- Ozone Depletion Potential
- A relative number comparing a substance's ability to destroy stratospheric ozone, with CFC-11 set at 1.0. HCFCs such as R-22 have a value below 1.
- Global Warming Potential
- A relative measure of how much heat a greenhouse gas traps over 100 years compared with carbon dioxide, which is set at 1. R-410A is roughly 2088.
- 80% Cylinder Fill Rule
- Refrigerant cylinders must never be filled beyond 80% of their capacity by liquid volume, leaving vapour space so liquid expansion with temperature does not rupture the cylinder.
- Confined Space Atmospheric Testing
- Before entry, test oxygen between 19.5 and 23 percent, flammability below 10 percent of the lower explosive limit, and toxicity, with a standby attendant outside.
- Micron Gauge
- An instrument measuring absolute pressure in microns, where one atmosphere is about 760,000 microns. It verifies evacuation depth and standing vacuum on a refrigeration system.
- Standing Vacuum Test
- After evacuating below 500 microns, isolate the pump and confirm the pressure rise stays small over about ten minutes, proving the system is dry and leak-free.
- Nitrogen Purge While Brazing
- A slow flow of dry nitrogen through the tubing during brazing displaces oxygen, preventing internal oxidation scale that would later clog driers, valves, and screens.
- Clamp-On Ammeter
- A meter whose jaws surround a conductor to measure current without breaking the circuit. It is used to check compressor, fan, and heater amp draw against nameplate values.
- Ton of Refrigeration
- A cooling rate equal to 12,000 Btu per hour, 200 Btu per minute, or 3.517 kilowatts, based on melting one ton of ice in 24 hours.
- Superheat
- The difference between the actual suction line temperature and the saturated evaporating temperature at the same pressure. It confirms the evaporator is fully fed with liquid.
- Subcooling
- The difference between the condensing temperature and the liquid line temperature. It confirms the condenser has enough liquid refrigerant and the charge is adequate.
- Latent Heat
- Heat added or removed that changes a substance's state without changing its temperature, such as boiling liquid refrigerant into vapour inside the evaporator coil.
- Relative Humidity
- The ratio of actual water vapour pressure in air to the saturation vapour pressure at the same dry-bulb temperature, expressed as a percentage of saturation.
- Potential Relay
- A start relay whose coil senses rising back-EMF across the start winding. It opens the start capacitor circuit once the motor reaches running speed.
- PSC Motor
- A permanent split capacitor motor with a run capacitor in series with the start winding. It has moderate starting torque and is common on fans and small compressors.
- Thermistor
- A solid-state temperature sensor whose resistance changes predictably with temperature, feeding a controller that interprets the resistance as a temperature reading.
- Contactor
- An electrically operated switch whose coil is energized by the control circuit, closing heavy-duty contacts that supply power to compressors, fans, or heaters.
- ACR Copper Tubing
- Copper tubing manufactured, cleaned, and capped for refrigeration service, sized by outside diameter, and kept sealed until installation to prevent moisture and dirt entry.
- Brazing Versus Soldering
- Brazing joins tubing with filler melting above 450 degrees Celsius and is required for refrigerant lines. Soldering melts below that and is unsuitable for system pressures.
- Suction Line P-Trap
- A trap installed at the bottom of a vertical suction riser to collect oil and return it to the compressor, preventing oil logging and loss of lubrication.
- Filter Drier
- A device in the liquid line containing desiccant and a screen that removes moisture and particles. The flow arrow must point in the direction of refrigerant flow.
- POE Lubricant
- Polyol ester oil used with HFC and HFO refrigerants. It is hygroscopic, so containers must stay sealed and systems must be evacuated thoroughly to avoid moisture.
- Refrigerant Reclamation
- Processing recovered refrigerant to meet AHRI 700 purity standards, performed by a certified reclaimer. Reclaimed refrigerant can be resold and reused in any system.
- Near-Azeotropic Blend
- A refrigerant mixture whose components have slightly different boiling points, causing temperature glide. R-410A must be charged as a liquid to prevent fractionation.
- Recovery Versus Recycling
- Recovery removes refrigerant from a system for storage. Recycling cleans it on site with oil separation and filtration but does not restore it to new specification.
- Triple Evacuation
- An evacuation method using three vacuum cycles separated by dry nitrogen breaks, used on systems suspected of containing moisture, to drive out water vapour.
- Weigh-In Charging
- Charging refrigerant by weight using a scale and the nameplate charge, the most accurate method, then verified by superheat or subcooling readings.
- External Static Pressure
- The resistance to airflow measured across the blower and duct system. It is compared with the fan performance curve to determine actual delivered airflow in CFM.
- High Discharge Pressure Causes
- Dirty or blocked condenser, high ambient temperature, non-condensable gases, overcharge, or restricted condenser airflow. Each raises head pressure and compressor current.
- Low Suction Pressure Causes
- Restricted liquid line or filter drier, undercharge, faulty expansion valve, iced evaporator, or low heat load. Diagnose by checking superheat and airflow.
- Pump-Down Control
- A liquid line solenoid valve closes on thermostat satisfaction while the compressor runs until low pressure is reached, storing refrigerant in the receiver and preventing migration.
- Sensible Heat Ratio
- The sensible heat divided by the total heat of a load or coil. Equipment selection must match the space ratio to control both temperature and humidity properly.