BC Class C-R Low Energy FSR study materials
BC Class C-R Low Energy FSR study resources

BC Class C-R Low Energy FSR flashcards

BC Class C-R Low Energy FSR · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Authority having jurisdiction
The organization or official responsible for enforcing the adopted code and approving installations, permits, and inspections for the FSR system.
Listed and labeled
Equipment tested by an approved agency and marked to show it meets a recognized standard; listing conditions must be followed for acceptance.
Maximum allowable working pressure
The highest pressure a component or system is designed to withstand in normal service; exceeding it requires a higher-hazard design category.
Fuel-gas code scope
The adopted gas code governs piping, materials, and testing for fuel gas, while separate oil-burner codes govern fuel-oil piping installations.
Sediment trap purpose
A drip leg installed downstream of the regulator and shutoff that captures debris and condensate before they reach appliance controls.
Pressure regulator function
A device that reduces supply pressure to the appliance's rated inlet pressure and maintains it within the regulator's rated flow capacity.
Manual shutoff valve
A listed valve at the appliance connection and supply point that allows the fuel to be isolated for service without cutting pipe.
Listed flexible connector
A fuel-rated flexible hose sized to the appliance input, used to connect the appliance while protecting against vibration and misalignment.
Equivalent length method
A sizing method adding fitting and valve equivalent lengths to measured pipe length to select a size that meets allowable pressure drop.
Longest run governs
In branch piping, the most remote appliance's equivalent length typically controls pipe sizing because it has the greatest pressure loss.
Connected load total
The sum of appliance input ratings served by a common header, used to size the meter, regulator, and main piping.
Accessible valve location
Regulators, shutoffs, and traps must remain reachable for service; they cannot be concealed in inaccessible spaces or buried.
Pipe support spacing
Code-required intervals and points of support that carry pipe weight so fittings and appliance connections are not loaded.
Thread compound application
Approved compound or tape applied to male threads only, leaving the first two threads bare to prevent compound entering the fuel line.
Two-wrench rule
Using one wrench to hold the fitting and one to turn the pipe prevents torque from damaging valves, regulators, and controls.
Regulator orientation
Regulators must be installed per the flow arrow and vent position, with a vent line to a safe location when venting indoors.
Capped open ends
Plugging or capping open pipe ends during construction keeps debris and moisture out of the line until final connection.
Pneumatic pressure test
Testing new piping with air or inert gas at code-required pressure and duration, with appliances and regulators isolated or removed.
Gauge selection for test
A calibrated gauge whose range places the test pressure near mid-scale gives the most accurate reading during the pressure test.
Leak detection method
Approved soap solution or an electronic detector applied to joints; an open flame must never be used to locate a leak.
Purging before fuel
Removing air and debris from the line with the proper medium, purged to a safe location, before introducing fuel to the appliance.
Regulator lockup check
Verifying that the regulator closes tightly and holds outlet pressure when flow stops, confirming proper seat and vent operation.
Low inlet pressure cause
Appliance inlet pressure below rating under load can indicate an undersized regulator, a partly closed valve, or a line restriction.
Regulator vent blockage
A blocked or missing regulator vent can cause high or fluctuating outlet pressure and must be cleared or repaired promptly.
Sediment trap servicing
Cleaning a filled trap restores flow and prevents intermittent appliance lockout; the debris source should also be investigated.
Service log record
A dated record of inspections, repairs, and replacements that documents system condition and supports troubleshooting and compliance.
Hot-work permit
Required before brazing or welding; it establishes combustible removal, fire watch, and extinguisher provisions at the worksite.
Lockout tagout
Isolating fuel and energy sources, applying locks and tags, and verifying zero energy before opening or servicing lines.
Confined space entry
Entry into a space with limited access requires atmosphere testing, ventilation, and a standby attendant before and during work.
Personal protective equipment
Safety glasses, gloves, and hearing protection for cutting and threading; respiratory protection where dust or fumes are present.
Cylinder storage rules
Fuel cylinders are stored upright, secured, away from heat, and separated per code to prevent tipping, leakage, and fire exposure.
Emergency shutdown location
Knowing where the fuel supply can be quickly isolated and posting emergency contacts prepares the crew to respond to a release.