Occupational Skills and Safety

  • WHMIS 2015 uses pictograms, signal words, and SDS Sections 1-16; Section 8 lists exposure controls and PPE, Section 9 lists physical properties.

  • Asbestos-containing insulation is presumed in buildings built before the 1990s in Canada; only a qualified person may confirm by bulk sampling, and friable material requires a Type 3 asbestos abatement procedure.

  • Respirable crystalline silica exposure limit in most Canadian jurisdictions is 0.025 mg/m3 as an 8-hour TWA; wet cutting and local exhaust ventilation are the primary controls.

  • Fibreglass and mineral wool irritation is mechanical, not chemical; loose-fitting clothing covering the arms and neck plus barrier cream reduces fibre contact.

  • Fall protection is required at 3 m in most jurisdictions (2.4 m in some); a full-body harness with shock-absorbing lanyard limits free fall to 1.8 m or less.

  • A confined space requires a hazard assessment, entry permit, atmospheric testing for O2 (19.5-23%), LEL, H2S and CO, plus a standby attendant outside.

  • Scaffold guardrails sit at 0.9-1.1 m top rail with a mid-rail; the platform must be fully planked and within 300 mm of the work face.

  • Ladder setup uses the 4:1 rule: base set out 1 m for every 4 m of working height, extending 1 m above the landing.

Quick reference

Planning and Preparation

  • Insulation thickness is selected from the mechanical insulation tables (MIS) or ASHRAE 90.1 for the pipe size, operating temperature, and ambient design conditions.

  • Heat loss calculation: Q = 2 pi k L (T1 - T2) / ln(r2/r1) for a cylindrical layer; add layers in series by summing thermal resistances.

  • Personal protective equipment and material takeoff are ordered before mobilization: pipe length by diameter, fitting counts, and 5-10% waste allowance.

  • Surface temperature above 60 C on accessible surfaces triggers personnel protection; below 13 C with high humidity triggers condensation control design.

  • Vapour barrier position: on a cold pipe the barrier goes on the warm (outer) side; on a cold service the jacket and vapour retarder must be continuous and sealed.

  • Cellular glass or foamglas is specified for below-ambient and cryogenic service; mineral wool for high temperature above 450 C.

  • Work sequencing follows the trade stack: hangers and supports, then equipment, then large-bore piping, then small-bore and fittings, then finishing and cladding.

Quick reference

Removal and Surface Preparation

  • Before removal, isolate and lock out the system, verify zero energy, and confirm the insulation is not asbestos by label, register, or bulk sample.

  • Removal of old insulation is done top-down and bagged in 6-mil poly; friable ACM waste goes into labelled, sealed containers per jurisdiction.

  • Carbon steel surfaces are cleaned to SSPC-SP2 (hand) or SP3 (power) before coating; mill scale and rust must be removed for coating adhesion.

  • Surface temperature must be at least 3 C above dew point and above 10 C for coating application; below that, use a compatible primer or wait.

  • Galvanic corrosion occurs where copper or brass contacts aluminum jacketing; a separation layer or stainless jacketing prevents it on wet or outdoor service.

  • Stress corrosion cracking of austenitic stainless under insulation (chloride SCC) requires low-chloride insulation and a coating on the steel for 60-175 C service.

  • Insulation removed from a line is tagged and recorded so the same thickness and material can be reinstated; never substitute a lower temperature rating.

Quick reference

Insulation Application and Installation

  • Pipe insulation is applied with joints staggered and tightly butted; each layer's longitudinal seam is offset at least 90 degrees from the layer below.

  • Fitting insulation uses mitred or segmented pieces; a 90-degree elbow is covered with a minimum of 3 segments for small bore and more for large bore.

  • Mineral wool and fibreglass are secured with 16-gauge (1.6 mm) wire or stainless bands at 225-300 mm centres, plus one band within 50 mm of each end.

  • Cellular glass and foam insulation are adhered with the manufacturer's adhesive and sealed with vapour-retarder mastic on all joints for cold service.

  • Expansion and contraction allowance: leave a gap at flanges and at expansion joints; a 100 C temperature change on 10 m of steel moves about 12 mm.

  • Insulation on valves and flanges uses removable boxes or blankets so the fitting can be serviced without destroying the insulation.

  • Vertical runs above 3 m require support rings or spacers at intervals to prevent the insulation from sliding down the pipe.

  • Double-layer application: inner layer seams are taped or wired, outer layer seams are offset and the outer layer carries the jacket and vapour retarder.

Quick reference

Finishing, Cladding, and Jacketing

  • Aluminum jacketing is installed with the overlap facing away from the prevailing weather; minimum 50 mm overlap on horizontal runs and 75 mm on vertical.

  • Jacket bands are spaced at 300 mm on straight runs and 150 mm near fittings; band tension is set so the jacket cannot be lifted by hand.

  • Stainless steel jacketing is specified for coastal, chemical, and high-chloride environments to avoid aluminium corrosion.

  • PVC or ASJ (all-service jacket) is used indoors where a clean vapour-tight finish is required; it is not suitable above 65 C or outdoors.

  • Mastic coatings and vapour-retarder mastic are applied in two coats on cold service, with the first coat worked into the joint and the second finishing the surface.

  • Cladding on outdoor lines is installed with a weatherproof seal at penetrations, and the low point of the jacket is left unsealed for drainage.

  • Insulation cement is mixed to a putty consistency and applied in thin coats, drying between coats to prevent cracking.

Quick reference

Firestopping and Vapour Barriers

  • Firestopping systems are listed by assembly (UL or ULC) and must match the pipe material, diameter, insulation type, and annular space tested.

  • A firestop seal must be installed on both sides of a fire-rated wall or floor penetration unless the tested system states otherwise.

  • Intumescent firestop materials expand on heating to close the annular gap when plastic pipe burns away; non-intumescent sealant is used for metal pipe.

  • Vapour barrier continuity is tested by a dew-point check: the surface temperature of the barrier must stay above the dew point of the surrounding air.

  • On cold service, all joints, seams, and penetrations of the vapour retarder are sealed with a compatible mastic; a single unsealed joint defeats the barrier.

  • Permeance of the vapour retarder is expressed in ng/(Pa s m2); lower permeance means better resistance to moisture vapour flow.

  • Firestop labels record the system number, the tested annular space, and the required thickness; the installed assembly must match the label exactly.

Quick reference

Inspection, Repair, and Maintenance

  • Inspection of finished insulation checks thickness, joint tightness, band spacing, jacket overlap, and vapour-retarder continuity against the specification.

  • Damaged jacketing is repaired before insulation damage; a crushed or dented jacket traps moisture and leads to CUI on carbon steel.

  • CUI (corrosion under insulation) inspection focuses on 60-175 C service, wet or cyclic conditions, and low points where water collects.

  • Repair of a vapour barrier uses the same mastic and tape as the original system; a mismatched product can fail the permeance requirement.

  • Thermal imaging of insulation finds missing sections and wet insulation as hot or cold spots; it is done under steady load, not during startup.

  • A repair record should include the location, the original material and thickness, the repair method, and the date so the next inspection can compare.

  • Insulation that has been wetted loses R-value; mineral wool and fibreglass must be replaced, not dried in place, when saturated.