CA Elevator Mechanic flashcards
CA Elevator Mechanic · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Rated load plate
- A plate in the car listing the rated load in pounds, the number of persons allowed, and the manufacturer; inspectors verify it matches the machine and rope data.
- A17.3 scope
- The safety code for existing elevators and escalators; it sets retrofit requirements for car lighting, firefighter service, door restrictors, and pit access on units installed before current code.
- Door open time
- Under A17.1, power-operated car doors must remain fully open at least 20 seconds at a landing to allow passenger transfer, unless a shorter time is set by a special operating mode.
- Leveling tolerance
- The car sill must stop within plus or minus 0.5 inch of the landing sill; if the car drifts outside that band, automatic operation must stop and hold the car.
- Two-way communication
- A17.1 requires a means in the car to call a continuously staffed location, with battery backup and a way to summon help if the primary line fails.
- Machine room clearance
- At least 18 inches clear in front of controllers and 30 inches clear working space in front of electrical panels; the room may not be used for storage.
- Car lighting minimum
- A17.3 requires at least 5 foot-candles of light at the car floor with the doors closed, measured at the sill and at the center of the car.
- Permit to operate
- The current operating permit must be posted in the car; it is issued after a passing periodic inspection and must be renewed before its expiration date.
- Rope safety factor
- Under A17.1, suspension rope safety factor is at least 12 for traction elevators rated 500 fpm or less, increasing for higher speeds per the code table.
- Rope tension equalization
- Adjust each rope until it carries within 10 percent of the average tension; unequal tension causes uneven wear on sheave grooves and shortens rope life.
- Counterweight runby
- At least 2 inches of clearance between the car buffer contact and counterweight buffer contact, ensuring the counterweight does not strike its buffer before the car does.
- Motor branch sizing
- Branch circuit conductors must be at least 125 percent of motor full-load current, with overload protection in each conductor and short-circuit protection sized per code.
- Hydraulic relief valve
- The relief valve must open at not more than 150 percent of working pressure; the tank also needs a low-oil or oil-temperature safeguard where the code requires it.
- Sheave groove wear
- Worn or undercut grooves reduce traction and let the rope sit too deep; measure groove depth and compare to rope diameter to decide on resurfacing or replacement.
- Governor trip speed
- The governor must trip the car safety at a speed set by the code table, typically 115 to 140 percent of rated speed depending on the speed range.
- Equipotential bonding
- Rails, machine, controller, and pit equipment are bonded to the building grounding electrode system; verify continuity with a meter before energizing the unit.
- Category 1 test
- An annual no-load safety test at rated speed with the car empty; the governor trips the safety and the car is verified to stop and hold.
- Category 5 test
- A full-load safety test at rated speed with rated load, performed every 5 years; it verifies the safety and governor work under maximum load conditions.
- Buffer return time
- Oil buffers must return to full extension within 90 seconds after compression, and the oil level must be within the marked range on the sight glass.
- Door closing force
- Power-operated doors must not exceed 30 lbf kinetic energy, and the reopening device must reverse the door on contact with an object in its path.
- Troubleshooting sequence
- Verify power at the disconnect, then control voltage, then safety circuit continuity, then door lock circuit, then motor and brake circuits, before replacing parts.
- Brake holding test
- The brake must hold rated load plus 25 percent; check for even shoe contact and air gap within the manufacturer specification during the test.
- Rated speed verification
- Measure car speed with a recording tachometer; a result outside plus or minus 5 percent of rated speed indicates a drive, sheave, or adjustment problem.
- Serious hazard handling
- A condition that endangers life or limb requires the unit be taken out of service until corrected, and the finding is recorded with the code section cited.
- Lockout/tagout
- Isolate the main disconnect, verify zero energy with a meter, apply a personal lock and tag; only the person who applied the lock may remove it.
- Pit entry procedure
- Stop the car at the landing above, open the pit switch to remove power, and verify the pit stop switch works before entering the pit.
- Fall protection threshold
- California general industry requires 100 percent tie-off above 6 feet, and guardrails or covers over all floor and shaft openings.
- Hoistway opening protection
- Barricade the landing opening before work, and use the top-of-car operating station with the car top rail in place when working on the car top.
- Confined space testing
- Test the pit atmosphere for oxygen and combustibles before entry when there is no permanent ventilation, and wear a retrieval harness.
- Electrical PPE
- Use voltage-rated gloves and insulated tools on energized circuits; de-energize whenever feasible and treat every circuit as live until verified.
- Rigging inspection
- Know the working load limit of slings and shackles, never exceed it, use tag lines to control the load, and inspect rigging before each lift.
- Emergency response prep
- Before starting work, know the manual lowering procedure, the disconnect location, and the entrapment release procedure for the unit.