HRAI ODP Refrigerant Handling flashcards
HRAI ODP Refrigerant Handling · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- ODP definition
- Ozone Depletion Potential is a relative index, scaled so CFC-11 equals 1.0, expressing the relative amount of stratospheric ozone destruction per unit mass of a substance.
- CFC-11 ODP value
- CFC-11 (trichlorofluoromethane) is the reference compound with an ODP defined as exactly 1.0 against which all other substances are compared.
- HCFC-22 ODP value
- HCFC-22 has an ODP of about 0.055, roughly one-twentieth that of CFC-11, because its hydrogen atom makes it break down in the lower atmosphere.
- HFC ODP value
- HFC refrigerants such as R-134a and R-410A contain no chlorine or bromine, so their ODP is zero and they are not classified as ozone-depleting substances.
- Bromine versus chlorine potency
- Bromine atoms destroy ozone far more efficiently than chlorine atoms, roughly 45 to 60 times more per atom, so halons have high ODP despite small atmospheric concentrations.
- What makes a substance ODS
- A substance is an ozone-depleting substance if it carries chlorine or bromine and survives long enough in the atmosphere to reach the stratosphere and release those halogens.
- Montreal Protocol Annex A
- Annex A lists the original controlled substances: CFC-11, CFC-12, CFC-113, CFC-114, CFC-115 and the halons 1211, 1301 and 2402.
- Kigali Amendment scope
- The Kigali Amendment controls hydrofluorocarbons by phasedown of production and consumption based on GWP, but HFCs are not ozone-depleting substances under the Protocol.
- ODP versus GWP
- ODP measures ozone destruction relative to CFC-11 while GWP measures infrared radiative forcing relative to CO2 over 100 years; the two metrics are independent.
- Recovery definition
- Recovery is the removal of refrigerant from a system into an external container for storage, reuse, recycling, reclamation or destruction, without processing it.
- Recycling definition
- Recycling is the field reduction of contaminants such as oil, moisture and acids in recovered refrigerant, typically by filtering and separation, without full chemical analysis.
- Reclamation definition
- Reclamation is the reprocessing of recovered refrigerant to new-product specification, usually AHRI 700, verified by chemical analysis, and is required before resale or use in another owner's equipment.
- AHRI 700 standard
- AHRI Standard 700 specifies acceptable purity levels and test methods for new and reclaimed refrigerants, including composition, moisture, acidity and non-condensable gas limits.
- Venting prohibition
- Intentional discharge of ozone-depleting refrigerant to the atmosphere is prohibited; recovery equipment must evacuate the circuit to the required vacuum before opening or disposal.
- De minimis charge exemption
- Some regulations exempt very small ODS charges, commonly 5 pounds or less, from certain recovery and leak-repair requirements, but never permit deliberate venting.
- Recovery cylinder fill limit
- Recovery cylinders must not be filled above about 80 percent of water capacity by liquid, leaving vapor space for thermal expansion and preventing hydrostatic rupture.
- Cylinder rating requirement
- A recovery cylinder must be rated and stamped for the pressure of the refrigerant it holds, and must be labeled with the refrigerant identity and the applicable hazard class.
- Zeotropic blend charging
- Zeotropic blends such as R-407C change composition as they evaporate, so they must be charged as a liquid and cannot be fractionally topped off without composition drift.
- Retrofit label update
- When an ODS refrigerant is replaced with a non-ODS substitute, the equipment label must be updated to record the new refrigerant type and the full charge amount.
- Asphyxiation hazard
- Most ODS refrigerants are nonflammable but denser than air; they displace oxygen in low areas, so confined spaces require ventilation and atmospheric oxygen monitoring before entry.
- Appliance disposal rule
- Before an appliance is shredded or landfilled, its refrigerant must be recovered; ODS that cannot be reclaimed must be destroyed by an approved process rather than vented.
- Leak repair requirement
- When a leak is detected in equipment above the regulated charge threshold, the leak must be repaired within the specified period and the repair documented in service records.
- HCFC phase-out status
- HCFCs such as R-22 are scheduled for complete phase-out of production and consumption under the Montreal Protocol, with allowances for servicing existing equipment in some regions.
- Carbon tetrachloride ODP
- Carbon tetrachloride has an ODP of about 1.1, slightly above CFC-11, and is controlled under Annex B of the Montreal Protocol as an ozone-depleting substance.
- Methyl bromide ODP
- Methyl bromide has an ODP of about 0.6 and is listed in Annex E of the Montreal Protocol, with quarantine and pre-shipment uses treated separately from general controls.
- Recovered refrigerant reuse
- Recovered ODS refrigerant may be reused only in equipment owned by the same owner or if it has been reclaimed and certified to AHRI 700 purity for resale.
- Non-condensable gas effect
- Air or nitrogen trapped in a circuit raises discharge pressure and temperature, reduces capacity and efficiency, and must be purged or avoided during recovery and charging.
- Moisture in ODS systems
- Moisture in a CFC or HCFC circuit forms acids and sludge, degrades lubricant and can freeze at the metering device, so filter-driers and evacuation are required.
- Evacuation before charging
- A system must be evacuated to the specified micron level and hold that vacuum before charging, removing moisture and non-condensables that would otherwise damage the system.
- Recovery equipment certification
- Recovery machines must be certified to the applicable standard for the refrigerant type, and separate machines or verified changeover are needed for different refrigerant families.
- Refrigerant mixing prohibition
- Different refrigerants must never be mixed in one cylinder, because the resulting mixture has unknown properties, cannot be reclaimed and becomes a costly hazardous waste stream.
- ODS recordkeeping
- Regulations require records of refrigerant purchases, charges, recoveries, leak repairs and disposal, retained for the specified period and available for inspection.