CFAA Fire Alarm Tech flashcards
CFAA Fire Alarm Tech · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Listed spacing (S)
- The maximum distance between detectors under a given ceiling height and type, published by the listing agency; spacing is reduced to 0.7S for smooth ceilings in NFPA 72 detector layout.
- Addressable system
- A system in which each initiating or notification device has a unique address reported individually to the control unit, allowing precise annunciation and faster troubleshooting than zone-based conventional systems.
- Class A circuit
- A signaling circuit that continues to operate during a single open or ground fault condition because it is wired out and back to the control unit; it provides greater survivability than Class B.
- Class B circuit
- A signaling circuit that does not continue to operate beyond a single open fault; the fault is annunciated as a trouble but devices beyond the break stop functioning.
- Ionization detector
- A smoke detector using a small radioactive source to ionize air in a chamber; it responds best to small particles from fast-flaming fires and is less responsive to smoldering smoke.
- Photoelectric detector
- A smoke detector using light scattering or beam obscuration; it responds best to larger particles from smoldering fires and is commonly used near sleeping areas and in duct applications.
- Rate-of-rise detector
- A heat detector that responds when temperature increases faster than a set rate, typically around 15 degrees Fahrenheit per minute; it does not respond to slow temperature rise.
- Supervisory signal
- A signal indicating an off-normal condition of a system component, such as a closed valve or low air pressure, that could impair performance but is not itself an alarm.
- Trouble signal annunciation
- An audible and visual indication at the control unit that a circuit or component is abnormal; NFPA 72 requires annunciation within 200 seconds of the condition.
- Record of Completion
- The NFPA 72 document signed at acceptance testing that certifies the system was installed per the approved plans and tested, and records the responsible parties and test results.
- Contemporaneous log entry
- A record written at the time the task is performed, capturing date, time, location, device, task, instrument, and signatures; later reconstruction weakens its evidentiary value.
- Instrument calibration record
- Documentation of a test instrument's calibration date and status, recorded with each use; an out-of-calibration instrument invalidates the test results it produced.
- Finding versus corrective action
- A finding records what failed and where; a corrective action records the cause, the repair performed, the retest result, and the date closed. They are logged as separate fields.
- As-built reconciliation
- Comparing the device list and address list in the logbook against the as-built drawings; discrepancies are documented as findings rather than silently corrected.
- Panel event log export
- A printed or electronic export of the control unit's event history used as documentary evidence of alarms, troubles, and tests performed during a logbook entry.
- Retention period for ITM records
- NFPA 72 requires inspection, testing, and maintenance records be retained for one inspection/test/maintenance cycle plus one year and made available to the authority having jurisdiction.
- Supervisor sign-off
- A supervisor's signature confirming the trainee performed the logged task under the level of supervision the jurisdiction requires, validating the entry for credit.
- Acceptance test documentation
- A record of each device test showing the test method, pass or fail result, and the standard or manufacturer instruction that defines the pass criterion.
- Contact hour
- One 60-minute unit of instruction used to measure continuing education credit; breaks and non-instructional time are excluded from the count.
- CE category cap
- A jurisdictional limit on how many continuing education credits may come from one category, such as code update, technical, or ethics, within a renewal cycle.
- Renewal cycle window
- The defined period, usually annual or biennial, within which continuing education must be completed; credits earned outside the window generally do not count.
- Approved provider
- An organization authorized by the jurisdiction or a recognized body to deliver continuing education; courses from unapproved providers may be rejected at audit.
- CE certificate of completion
- The record showing provider name, course title, course number, date, and contact hours, retained for the audit period to substantiate claimed continuing education credit.
- Carryover of excess credits
- The transfer of credits earned beyond the current cycle requirement into the next cycle; permitted only where the jurisdiction's rule allows, often with a cap.
- Proctored CE assessment
- A supervised or scored examination required for some self-study or online continuing education courses; attendance alone without a passing score may earn no credit.
- Deficiency notice
- A jurisdiction's written notice that continuing education requirements were not met, usually specifying a deadline to cure the deficiency before license action.
- Authority Having Jurisdiction
- The organization or individual legally empowered to enforce code requirements, approve plans, witness acceptance tests, and grant final approval for a fire alarm installation.
- Local amendment
- A jurisdiction's modification to an adopted model code, such as NFPA 72, that supersedes the model text within that jurisdiction and must be checked before design.
- Permit submittal package
- The documents required before installation, typically shop drawings, device layout, riser diagram, and battery and voltage-drop calculations, submitted for jurisdictional review.
- Trainee registration
- A jurisdictional credential separate from contractor licensing and technician certification that defines the scope of work a trainee may perform and under what supervision.
- Adopted code edition
- The specific edition of the model code in force at the time a permit is issued; new work follows that edition, and older permitted work may be grandfathered.
- Fire watch requirement
- A jurisdictional condition requiring personnel to patrol for fire while a detection or suppression system is out of service, often triggered when notification to the fire department is made.