Lockout/tagout
A procedure that isolates all energy sources, verifies zero energy, and applies a personal lock and tag before maintenance begins on an instrument loop.
Intrinsic safety
A protection method that limits electrical energy into a hazardous-area circuit so that no spark or heat can ignite the surrounding flammable atmosphere.
Temperature class
A T-code assigned to hazardous-area equipment that states the maximum surface temperature; it must not exceed the ignition temperature of the gas present.
Arc-flash boundary
The distance from energized equipment at which incident energy equals 1.2 cal/cm²; PPE selection is based on the energy inside this boundary.
CAT rating
A multimeter safety rating that states the maximum transient overvoltage the meter can withstand in a given circuit category, from CAT I to CAT IV.
Loop calibrator
A portable instrument that sources or reads 4-20 mA and often HART signals, used to stroke a valve or verify a transmitter without the control system.
Calibration traceability
A documented chain linking the calibration standard used to a national metrology institute, with an accuracy ratio of at least 4:1 to the device under test.
Megohmmeter
An instrument that applies a high DC voltage to measure insulation resistance; it must be disconnected from electronic instruments before testing.
Ohm's law
The relationship V = IR between voltage, current and resistance in a circuit; combined with P = VI it gives power in watts.
4-20 mA loop
A current-loop signal in which 4 mA represents 0% and 20 mA represents 100% of span; a 250 ohm resistor converts it to 1-5 V.
Cold-junction compensation
A correction applied to a thermocouple circuit that accounts for the temperature of the reference junction so the reading reflects the measuring junction only.
PT100 RTD
A resistance temperature detector with 100 ohms at 0 °C; its resistance rises about 0.385 ohm per °C near ambient temperature.
Differential pressure flow
A flow measurement in which the square of the flow rate is proportional to the pressure drop across an orifice or venturi; square-root extraction linearizes it.
Level by DP
A level measurement using the hydrostatic relationship delta-P equals density times gravity times height; reference-leg fill and density must be known.
Thermocouple
A temperature sensor made of two dissimilar metals that generates a small EMF proportional to the temperature difference between its junctions.
pH two-point calibration
A calibration using two buffer solutions, typically pH 4 and pH 7, to set the slope and offset of a glass electrode.
Valve Cv
The flow coefficient equal to the volume of water in US gallons per minute that passes through a fully open valve at a pressure drop of one psi.
Cavitation
A condition in which the pressure at the vena contracta of a valve falls below the liquid vapor pressure, forming bubbles that collapse and damage the trim.
Fail-closed valve
A valve whose actuator spring drives it closed when air or power is lost; also called air-to-open.
Valve positioner
A device that compares the controller signal with actual stem position and adjusts actuator air to reduce friction and hysteresis effects.
PID control
A control algorithm whose output combines proportional, integral and derivative terms acting on the error between setpoint and measured value.
Cascade control
A control scheme in which the output of a primary controller becomes the setpoint of a secondary controller that regulates a faster inner loop.
Feedforward control
A control strategy that measures a disturbance and adjusts the manipulated variable before the error appears, usually trimmed by feedback.
PLC scan cycle
The repeated sequence of reading inputs, executing the program and updating outputs; its duration affects the response of the control loop.
Dead time
The transport delay between a change in the manipulated variable and the first measurable response; it limits the gain a loop can tolerate.
Ziegler-Nichols method
A tuning technique that finds the ultimate gain and period at sustained oscillation, then sets controller parameters from fixed ratios of those values.
Bumpless transfer
A switch between manual and automatic control in which the controller output tracks the manual value so the final element does not move abruptly.
I/P transducer
A device that converts a 4-20 mA electrical signal into a proportional 3-15 psi pneumatic signal for a valve actuator or pneumatic controller.
Pascal's law
The principle that pressure applied to a confined fluid is transmitted equally in all directions, so force equals pressure times piston area.
Nernst equation
The relationship giving the electrode potential of a pH cell, about 59 millivolts per pH unit at 25 °C.
LEL detector
A combustible gas sensor, often catalytic bead or infrared, calibrated so that alarms occur at a percentage of the lower explosive limit.
P&ID instrument bubble
A circle on a piping and instrumentation diagram containing a tag; a horizontal line through it means the instrument is field-mounted.