMGB to each TGB and to building steel.

  • OSHA and NFPA 70E require lockout/tagout and PPE when working near energized circuits; laser sources require eye protection and fiber caps.

  • Labeling per TIA-606 uses a unique identifier for each cable, termination, and pathway, applied at both ends and at cross-connects.

Quick reference

Network Hardware, Racks, and Power/Cooling

  • Standard 19-inch equipment rack uses EIA-310 hole spacing; one rack unit (1U) equals 44.45 mm (1.75 in).

  • Rack-mounted equipment should be supported at both front and rear rails when depth permits; heavy gear goes at the bottom.

  • Vertical cable managers and horizontal managers preserve bend radius and separate patch cords from power cords.

  • Power: a rack PDU distributes branch circuits; UPS sizing must cover load in watts, runtime, and power factor.

  • Cooling: equipment intake air is front-to-back in most racks; arrange racks in hot-aisle/cold-aisle rows to prevent recirculation.

  • Heat load in watts approximates to BTU/h by multiplying by 3.412; this sizes CRAC/CRAH capacity.

  • Redundant power uses dual-corded devices on separate A/B feeds from independent PDUs or UPS systems.

  • Grounding: racks and cable trays bond to the telecommunications bonding backbone; do not use the rack as the only grounding path.