OBC Large Buildings · Put your knowledge to work in context.

All case studies

Sprinklered Warehouse Addition and Construction Type

A developer owns a one-storey, 4,500 m² warehouse of combustible construction that has been fully sprinklered throughout its life. A 1,200 m² rear addition is proposed. The design team wants to keep the entire building combustible, but the site is tight: the new rear wall will sit 4.5 m from the property line, and the existing east wall already has unprotected openings 3.2 m from a neighbouring building. The owner asks whether the sprinkler system alone can justify the addition without changing construction type, and whether the proximity of the new wall and existing openings forces any change. The building official has flagged both the size/construction question and the exposing building face question for review.

1. Evaluate whether the proposed combustible construction is acceptable for the enlarged building, and identify what the sprinkler system does and does not permit.

Read the worked answer

The sprinkler system is not a substitute for construction type. In a code framework where the permitted area for combustible (Group F-3 type) construction is set out in a table and increased by sprinkler protection, you must first establish the base permitted area for the occupancy and construction type, then apply the permitted increase for a full sprinkler system, then check the proposed total area (4,500 + 1,200 = 5,700 m²) against that increased limit. If the increased limit is exceeded, the options are: (a) upgrade part or all of the building to noncombustible construction, (b) introduce a fire wall/fire separation creating two buildings, or (c) reduce the addition. Do not assume sprinklers make unlimited combustible area acceptable; sprinklers permit a defined increase, not an exemption. Also confirm the sprinkler design meets the required standard and covers the addition, and that the water supply is adequate. The correct answer is a calculation and comparison, not a yes/no based on the presence of sprinklers.

2. Assess the exposing building face issues at the new rear wall and the existing east wall openings, and state what remedial measures are available.

Read the worked answer

Two separate exposing building face problems exist. First, the new rear wall at 4.5 m from the property line: determine the required fire-resistance rating and the maximum permitted percentage of glazed openings for that limiting distance, based on the occupancy, the area of the exposing building face, and whether the face is sprinklered. If the proposed wall has more or larger openings than permitted, remedies include increasing the fire-resistance rating of the wall assembly, reducing the area of unprotected openings, or installing limited-combustible cladding. Second, the existing east wall openings at 3.2 m from the neighbouring building: this is a pre-existing nonconformity. The addition must not worsen it, and if the work triggers upgrading, the openings may need protection (rated closures, sprinklers on the exposing side, or reduced opening area). The key judgement is that limiting distance drives both the rating and the opening percentage, and the more restrictive of the two governs.