California Low Voltage Practice flashcards
California Low Voltage Practice · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 70E
- Standard for Electrical Safety in the Workplace, covering arc flash risk assessment, PPE selection, and safe work practices for electrical workers.
- Class 2 circuit
- A circuit limited to 100 VA and 30 V RMS, typically used for low-voltage control and signaling, and exempt from many Chapter 3 wiring requirements.
- NEC Article 725
- The National Electrical Code article governing Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits, including cable and conductor requirements.
- Plenum-rated cable
- Cable marked CMP that has low smoke and flame spread characteristics and is approved for installation in air-handling spaces without conduit.
- Conduit fill 40 percent
- The maximum cross-sectional area of three or more conductors or cables allowed in a conduit, per NEC Chapter 9, Table 1.
- Horizontal cable limit
- TIA-568 specifies a maximum of 90 meters (295 feet) of horizontal cable plus 10 meters (33 feet) of patch cords for a 100-meter channel.
- TIA-606 labeling
- The standard requiring unique, machine-printed identifiers for cables, termination points, and patch panel ports to ensure accurate administration of cabling infrastructure.
- Fiber loss budget
- The sum of connector losses, splice losses, and fiber attenuation over a link, used to verify that the link will operate within the receiver sensitivity.
- Smoke detector spacing
- NFPA 72 requires detectors spaced no more than 30 feet apart on smooth ceilings, 15 feet from walls, and adjusted for ceiling height.
- NAC appliance rating
- Notification appliances must produce 15 dBA above ambient or 5 dBA above a maximum 105 dBA, whichever is greater, measured at 10 feet.
- Class A circuit
- A fire alarm circuit that continues to operate during a single open or ground fault, as defined in NFPA 72 Chapter 12.
- Fail-safe lock
- An access control lock that unlocks when power is removed, providing egress safety and typically used on perimeter doors.
- PoE 802.3at
- The IEEE standard for Power over Ethernet Plus, supplying up to 25.5 watts per port, used for PTZ cameras and access control readers.
- OSDP protocol
- Open Supervised Device Protocol, a secure encrypted communication standard for access control readers that replaces the older Wiegand interface.
- 70V speaker system
- A constant-voltage distributed audio system using transformers to step up voltage, reducing line loss over long cable runs compared to 25V systems.
- HDMI 2.1
- A video interface standard supporting 48 Gbps bandwidth, 8K at 60 Hz, and 4K at 120 Hz, used for high-resolution AV distribution.
- RS-485
- A differential serial bus standard supporting up to 32 unit loads and 1,200 meters at lower baud rates, commonly used for control systems.
- Ground rod minimum
- NEC 250.52 requires a ground rod to be at least 8 feet long and 5/8 inch in diameter, and bonded to the building grounding electrode system.
- SPD Type 1
- A surge protective device installed at the service entrance, designed to handle high surge currents and protect downstream equipment.
- Single-point ground
- A grounding configuration for communications systems that bonds all equipment to one reference point to prevent ground loops and circulating currents.
- Wire map test
- A cabling certification test that verifies pin-to-pin connections, detects opens, shorts, crossed pairs, and split pairs in twisted-pair cable.
- OTDR
- Optical Time Domain Reflectometer, a test instrument that measures fiber loss and locates faults by analyzing backscattered light along the fiber.
- As-built documentation
- Final project records including cable schedules, panel schedules, test results, and device addresses, retained for the life of the system.
- CSLB C-7 license
- A California Contractors State License Board classification for low-voltage systems contractors, required for installation of communications and alarm wiring.
- Title 24 Part 3
- The California Electrical Code, adopted from the National Electrical Code with state amendments, governing electrical installations in California.
- Ground resistance 25 ohms
- NEC 250.53 requires a single ground rod to have a resistance of 25 ohms or less, or be supplemented by an additional electrode.
- ACR
- Attenuation-to-Crosstalk Ratio, calculated as insertion loss subtracted from near-end crosstalk in dB, indicating signal-to-noise margin in cabling.
- Wiegand interface
- A legacy access control communication protocol using two data wires and a ground, now being replaced by OSDP for security reasons.
- TDR
- Time Domain Reflectometer, a test instrument that locates faults in metallic cables by measuring the reflection time of a pulse and using velocity of propagation.
- GFCI requirement
- California OSHA Title 8 Section 2395 requires ground-fault circuit interrupter protection for temporary power and extension cords used outdoors or in wet locations.
- FPLR cable
- Fire alarm cable rated for riser installation, with flame-retardant characteristics suitable for vertical runs in a building, per NEC 760.
- Bend radius four times
- The minimum bend radius for 4-pair UTP cable during installation is four times the cable diameter; after installation it is one times the diameter.