Troubleshooting a Pressure Drop and Worksite Safety

BC Class C-R Low Energy FSR · Put your knowledge to work in context.

All case studies

Troubleshooting a Pressure Drop and Worksite Safety

A low-energy FSR system that passed commissioning now shows a slow pressure drop at the source gauge, from 12 bar to about 10.5 bar over several days, with no visible discharge. A technician is sent to investigate. The room is a small, poorly ventilated storage area, and the technician plans to work alone, use a ladder to reach ceiling nozzles, and isolate the system by closing a valve without locking it out. The gauge at the source is the only monitoring point, and the owner reports no alarms.

1. How should the technician approach the pressure-drop diagnosis, and what are the likely causes?

Read the worked answer

The technician should first establish whether the loss is real and where it occurs: check the source gauge against a second gauge, inspect for slow leaks at joints, fittings, and nozzles, and check for trapped air or a partially closed valve. A drop from 12 bar to 10.5 bar over days with no visible discharge suggests a small leak, a weeping joint, or a valve not fully seated, rather than a major breach.

Diagnosis should proceed systematically: isolate sections to localize the loss, inspect concealed and exposed runs, and verify the source supply itself is stable. The single gauge is a limitation; the technician should confirm with an independent reading. Once localized, the repair is documented and the system retested to the commissioning standard, because a system that drifted below design margin may not deliver 10 bar at the most remote nozzle.

2. What safety and worksite practice failures are present in the technician's plan, and how should they be corrected?

Read the worked answer

Several failures are present. Working alone in a poorly ventilated storage area is a hazard, especially if any agent or contaminant could be present; the technician should have a second person or follow the site's lone-worker procedure. The ladder work at the ceiling requires a safe platform and fall protection as applicable, not an improvised reach. Closing a valve without lockout/tagout risks unexpected re-pressurization while the technician is working on the system.

The correction is to isolate and lock out the source, verify zero energy before opening anything, ventilate the space, use proper access equipment, and work with a second person or under the site's lone-worker rule. These are not paperwork items: a system that re-pressurizes while a technician is at a fitting can cause serious injury. The technician should also record the isolation and the repair, and retest before returning the system to service.