BOABC Building Official Level I · Keep the key ideas within reach.

Quick reference

Building Code Knowledge

  • Occupant load is the floor area divided by the occupant load factor; the resulting number is the minimum design population for exits, egress width, and plumbing fixture counts.

  • Means of egress has three continuous parts: exit access, the exit itself, and exit discharge; each must be continuous and unobstructed from any point in the building to the public way.

  • Required egress capacity equals occupant load multiplied by the code capacity factor (commonly 0.2 in per person for level components and 0.15 in per person for stairs and ramps); the width provided must equal or exceed this value.

  • Two remote exits are required when the occupant load exceeds the threshold for the occupancy group; the separation distance is generally not less than one-half the diagonal of the area served, measured along the path of travel.

  • Dead-end corridors are limited to 20 ft in most occupancies and 50 ft where the code permits an increase for sprinklered buildings with approved travel distances.

  • Fire-resistance-rated construction is expressed in hours; the required rating depends on construction type, occupancy group, and whether automatic sprinklers are installed.

  • A fire area is the aggregate floor area enclosed and bounded by fire walls, fire barriers, exterior walls, or horizontal assemblies; it drives sprinkler thresholds and allowable area.

  • Travel distance is measured along the natural path of travel from the most remote point to the nearest exit, including turns, but not including the path within the exit itself.

  • Accessibility provisions require an accessible route connecting accessible entrances, parking, and all accessible spaces, with running slope not steeper than 1:20 and cross slope not steeper than 1:48.

Quick reference

Plan Review and Inspection Practice

  • Plan review order: verify occupancy classification and construction type first, then allowable area and height, then egress, then fire protection systems, then accessibility and structural items.

  • Allowable building area = tabular allowable area x frontage increase factor x sprinkler increase factor; confirm each factor against the code tables and the site plan frontage data.

  • Check that the submitted drawings are sealed by the responsible design professional and that the scope of the seal covers the work shown before beginning technical review.

  • Inspection sequence: footing and foundation, then framing and rough-in, then insulation and firestopping, then final; each must pass before the next phase is concealed.

  • A correction notice must cite the specific code section, the location on the drawings, and the required corrective action so the applicant can respond without ambiguity.

  • Field inspection verifies installed conditions against approved plans; any deviation requires a revised plan or a documented field change approved by the building official.

  • Record retention: inspection records, approved plans, and certificates of occupancy are retained for the period required by the jurisdiction; the certificate of occupancy is issued only after final inspection passes.