Electrical and Electronic Fundamentals tests DC and AC circuit analysis, components, signal transmission, grounding, and troubleshooting. Expect Ohm's law, series/parallel circuits, power, impedance, transformers, diodes, transistors, op amps, digital logic, 4–20 mA loops, shielding, and intrinsic safety.

Core rules

  • Ohm's law: V = IR. Power: P = VI = I²R = V²/R. In series, current is common and voltages add; in parallel, voltage is common and currents add.
  • A 4–20 mA transmitter is a current source. The receiver develops a voltage across a sense resistor; the loop supply must exceed the sum of transmitter minimum voltage and all voltage drops at 20 mA.
  • Ground shields at one end to avoid ground loops unless the design requires otherwise. Separately identify safety ground, signal common, and shield.
  • Use Thevenin or Kirchhoff's laws for bridge and divider circuits. Check polarity before replacing electrolytic capacitors or diodes.

Worked example

A 24 VDC supply powers a two-wire transmitter with a minimum operating voltage of 12 V. The loop has a 250 Ω sense resistor and 50 Ω of cable resistance. At 20 mA, total resistance is 300 Ω, so drop is 0.020 × 300 = 6 V. Available transmitter voltage is 24 − 6 = 18 V, which is above 12 V, so the loop should operate. If the cable resistance were 500 Ω, total drop would be 0.020 × 750 = 15 V, leaving only 9 V; the transmitter could drop out at high current. The fix is a larger supply, shorter/larger conductor, or lower burden-not simply replacing the transmitter.

Traps

Measuring current by placing a meter in parallel, ignoring burden voltage, assuming 4 mA is always "zero" for every variable, and connecting a shield at both ends are frequent errors. Also distinguish AC impedance from DC resistance when capacitors or inductors are present.

Key points

  • Apply Ohm's and Kirchhoff's laws systematically.
  • Budget loop voltage at 20 mA.
  • Ground shields to prevent loops.
  • Observe polarity and component ratings.
  • Separate safety ground from signal common.