Boiler horsepower
A measure of boiler capacity equal to 33,475 Btu per hour, defined as evaporating 34.5 pounds of water per hour from and at 212 degrees Fahrenheit.
Fire-tube boiler
A boiler in which hot combustion gases flow through tubes surrounded by water, limiting pressure and capacity but offering large steam storage and simple construction.
Water-tube boiler
A boiler in which water circulates through tubes heated externally by combustion gases, permitting higher pressures, larger capacities, and faster response to load changes.
Equivalent evaporation
The evaporation rate corrected to a standard of feedwater at 212 degrees Fahrenheit producing dry saturated steam, allowing boilers of different conditions to be compared.
Safety valve requirement
Each boiler must have at least one safety valve whose capacity equals or exceeds maximum steam output, with set pressure not above the maximum allowable working pressure.
Steam drum function
The upper drum separates steam from water, houses separators and baffles, and provides a point for chemical feed and water level indication.
Mud drum function
The lower drum collects sludge and sediment and provides a low point for bottom blowdown, helping keep heating surfaces free of deposits.
Gauge glass test
Opening the gauge glass drain and observing water return verifies that the water column connections are clear and the indicated level is reliable.
Economizer
A heat recovery device that uses flue gas to preheat feedwater before it enters the boiler, improving efficiency and reducing stack temperature.
Three T's of combustion
Temperature, turbulence, and time must all be sufficient for complete combustion; a deficiency in any one produces smoke, carbon monoxide, or unburned fuel.
Excess air
The amount of combustion air supplied above theoretical air, expressed as a percentage and adjusted by flue gas oxygen and carbon monoxide readings.
Flame scanner
A detector that senses ultraviolet or infrared radiation from the burner flame and signals the flame safeguard to close the fuel valve on flame loss.
Burner turndown
The ratio of maximum firing rate to minimum stable firing rate; operating below the turndown limit risks flame instability and unburned fuel.
Atomization
Breaking liquid fuel into fine droplets so it vaporizes and mixes with air, improving combustion efficiency and reducing smoke and unburned fuel.
Scale formation
Deposits of precipitated calcium and magnesium salts on heating surfaces that reduce heat transfer, raise metal temperatures, and can cause tube failure.
Deaerator
Equipment that heats feedwater to near saturation and vents released gases, removing dissolved oxygen and carbon dioxide that cause corrosion.
Continuous blowdown
A controlled, continuous removal of boiler water from near the water surface to limit dissolved solids concentration and prevent foaming and carryover.
Carryover
Boiler water droplets entrained in steam, caused by high dissolved solids, foaming, or high water level, which can deposit solids on superheaters and turbines.
Furnace purge
A required flow of air through the furnace before ignition to remove combustible gases, typically four to five furnace volumes.
Cold startup sequence
Verify water level, purge the furnace, establish pilot flame, prove main flame, then raise load gradually while monitoring pressure and level.
Bottom blowdown
Short, repeated opening of the bottom blowdown valves with the boiler under load to remove sludge and sediment from the mud drum.
Normal shutdown
Reduce load gradually, cut fuel, purge the furnace, close the main steam stop, and maintain water level while the boiler cools.
Low-water fuel cutoff
A safety device that stops fuel and air supply when the water level falls below a safe point, preventing overheating and tube failure.
High-pressure limit switch
A control that stops the burner at a set pressure above normal operating pressure but below the safety valve setpoint, providing overpressure protection.
Flame safeguard programmer
A control that supervises purge, pilot, main flame, and flame failure timing, closing the main fuel valve when the flame signal is lost.
Manual reset requirement
A low-water trip must remain latched after a low-water condition so the boiler cannot restart automatically until an operator resets it.
Hydrostatic test
A pressure test at 1.5 times maximum allowable working pressure for new boilers, with safety valves removed or gagged and the boiler vented.
Safety valve pop test
A test performed with steam pressure to verify that the safety valve opens at its set pressure and reseats properly, never by hand lifting alone.
Low-water cutoff test
Lowering the water level or opening the test connection to confirm the burner trips and the alarm sounds, verifying the safety device functions.
Low-water emergency
Shut off fuel, do not add water to a hot boiler until the cause is found and the boiler cools, and inspect for overheating damage.
Dry-fired boiler
An overheated boiler without water must be cooled slowly; adding cold water to hot dry metal can cause violent steam expansion and a pressure surge.
ASME Code sections
ASME Section I covers power boilers, Section IV covers heating boilers, and Section VIII covers pressure vessels, establishing design and construction rules.
Maximum allowable working pressure
The highest pressure at which a boiler may be operated, established by code design and protected by the safety valve as the final overpressure device.